B-Low Ambient Pressure Switch Setting (S11)

One of two types of pressure switches are provided. The
Ranco switch has one square and one round adjustment

knob and the Alco switch has two square  adjustment
knobs.

Ranco Model

The low ambient pressure switch provided in the kit is

factory set for 285 psig (1965 kPa) cut-in and 140 psig
(965 kPa) cut-out.
If  necessary,  adjust  low  ambient  pressure  switch  as
follows:
 1-Rotate round knob to set cut-in pressure. Refer to right

set  of  indicating  numbers  on  face  of  control.  See
figure 3.

 2- Rotate square knob to set differential indicator to 145

psig (999 kPa). Refer to left set of indicating numbers.

Alco Model

If  necessary,  adjust  low  ambient  pressure  switch  as

follows:
 1-Rotate the square knob located on the left to set cut-in

pressure. Refer to left set of indicating numbers on

face of control. See figure 2.

 2- Rotate the square knob located on the right to set

differential indicator to 145 psig (999 kPa). Refer to
right set of indicating numbers.

 3- Use only terminals 1 and 4 when connecting wiring.

NOTE  -  Disregard  Cut  out  minus  Diff.  is  Cut  In"

statement on face of control. This does not apply in this
application.

C-Low Ambient Relay (K58)

 1- Install low ambient relay in control box.

LOW AMBIENT PRESSURE SWITCH S11 DETAIL

SQUARE DIFFERENTIAL

ADJUSTMENT KNOB

FIGURE 2

ROUND CUT-IN

ADJUSTMENT

KNOB

PRESSURE SWITCH IS FACTORY-SET AT 285 PSIG CUT-IN

AND 145 PSIG DIFFERENTIAL (140 PSIG CUT-OUT)

CUT-IN PRESSURE

READOUT ON

RIGHT

DIFFERENTIAL

PRESSURE READĆ

OUT ON LEFT

SQUARE DIFFERENTIAL

ADJUSTMENT KNOB

ROUND CUT-IN

ADJUSTMENT

KNOB

CUT-IN PRESSURE

READOUT ON LEFT

DIFFERENTIAL

PRESSURE READĆ

OUT ON RIGHT

RANCO MODEL

ALCO MODEL

Summary of Contents for LB57113BM

Page 1: ...ures no lower than 30 F Lennox recommends a belly band style crankcase heater P 8 8852 240v 45w be added to compressors which do not have one A freezestat LB 62858CA should also be added to any system...

Page 2: ...knob located on the left to set cut in pressure Refer to left set of indicating numbers on face of control See figure 2 2 Rotate the square knob located on the right to set differential indicator to 1...

Page 3: ...priate wiring diagram in figures 3 through 13 for wiring connections 8 K4 DEFROST RELAY 9 7 5 6 4 2 3 1 9 7 6 4 3 1 S11 LOW AMBIENT PRESSURE SWITCH L1 REVERSING VALVE B4 K58 LOW AMBIENT RELAY FIGURE 3...

Page 4: ...Page 4 FIGURE 4 TYPICAL SINGLE COMPRESSOR HEAT PUMP UNIT WIRING DIAGRAM S11 LOW AMBIENT CONTROL SWITCHES OUTDOOR FAN DIRECTLY SEE PICTORIAL FIGURE 3...

Page 5: ...1 9 7 6 4 3 1 L1 REVERSING VALVE K10 CONDENSER FAN CONTACTOR TO 24V COM K45 REVERSING VALVE RELAY HP17 953 1353 TWO SPEED S11 LOW AMBIENT PRESSURE CONTROL SWITCHES OUTDOOR FAN S THROUGH A RELAY OR CO...

Page 6: ...Page 6 FIGURE 6 TYPICAL SINGLE COMPRESSOR HEAT PUMP UNIT WIRING DIAGRAM S11 LOW AMBIENT CONTROL SWITCHES OUTDOOR FAN THROUGH A RELAY OR CONTACTOR PILOT CIRCUIT SEE PICTORIAL FIGURE 5...

Page 7: ...T3 B4 OUTDOOR FAN MOTOR 1 P35 J35 12 13 12 13 L1 REVERSING VALVE S11 LOW AMBIENT PRESSURE SWITCH COMP 1 FIELD WIRING FACTORY WIRING C1 CAPACITOR REMOVE THIS WIRE 4 1 FIGURE 8 TYPICAL SINGLE COMPRESSO...

Page 8: ...Page 8 TYPICAL SINGLE COMPRESSOR PACKAGED HEAT PUMP UNIT WIRING DIAGRAM S11 LOW AMBIENT CONTROL SWITCHES OUTDOOR FAN DIRECTLY CHP16 2 TO 5 TON UNITS FIGURE 9 SEE PICTORIAL FIGURE 7...

Page 9: ...L 1 K4 DEFROST RELAY 9 7 5 6 4 3 1 9 7 6 4 3 1 S11 LOW AMBIENT PRESSURE SWITCH L1 REVERSING VALVE B4 K58 LOW AMBIENT RELAY TO 24V COM OUTDOOR FAN MOTOR TO C12 TERMINAL F REMOVE THIS WIRE FIELD WIRING...

Page 10: ...Page 10 FIGURE 11 SEE PICTORAL FIGURE 10 TYPICAL SINGLE COMPRESSOR TWO STAGE SINGLE PHASE HEAT PUMP UNIT WIRING DIAGRAM S11 Low Ambient Control Switches Outdoor Fan Directly...

Page 11: ...9 7 6 4 3 1 S11 LOW AMBIENT PRESSURE SWITCH L1 REVERSING VALVE B4 K58 LOW AMBIENT RELAY TO 24V COM OUTDOOR FAN MOTOR REMOVE THIS WIRE FIELD WIRING FACTORY WIRING TO K10 1 TERMINAL 3 2 3 1 THREE PHASE...

Page 12: ...Page 12 FIGURE 13 SEE PICTORAL FIGURE 12 TYPICAL SINGLE COMPRESSOR TWO STAGE THREE PHASE HEAT PUMP UNIT WIRING DIAGRAM S11 Low Ambient Control Switches Outdoor Fan Directly...

Reviews: