background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

18

Secure the hearth extension to the floor to
prevent possible shifting.

FINISH TO YOUR TASTE

There are a wide variety of “finished looks” for
these fireplaces, from formal wall decor with
elaborate mantels to rustic wood paneling or
warm brick facings.

Only noncombustible materials like stone, tile,
brick, etc., may overlap the black front facing.
Do not extend these materials beyond the black
facing and into the firebox area. Be sure not to
interfere with the installation and operation of
glass doors or block the upper or lower grilles.
Seal all joints between the black facing and wall
surrounds to prevent air intrusion. Use non-
combustible caulking material only to seal the
black metal facing to the surround material on
the finished wall.

Combustible materials may project beyond the
sides of the fireplace opening as long as they
are kept within the shaded areas illustrated in
Figure 51.

Figure 50

Figure 51

7 1/2"

Max. Thickness Of Hearth Extension When

Non-Circulating Models Are On The Floor

Figure 49

5 1/2"

2"

Max. Thickness Of Hearth Extension When

Circulating Models Are On The Floor

12"

12"

Min. Distance To

Unprotected Side Wall

45

°

Combustible

Materials

Allowed In

Shaded Area

“Safe Zone”

1"

Fireplace

Figure 48

WARNING: THE CRACK BETWEEN THE
FIREPLACE AND THE HEARTH EXTEN-
SION MUST BE SEALED WITH A NON-
COMBUSTIBLE MATERIAL.

Calculating Minimum Thickness if Multiple
Materials are Used

At times it is important to know what
combination of materials are acceptable for
use as floor protection. The “R values” are
used to determine acceptable combinations of
materials because “R values” are additive where
r and k values are not.

“R value” =  1/k  =  “r” x thickness of material
used

Example:  Given that the required “R value”
for a suitable floor protector used must be
equal to or greater than:

“R” = r

L

 x T

L

 = 2.33 x 1” = 2.33.”

If it is desired to elevate a marble hearth ex-
tension to a level of 5” or more above the floor
surface.  What combination of noncombus-
tible materials can be used to accomplish this?

If common brick is used so that the 3 1/2”
dimension is the height, “R” for the common
brick becomes:

brick

“R”

M

 = r

M

 x T

S

 =  0.20   x 3 1/2"  = .70

Using 1/2” of mortar to set the brick, “R” for
the mortar is calculated as follows:

mortar

“R”

M

 = r

M

 x T

S

 =  0.20  x 1/2"  = .10

Next, a 3/4" marble slab set in 1/2" mortar cov-
ers the brick, “R” for the marble and mortar
becomes:

marble

“R”

M

 = r

M

 x T

S

 =  0.05   x 3/4"  = .038

mortar

“R”

M

 = r

M

 x T

S

 =  0.20  x 1/2"  = .10

The sum of all “R values” is: .70 + .10 +. 038
+ .10 = .938

This would NOT be an acceptable combination
of material for the hearth extension since the
total calculated “R value” of the materials used
is under the required “R value” of 2.33.  An
additional layer of insulating materials must
be used.

Note: Also see NFI Certification Manuals for
expanded explanation on calculating “R val-
ues” when multiple materials are used.

WARNING: WHEN INSTALLING HEARTH
EXTENSION IN FRONT OF A NON-CIRCU-
LATING FIREPLACE MODEL, THE FIRE-
PLACE MUST BE RAISED IF HEIGHT OF
HEARTH EXTENSION EXCEEDS 7" ABOVE
THE BOTTOM OF FIREPLACE (

FIGURE 49 ).

12" Min.

A

B

C

C

D

WARNING: WHEN INSTALLING THE
HEARTH EXTENSION BE CAREFUL NOT
TO BLOCK THE HEAT-CIRCULATING AIR
INLET GRILL ON CIRCULATING MODELS.

WARNING: WHEN INSTALLING HEARTH
EXTENSION IN FRONT OF A CIRCULAT-
ING FIREPLACE MODEL, THE FIREPLACE
MUST BE RAISED IF HEIGHT OF HEARTH
EXTENSION EXCEEDS 2" ABOVE BOTTOM
OF FIREPLACE (

FIGURE 50 ).

Summary of Contents for HC-42

Page 1: ...modify the fireplace or its components under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may...

Page 2: ...damage as a result of handling or transporta tion These items should be inspected by your distributor or qualified factory representative to ensure safe condition When in doubt con sult your distribu...

Page 3: ...These fireplace systems are designed for in stallation in accordance with the National Fire Protection Standard for chimneys fireplaces and solid fuel burning appliances NFPA 211 and in accordance wit...

Page 4: ...overhead obstructions such as trees power lines etc A chase should be constructed and insulated just like any outside wall In a cold climate we recommend the base of the chase should also be insulate...

Page 5: ...l safety strips beneaththefireplaceasillustrated Figures6 7 and 8 The safety strips should overlap for continual coverage of the floor Note Safety strips are not required when fire place rests on a no...

Page 6: ...ce If a wall covering such as drywall is to be attached to the rear wall then the 23 606 mm must be measured from the drywall surface It is important that this dimension be exact If the appliance is t...

Page 7: ...der Fireplace Framing B A A Outside Chase G H Back Wall of Chase Enclosure Including Finising Materials if any Rough Framing Face Unfinished Shown FOAK Combustion Air Kit Optional Corner Installation...

Page 8: ...upthroughtheceiling or floor joists to an outside wall The air duct s inlet should be located above any anticipated snow level Note If the fireplace is installed against an inside wall the Class 0 me...

Page 9: ...sure proper engagement Checkverticalalignmentofchim ney so that it projects from the roof in true vertical position Figure 27 Step 4 Note Chimney sections are con structed with a unique locking tab de...

Page 10: ...Do not overtighten as this might dam age the chimney section refer to Figure 31 Note If chimney extends more than 8 above roof surface guy wires are also recommended Use three 3 guy wires attach to l...

Page 11: ...fireplace system is 15 0 The maxi mum height is 60 0 To determine the number of chimney sections and chimney components required follow these steps 1 Determine total vertical height of the fireplace i...

Page 12: ...23 0 1 0 1 5 278 23 2 0 0 0 6 282 23 6 0 1 1 5 288 24 0 1 0 0 6 294 24 6 0 1 0 6 298 24 10 2 0 0 6 304 25 4 1 1 0 6 312 26 0 0 0 1 6 322 26 10 1 0 1 6 324 27 0 0 0 0 7 328 27 4 0 1 1 6 334 27 10 1 0 0...

Page 13: ...35 69 1 0 0 1 0 1 37 73 1 0 0 2 1 0 38 75 1 0 0 0 2 0 39 77 1 0 2 1 1 0 41 80 1 0 1 4 0 0 43 83 1 0 1 0 2 0 44 85 1 0 0 0 1 1 45 87 1 0 0 3 1 0 46 89 1 0 0 1 2 0 48 91 1 0 2 0 2 0 49 94 1 0 1 0 1 1 50...

Page 14: ...mney section Step 2 Center inner slip section into inner flue pipe slip down Step 3 Center outer locking section over outer chimneypipe Pushdownuntillockingjointhas firmly engaged Step 4 Pull up sligh...

Page 15: ...per operation before completing any enclo sure around the firebox Failure to do so may result in extensive and costly rework Locate the actuator arm along the right side of the appliance firebox openi...

Page 16: ...LACE IF THE FIREPLACE HAS BEEN FACED WITHNONCOMBUSTIBLEMATERIALS THERE MIGHT NOT BE SUFFICIENT CLEARANCE TO INSTALL THE GLASS DOORS OF YOUR CHOICE ENSURE ADEQUATE CLEARANCE IS MAINTAINED AT ALL TIMES...

Page 17: ...5 6 56 6 1 2 Wonderboard 3 23 31 7 51 7 1 2 Super Firetemp M Johns Manville 61 1 64 1 42 1 3 8 Super Firetemp L Johns Manville 54 1 85 Face brick 9 00 111 20 93 20 7 8 Common brick 5 00 20 Cement mort...

Page 18: ...ptable combinations of materialsbecause Rvalues areadditivewhere r and k values are not R value 1 k r x thickness of material used Example Given that the required R value for a suitable floor protecto...

Page 19: ...Chase Termination Square 63L48 FTF8 CT1 Firestop Spacer Flat 63L31 F8FS 2 Locking Band 63L60 FLB Forced Air Blower Kits Single Speed 80L84 FBK 100 Variable Speed 80L85 FBK 200 FBK 200 Models Only Outs...

Page 20: ...ign materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information 1110 West Taft Avenue Orange CA 92865 Chase Termina...

Reviews: