background image

Page 13

B – Evacuating the System

IMPORTANT

The compressor should never be used to evacuate
a refrigeration or air conditioning system.

 1– Attach gauge manifold. Connect vacuum pump (with

vacuum gauge) to center port of gauge manifold.
With both manifold service valves open, start pump
and evacuate indoor coil and refrigerant lines.

IMPORTANT

A temperature vacuum gauge, mercury vacuum
(U–tube), or thermocouple gauge should be used.
The usual Bourdon tube gauges are not accurate
enough in the vacuum range.

 2– Evacuate the system to 29 inches (737mm) vacuum.

During the early stages of evacuation, it is desirable
to stop the vacuum pump at least once to determine
if there is a rapid loss of vacuum. A rapid loss of
vacuum would indicate a leak in the system and a
repeat of the leak testing section would be necessary.

 3– After evacuating system to 29 inches (737mm), close

gauge manifold valves to center port, stop vacuum
pump and disconnect from gauge manifold. Attach
an upright nitrogen drum to center port of gauge
manifold and open drum valve slightly to purge line
at manifold. Break vacuum in system with nitrogen
pressure by opening manifold high pressure valve.
Close manifold high pressure valve to center port.

 4– Close nitrogen drum valve and disconnect from

gauge manifold center port. Release nitrogen
pressure from system.

 5– Connect vacuum pump to gauge manifold center

port. Evacuate system through manifold service
valves until vacuum in system does not rise above
29.7 inches (754mm) mercury (5mm absolute
pressure) within a 20–minute period after stopping
vacuum pump.

 6– After evacuation is complete, close manifold center

port, and connect refrigerant drum. Pressurize
system slightly with refrigerant to break vacuum.

C – Leak Testing (To Be Done Only After

Pump Down)

 1– Attach gauge manifold and connect a drum of dry

nitrogen to center port of gauge manifold.

 2– Open high pressure valve on gauge manifold and

pressurize line set /indoor coil to 150 psig (1034 kPa).

 3– Check lines and connections for leaks.

 

4– Release nitrogen pressure from the system,

correct any leaks and recheck.

CAUTION

When using dry nitrogen, a pressure reducing
regulator must be used to prevent excessive
pressure in gauge manifold, connecting hoses, and
within the system. Regulator setting must not
exceed 150 psig (1034 kpa). Failure to use a regulator
can cause equipment failure resulting in injury.

NOTE-If electronic leak detector is used, add a trace of
refrigerant to the nitrogen for detection by the leak
detector.

D – Charging

Charging must be done in the cooling mode. If system
is completely void of refrigerant, the recommended and
most accurate method of charging is to weigh the
refrigerant into the unit according to the total amount
shown on the unit nameplate.
If weighing facilities are not available or if unit is just
low on charge, the following procedure applies. RFC
and TXV systems use different charging methods.
Separate discharge and vapor line service ports are
provided outside the unit for connection of gauge
manifold during charging procedure as well as a
suction line service port.

1 – Expansion Valve Systems

The following procedures are intended as a general
guide for use with expansion valve systems only. For
best results, indoor temperature should be between 70 

°

F

and 80 

°

F. If outdoor temperature is 60 

°

F (16 

°

C) or above

the approach method of charging is used. If outdoor
temperature is less than 60 

°

F (16 

°

C) the subcooling

method of charging is used. Slight variations in charging
temperature and pressure should be expected. Large
variations may indicate a need for further servicing.

IMPORTANT

The following procedures require accurate
readings of ambient (outdoor) temperature, liquid
temperature and liquid pressure for proper
charging. Use a thermometer with accuracy of +2

°

F and a pressure gauge with accuracy of +5 PSIG.

APPROACH METHOD (TXV SYSTEMS)

(Ambient Temperature of 60

F [16

C] or Above)

 1 – Connect gauge manifold. Connect an upright

R–22 drum to center port of gauge manifold.

 2 – Record outdoor air (ambient) temperature.
 3 – Operate  indoor  and  outdoor  units  in  cooling

mode. Allow outdoor unit to run until system
pressures stabilize.

 4 – Make  sure  thermometer  well  is  filled  with

mineral oil before checking liquid line
temperature.

Summary of Contents for HP23 Series

Page 1: ...ting in the compressor The heater is temperature actuated and operates only when required A crankcase heater for HP23 141 units is optional but suction accumulator is factory installed Several models...

Page 2: ...lectrical Code manual to determine wire fuse and disconnect size requirements NOTE Extremes of operating range are plus 10 and minus 5 of line voltage ELECTRICAL DATA Model No HP23 413 HP23 461 1 HP23...

Page 3: ...AN MOTOR CONTROL BOX EXPANSION VALVE FIGURE 2 FAN SPIDER A Control Box Figures 3 and 4 FIGURE 3 DUAL CAPACITOR C12 START CAPACITOR C7 POTENTIAL RELAY K31 COMPRESSOR CONTACTOR K1 HP23 UNIT CONTROL BOX...

Page 4: ...t Capacitor C7 All single phase units use a start capacitor C7 C7 is located inside the unit control box see figure 3 C7 is wired in parallel with the compressor side of the dual capacitor See table 2...

Page 5: ...fter defrost begins the timer will de energize the defrost relay and the unit will resume normal operation If the defrost thermostat opens during the 14 minute defrost period the defrost relay is de e...

Page 6: ...and NOTE Hold function operates between thermostat demands only when defrost thermostat is closed This is the only time that the timer is operating 5 TST Pins Each board is equipped with a set of test...

Page 7: ...ing parts a rotor shaft eccentric roller and a blade See figure 11 The compressor rotor shaft is attached directly to the compressor motor The rotor shaft is permanently attached to an eccentric The e...

Page 8: ...t relay ELECTRICAL DATA tables in this manual show specifications for outdoor fans used in HP23s Two different mounting arrangements are used fan up and fan motor up see figures 14 and 15 Access to th...

Page 9: ...LIZER LINE DRIER WITH CHECK VALVE PRESSURE TAP FITTING WITH VALVE CORE DISTRIBUTOR TO OUTDOOR COIL STRAINER HP23 LIQUID LINE COMPONENTS REFRIGERANT FLOW IN COOLING MODE REFRIGERANT FLOW IN HEATING MOD...

Page 10: ...is not pressurized The service port cap can be removed and gauge connections can be made CAUTION The service port cap is used to seal the liquid line service valve Access to service port requires back...

Page 11: ...stem cap tighten firmly Tighten finger tight then tighten an additional 1 6 turn To Close Vapor Line Service Valve 1 Remove stem cap with an adjustable wrench 2 Using service wrench and 5 16 hex head...

Page 12: ...ULATOR 460 510 AND 650 ONLY DEFROST SWITCH S6 FILTER DRIER W INTERNAL CHECK VALVE MUFFLER LIQUID LINE FROM INDOOR COIL TO OUTDOOR COIL DISCHARGE LINE SERVICE PORT STRAINER LIQUID LINE SERVICE PORT REV...

Page 13: ...nitrogen pressure from the system correct any leaks and recheck CAUTION When using dry nitrogen a pressure reducing regulator must be used to prevent excessive pressure in gauge manifold connecting ho...

Page 14: ...Warmer Than Liquid Line HP23 261 HP23 311 HP23 411 413 CAN HP23 461 463 HP23 211 HP23 141 HP23 511 513 HP23 651 653 SUBCOOLING METHOD EXPANSION VALVE SYSTEMS AMBIENT TEMPERATURE BELOW 60 F 16 C 4 2 9...

Page 15: ...4 13 11 10 7 8 1 12 9 8 6 7 0 6 7 6 4 5 0 4 5 4 2 2 Approved matchups only HP23 410 CB CBH19 41 17 15 14 11 8 5 18 16 15 12 9 6 Condensing Temp F Warmer Than Liquid Line At Various Ambients 5 Place th...

Page 16: ...Page 16 HP23 SINGLE PHASE OPERATING SEQUENCE 1 2 3 5 6 4 7 8 9 10 11 12 13 15 16 17 18 19 20 21 22 23 24 25 27 26 1 20...

Page 17: ...K1 1 opens and compressor B1 and outdoor fan motor B4 are de energized and stop im mediately FIRST STAGE HEAT 11 Heating demand initiates at W1 in the ther mostat 12 24VAC energizes compressor contac...

Page 18: ...Page 18 HP23 THREE PHASE OPERATING SEQUENCE 1 2 3 5 6 4 7 8 9 10 11 12 13 15 14 16 17 18 19 20 21 22 23 24 25 26 1...

Page 19: ...the ther mostat 11 24VAC energizes compressor contactor K1 12 K1 1 N O closes energizing compressor and outdoor fan motor 13 Compressor B1 and outdoor fan motor B4 begin immediate operation END OF FIR...

Reviews: