Page 1
11/02
*2P1102*
504,186M
*P504186M*
E
2000 Lennox Industries Inc.
Dallas, Texas, USA
HS40 Condensing Unit
HS40 condensing units use R407C which is an ozone
friendly HFC refrigerant. This unit must be installed with a
matching indoor coil and line set as outlined in the Lennox
Engineering Handbook. HS40 condensing units are de
signed for use in expansion valve systems only. They are
not designed to be used in RFC systems. An expansion
valve and filter drier approved for use with R407C have
been shipped with the unit. These components must be
installed prior to unit operation.
WARNING
Refrigerant can be harmful if it is inhaled. Refriger
ant must be used and recovered responsibly.
Failure to follow this warning may result in personal
injury or death.
WARNING
International legislation bans the intentional venting
of refrigerant (CFCs and HCFCs). Approved methods
of recovery, recycling or reclaiming must be fol
lowed. Fines and/or incarceration may be levied for
noncompliance.
INSTALLATION
INSTRUCTIONS
HS40 SERIES UNITS
CONDENSING UNITS
504,186M
11/2002
Supersedes 4/2000
Table of Contents
HS40 Condensing Unit
1
. . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List
1
. . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Unit
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Plumbing
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flushing Existing Line Set and Indoor Coil
4
. . . . . . . .
Liquid & Suction Line Service Valves
6
. . . . . . . . . . . . .
Leak Testing
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuation & Dehydration
7
. . . . . . . . . . . . . . . . . . . . . .
Start−Up
8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charging
8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation
10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance
10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up & Performance Check List
11
. . . . . . . . . . . . . .
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Shipping and Packing List
1 − Assembled HS40 condensing unit
1 − Bag assembly:
1 − Sight glass
1 − 5/16−3/8 inch adapter
1 − 45° elbow
1 − Expansion valve (approved for use with R407C)
1 − Drier (approved for use with R407C systems)
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
WARNING
This equipment must only be installed and serviced
by properly qualified personnel. Equipment contains
dangerous voltages and moving parts. Always
switch off power supply before opening any access
panel. Electrical control panel doors and fan access
door must be locked to prevent unauthorized access
at beginning of instruction.
Litho U.S.A.