background image

Page 7

TABLE 6

3/8" LIQUID LINE SERVICE VALVE TORQUE SPECS*

Manufacturer

Service Port

Cap Torque

Stem Cap

Torque

Seating Torque

Front Seat

PARKER

(Forged Body)

PRIMORE

(Brazed Body)

9Ć12 lbs./ft.

3Ć5 lbs./ft.

20Ć24 lbs./ft.

18Ć22 lbs./ft.

8Ć10 lbs./ft.

7Ć11 lbs./ft.

*Tighten each component firmly; if leaks are evident, tighten to

appropriate torque.

2 - Suction Line Service Valve

A full service suction line service valve is used on all HS24 seĆ
ries units. Suction valves are nonĆbackseating type. Three difĆ

ferent manufacturers of valves may be used. All suction line
service  valves  function  the  same  way,  differences  are  in

construction. Valves manufactured by Aeroquip and Parker

are forged assemblies. Valves manufactured by Primore are
brazed together. Valves are not rebuildable. Defective valves

must be replaced. The suction line service valve is illustrated

in figures 11 and 12.

SUCTION LINE SERVICE VALVE (VALVE OPEN)

FIGURE 11

SCHRADER VALVE

SERVICE PORT

SERVICE

PORT

CAP

STEM CAP

INSERT HEX WRENCH

HERE

SNAP RING

SUCTION LINE SERVICE VALVE (VALVE CLOSED)

FIGURE 12

STEM

CAP

SCHRADER VALVE

SERVICE PORT

SERVICE PORT CAP

(VALVEĆ

FRONT SEATED)

NOTE: WHEN VALVE IS FRONT SEATED THE SCHRADER

PORT IS NOT ISOLATED FROM THE SYSTEM.

SNAP RING

The valve is equipped with a service port. A schrader valve
is factory installed. A service port cap is supplied to protect
the schrader valve from contamination and assure a leak
free seal.
The suction line service valve is a front-seating valve and
does not backseat.

WARNING

Suction  valves  are  nonĆbackseating.  Do  not  atĆ

tempt to backseat this valve. Attempts to backseat

this  valve  will  cause  snap  ring  to  explode  from

valve body under pressure of refrigerant. PersonĆ

al injury and unit damage will result.

To Access Schrader Port:

 1 - Remove service port cap with an adjustable wrench.
 2 - Install in reverse order. Tighten firmly. See table 7 for

service port cap torque values.

To Open Suction Line Service Valve:

 1 - Remove stem cap with an adjustable wrench.
 2 - Insert a 5/16" hex wrench into the stem.
 3 - Back  the  stem  out  counterclockwise  until  the  valve

stem just touches the retaining ring.

 4 - Replace stem cap, tighten firmly. See table 7 for stem

cap torque specifications.

TABLE 7

SUCTION LINE SERVICE VALVE TORQUE SPECS*

Size

Stem Cap

Torque

1/2"

6Ć10 lbs./ft.

Manufacturer Seating Torque

Front Seat

Service Port

Cap

Parker**

Aeroquip

5/8"

Parker**

3/4"

Primore
Aeroquip

7/8"

Parker**

1 1/8"

Primore
Aeroquip

Primore

18Ć20 lbs./ft.

18Ć20 lbs./ft.
18Ć20 lbs./ft.

18Ć22 lbs./ft.
22Ć25 lbs./ft.

6Ć10 lbs./ft.

6Ć10 lbs./ft.
6Ć10 lbs./ft.
6Ć10 lbs./ft.

6Ć10 lbs./ft.

6Ć10 lbs./ft.

6Ć10 lbs./ft.

12Ć16 lbs./ft.

12Ć15 lbs./ft.

15Ć20 lbs./ft.
12Ć15 lbs./ft.
12Ć16 lbs./ft.

15Ć20 lbs./ft.

15Ć20 lbs./ft.

15Ć21 lbs./ft.

**Parker valves have a forged body, Primore and Aeroquip valves have a

brazed body.

*Tighten each component firmly; if leaks are evident, tighten to

appropriate torque.

18Ć24 lbs./ft.

18Ć24 lbs./ft.

18Ć24 lbs./ft.

To Close Suction Line Service Valve:

 1 - Remove stem cap with an adjustable wrench.
 2 - Insert a 5/16" hex wrench into the stem.
 3 - Turn stem in clockwise to seat the valve. Tighten firmly.

See table 7 for valve seating torque specifications.

 4 - Replace stem cap, tighten firmly. See table 7 for stem

cap torque specifications.

Summary of Contents for HS24-141

Page 1: ...ated and operates only when required Several models are available in sizes ranging from 1 through 5 tons This manual is divided into sections which discuss the ma jor components refrigerant system cha...

Page 2: ...2 2 1 2 3 3 1 2 4 and 5 ton capacities All major components indoor blower coil must be matched according to Lennox recommendations for the compressor to be covered under warranty Refer to the En gine...

Page 3: ...ted at 3 4 VA with a 575 volt primary and a 460 volt secondary 5 Potential Start Relay K31 All HS24 461 511 651 series units use a potential relay which controls the operation of the starting circuit...

Page 4: ...n exhaust cycle At this instant the compression is begin ning 1 The roller rotates and compression continues 2 When the blade is fully extended the suction port is separated from the discharge port 3...

Page 5: ...s and up FIGURE 8 Access to the condenser fan motor on all units is gained by removing the six 6 screws securing the fan guard See figures 8 and 9 The condenser fan motor is attached to the fan guard...

Page 6: ...ve is a front and back seating valve When the valve is backseated the service port is iso lated from the system CAUTION The service port cap is used to seal the liquid line service valve Access to ser...

Page 7: ...Suction valves are non backseating Do not at tempt to backseat this valve Attempts to backseat this valve will cause snap ring to explode from valve body under pressure of refrigerant Person al injur...

Page 8: ...cuating the System 1 Attach gauge manifold Connect vacuum pump with vacuum gauge to center port of gauge manifold With both manifold service valves open start pump and evacuate indoor coil and refrige...

Page 9: ...move refrigerant from system to increase ap proach temperature TABLE 10 Model Liquid Temp Minus Ambient Temp F HS24 261 HS24 311 HS24 411 413 HS24 461 463 APPROACH METHOD EXPANSION VALVE SYSTEMS 4 1 8...

Page 10: ...0 9 8 6 5 4 2 15 15 14 14 13 13 12 12 11 10 10 9 20 19 19 18 18 17 17 16 15 15 14 13 17 16 16 15 15 14 14 13 13 12 11 10 D Oil Charge Table 4 on page 3 shows the factory oil charge in HS24 units V Mai...

Page 11: ...emand 5 Cooling demand is satisfied 6 Contactor K1 is de energized 7 K1 1 opens and compressor B1 and condenser fan motor B4 are de energized and stop immediately Cooling With Start Components 8 Cooli...

Page 12: ...i cal or electronic Cooling 1 Cooling demand initiates at Y1 in the thermostat 2 Compressor contactor K1 is energized 3 K1 1 N O closes energizing terminal C of compressor B1 and condenser fan motor B...

Reviews: