background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

9

Figure 25

Outer pipe section installs in just the opposite
way; the lanced end goes down and each new
section goes OVER the outside of the previous
section installed (

Figure 26 ).

Figure 26

Security's chimney sections do not need to be
screwed together. Additional reinforcement is
not necessary except in certain offset condi-
tions (refer to page 14, 

Figure 38 ).

Step 5. The height of vertical chimney pipe
supported only by the fireplace must not ex-
ceed 30'. Chimney heights above 30' must be
supported by a Model FTF8-S4 stabilizer in-
stalled at 30' intervals.

Note: The Model FTF8-S4 adds 3" net effective
height to the total chimney system.

Install the Model FTF8-S4 stabilizer by fitting
inner section down into respective section of
proceeding flue pipe and locking outer stabi-
lizer section into place over the outer chimney
pipe. Position for proper clearance through
framed opening and nail straps securely (under
tension in “shear”) into place on framing. Use
8d nails. Attach successive lengths of chimney
pipe directly to stabilizer using same tech-
niques as described in Step 4 (

Figure 28 ).

Figure 28

F8FS30-2

Firestop Spacer

FTF8-S4 Stabilizer

2" Min.

Air Space

30

°

 Firestop

And Attic Above

10'

Max.

Attic Space

2" Min.

Air Space

F8FS30-2

Firestop Spacer

FTF8-S4 Stabilizer

30

°

 Firestop

And Room Above

10'

Max.

Room Above

2" Min.

Air Space

2" Min.

Air Space

Locking

Tabs

(Lances)

2" Min. Air Space
To Combustibles

FTF8-S4 Stabilizer

Note: Assemble one component of chimney at
a time (inner section first, then outer section
last) before proceeding with the next complete
section.

Continue to assemble the chimney up through
framed opening. Assemble just enough to pen-
etrate the roof flashing openings (

Figure 27 ).

Always maintain 2" minimum air space to com-
bustible materials and always check each chim-
ney joint (inner and outer) to ensure proper
engagement. Check vertical alignment of chim-
ney so that it projects from the roof in true
vertical position.

Figure 27

Step 4.

 Note: Chimney sections are con-

structed with a unique locking tab design,
which ensures an immediate, tight assembly
between sections. Plan your chimney require-
ments carefully before assembly as chimney
is difficult to disassemble after installation. If
disassembled, the tabs might become dam-
aged. Be certain tabs are properly formed to
ensure locking tabs engage properly.

The Security FTF8 chimney system is a two
piece chimney, which snap together from the
fireplace up. Start with the inner flue section
with the lanced end up, snap lock it in to the
matching collar on top of the fireplace. At all
subsequent joints, the upper flue section fits
into the preceding flue section. Each piece
snaps together by means of locking tabs (9
locking tabs per joint). Check each piece by
pulling up slightly from the top to ensure proper
engagement before installing the next section.
If the flue has been installed correctly, it will not
separate when you test it. Also, the inner flue
joint where each section is joined should be
tight and flat without gaps (

Figure 25 ).

CHIMNEY 30

°

 OFFSET THROUGH FLOOR

OR CEILING

It may be necessary to assemble the chimney at
30

°

 when passing through the floor or ceiling

area.  Use the F8FS30-2 firestop spacer as
shown in 

Figures 22 and 23.  Support the

chimney at floor or ceiling penetration with a
FTF8 stabilizer if distance of chimney below
ceiling is 10' or more. Maintain 2" minimum air
space to combustibles from chimney sections.

Figure 22

Figure 23

For Canada Only

When installing the chimney system through
an open attic space, the attic shield assembly-
firestop spacer must be used (

Figure 24 ). This

installation is required only for use in Canada.

Figure 24

Open Attic Space

Note: For Canadian installations, all chimney
installed outside the building must be constructed
with galvalume (outer sections only) effective
January 1, 1992.  The appropriate model desig-
nations are located in the back of this manual.

Summary of Contents for HC-42

Page 1: ...modify the fireplace or its components under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may...

Page 2: ...damage as a result of handling or transporta tion These items should be inspected by your distributor or qualified factory representative to ensure safe condition When in doubt con sult your distribu...

Page 3: ...These fireplace systems are designed for in stallation in accordance with the National Fire Protection Standard for chimneys fireplaces and solid fuel burning appliances NFPA 211 and in accordance wit...

Page 4: ...overhead obstructions such as trees power lines etc A chase should be constructed and insulated just like any outside wall In a cold climate we recommend the base of the chase should also be insulate...

Page 5: ...l safety strips beneaththefireplaceasillustrated Figures6 7 and 8 The safety strips should overlap for continual coverage of the floor Note Safety strips are not required when fire place rests on a no...

Page 6: ...ce If a wall covering such as drywall is to be attached to the rear wall then the 23 606 mm must be measured from the drywall surface It is important that this dimension be exact If the appliance is t...

Page 7: ...der Fireplace Framing B A A Outside Chase G H Back Wall of Chase Enclosure Including Finising Materials if any Rough Framing Face Unfinished Shown FOAK Combustion Air Kit Optional Corner Installation...

Page 8: ...upthroughtheceiling or floor joists to an outside wall The air duct s inlet should be located above any anticipated snow level Note If the fireplace is installed against an inside wall the Class 0 me...

Page 9: ...sure proper engagement Checkverticalalignmentofchim ney so that it projects from the roof in true vertical position Figure 27 Step 4 Note Chimney sections are con structed with a unique locking tab de...

Page 10: ...Do not overtighten as this might dam age the chimney section refer to Figure 31 Note If chimney extends more than 8 above roof surface guy wires are also recommended Use three 3 guy wires attach to l...

Page 11: ...fireplace system is 15 0 The maxi mum height is 60 0 To determine the number of chimney sections and chimney components required follow these steps 1 Determine total vertical height of the fireplace i...

Page 12: ...23 0 1 0 1 5 278 23 2 0 0 0 6 282 23 6 0 1 1 5 288 24 0 1 0 0 6 294 24 6 0 1 0 6 298 24 10 2 0 0 6 304 25 4 1 1 0 6 312 26 0 0 0 1 6 322 26 10 1 0 1 6 324 27 0 0 0 0 7 328 27 4 0 1 1 6 334 27 10 1 0 0...

Page 13: ...35 69 1 0 0 1 0 1 37 73 1 0 0 2 1 0 38 75 1 0 0 0 2 0 39 77 1 0 2 1 1 0 41 80 1 0 1 4 0 0 43 83 1 0 1 0 2 0 44 85 1 0 0 0 1 1 45 87 1 0 0 3 1 0 46 89 1 0 0 1 2 0 48 91 1 0 2 0 2 0 49 94 1 0 1 0 1 1 50...

Page 14: ...mney section Step 2 Center inner slip section into inner flue pipe slip down Step 3 Center outer locking section over outer chimneypipe Pushdownuntillockingjointhas firmly engaged Step 4 Pull up sligh...

Page 15: ...per operation before completing any enclo sure around the firebox Failure to do so may result in extensive and costly rework Locate the actuator arm along the right side of the appliance firebox openi...

Page 16: ...LACE IF THE FIREPLACE HAS BEEN FACED WITHNONCOMBUSTIBLEMATERIALS THERE MIGHT NOT BE SUFFICIENT CLEARANCE TO INSTALL THE GLASS DOORS OF YOUR CHOICE ENSURE ADEQUATE CLEARANCE IS MAINTAINED AT ALL TIMES...

Page 17: ...5 6 56 6 1 2 Wonderboard 3 23 31 7 51 7 1 2 Super Firetemp M Johns Manville 61 1 64 1 42 1 3 8 Super Firetemp L Johns Manville 54 1 85 Face brick 9 00 111 20 93 20 7 8 Common brick 5 00 20 Cement mort...

Page 18: ...ptable combinations of materialsbecause Rvalues areadditivewhere r and k values are not R value 1 k r x thickness of material used Example Given that the required R value for a suitable floor protecto...

Page 19: ...Chase Termination Square 63L48 FTF8 CT1 Firestop Spacer Flat 63L31 F8FS 2 Locking Band 63L60 FLB Forced Air Blower Kits Single Speed 80L84 FBK 100 Variable Speed 80L85 FBK 200 FBK 200 Models Only Outs...

Page 20: ...ign materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information 1110 West Taft Avenue Orange CA 92865 Chase Termina...

Reviews: