Lennox Grandview GV 230 Installation And Operation Manual Download Page 12

12

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Chimney Connector Systems and Clearances from Combustible 

Walls  for  Residential  Heating  Appliances  (NFPA  211) 

Refer  to 

Figure 9

System  A.

  Minimum  3.5  in.  (90  mm)  thick  brick  masonry  wall 

framed into combustible wall with a minimum of 12 in. (305 mm) 

brick separation from clay liner to combustibles. Fireclay liner (ASTM 

C 315, Standard Specification for Clay Flue Linings, or equivalent), 

minimum 5/8 in. (16 mm) wall thickness, shall run from outer surface 

of brick wall to, but not beyond, the inner surface of chimney flue 

liner and shall be firmly cemented in place.
Clearance: 12 in. (305 mm)

System B

. Solid-insulated, listed factory-built chimney length of the 

same inside diameter as the chimney connector and having 1 in. 

(25.4 mm) or more of insulation with a minimum 9 in. (229 mm) air 

space between the outer wall of the chimney length and combustibles.
The inner end of the chimney length shall be flush with the inside of 

the masonry chimney flue and shall be sealed to the flue and to the 

brick masonry penetration with non-water-soluble refractory cement. 

Supports shall be securely fastened to wall surfaces on all sides.
Fasteners between supports and the chimney length shall not pen-

etrate the chimney liner.
Clearance: 9 in. (229 mm)

System C.

 Sheet steel chimney connector, minimum 24 gauge [0.024 

in. (0.61 mm)] in thickness, with a ventilated thimble, minimum 24 

gauge [0.024 in. (0.61 mm)] in thickness, having two 1 in. (25.4 

mm) air channels, separated from combustibles by a minimum of 6 

in. (152 mm) of glass fiber insulation. Opening shall be covered, and 

thimble supported with a sheet steel support, minimum 24 gauge 

[0.024 in. (0.61 mm)] in thickness.
Supports shall be securely fastened to wall surfaces on all sides and 

shall be sized to fit and hold chimney section. Fasteners used to secure 

chimney section shall not penetrate chimney flue liner.
Clearance: 6 in. (152 mm)  

System D.

 Solid-insulated, listed factory-built chimney length with 

an inside diameter 2 in. (51 mm) larger than the chimney connector 

and having 1 in. (25.4 mm) or more of insulation, serving as a pass-

through for a single wall sheet steel chimney connector of minimum 

24 gauge [0.024 in. (0.61 mm)] thickness, with a minimum 2 in. 

(51 mm) air space between the  outer wall of chimney section and 

combustibles. Minimum length of chimney section shall be 12 in. 

(305 mm). Chimney section concentric with and spaced 1 in. (25.4 

mm) away from connector by means of sheet steel support plates 

on both ends of chimney section. Opening shall be covered, and 

chimney section supported on both sides with sheet steel supports 

of minimum 24 gauge [0.024 in. (0.61 mm)] thickness.
Supports shall be securely fastened to wall surfaces on all sides and 

shall be sized to fit and hold chimney section. Fasteners used to secure 

chimney section shall not penetrate chimney flue liner.
Clearance: 2 in. (51 mm)

Additional requirements:

1. Insulation material used as part of wall pass-through system shall be 

of noncombustible material and shall have a thermal conductivity of 

1.0 Btu-in./hr-ft

2

 - ºF (4.88 kg-cal/hr-m

2

 - ºC) or less.

2. All clearances and thicknesses are minimums; larger clearances and 

thicknesses shall be permitted.

3. Any material used to close up an opening for the connector shall be of 

noncombustible material.

4. A connector to a masonry chimney, except for System B, shall extend 

in one continuous piece through the wall pass-through system and the 

chimney wall to the inner face of the flue liner, but not beyond.

Factory Built 

Chimney Length 

Air Space – 9 in. 

(228.6mm) Min. 

Chimney Length 

Flush with 

Inside of Flue 

Min. Clearance 

9 in. (229mm) 

Chimney 

Connector 

Use Chimney 

Mfrs. Parts to 

Attach 

Connector 

Solid-Insulated 

Listed Factory-

Built Chimney 

Length

Sheet Steel Supports

Sheet Steel Supports

Sheet Steel Supports

Minimum Chimney Clearance from Masonry to Sheet Steel 

Supports & Combustibles – 2 in. (51mm) 

Nonsoluble 

Refractory  

Cement

Minimum chimney clearance to sheet

steel supportrs and combustibles

2 in. (51mm)

Chimney 

Connector 

2 Air Channels, Each 1 

in. (25.4 mm) 

2 Ventilated Air 

Channels, Each 

1 in. (25.4 mm) 

Construction of 

Sheet Steel 

Minimum chimney clearance to sheet steel 

supports and combustibles 2 in. (51mm) 

Sheet Steel 

Supports 

Chimney 

Connector 

Chimney 

Section

Air Space – 2 in. 

(51mm) Min. 

Chimney connector  

Chimney length

1 in. (25.4 mm) 

air space to 

        chimney length

Min. Clearance  

2 in. (51 mm) 

Minimum

12 in. (305mm)

to combustibles

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Minimum chimney clearance to brick

and combustibles 2 in. (51mm)

Minimum clearance

12 in. (305mm)

of brick

Chimney

Chimney

flue

Chimney

flue

Chimney

flue

connector

Fire clay

liner

Figure 9 - 

Chimney Connector Systems and Clearances from Combustible Walls

System A

System B

System C

System D

Summary of Contents for Grandview GV 230

Page 1: ...t en faire la demande Num ro de la pi ce 506223 28 This appliance must be properly installed and operated in order to prevent the possibility of a house fire Please read this entire installation and o...

Page 2: ...quirements 4 Selecting the Proper Venting System 4 Chimney Height Requirements 5 Negative Pressure Warning 5 Clearances to Combustibles 6 7 Floor Protection 6 8 Alcove Floor Protection 8 Specification...

Page 3: ...spectyourchimneyatleastonceamonthduringtheburn Safety and General ing season to check for soot and creosote accumulations Any accumulations over 1 8 thick should be removed by a professional chimney s...

Page 4: ...to the venting system Do not install an offset within the first two feet above the flue outlet on the appliance Inwellinsulatedandweathertighthomes itmaybedifficulttoestablish a good draft up your ch...

Page 5: ...is caused by many common household appliances which exhaust air from the home such as a furnace heat pump air conditioner clothes dryer exhaust fans fireplaces and other fuel burning appliances Also...

Page 6: ...ial chimney systems must be from the same brands as listed for mobile homes but connector pipe may be double wall single wall or single wall with shield as listed This appliance may be vented into a c...

Page 7: ...10 6 3 8 21 11 1 2 8 4 11 16 15 38 5 8 45 33 16 0 90 57 1 2 10 254 162 533 292 200 119 381 981 1143 838 406 0 2286 1461 N A Double Wall Alcove Vertical Vent 13 9 3 8 22 1 2 13 8 N A N A 38 5 8 48 33...

Page 8: ...kM x thickness alternate k value per inch of listed material TM of listed material kL material TL TM inches kM x TL 47 TM inches 35 x 50 47 312 inches 745 x 50 Answer The minimum required thickness o...

Page 9: ...1482 ULC S627 Listing Dimensions Notes Dimensions shown are approximations only 1 4 Diagrams illustrations and photographs are not to scale consult installa tion instructions Product designs materials...

Page 10: ...STAINLESS STEEL LINER Using 6 Diameter Rigid Stainless Steel Liner Figure 6 Typical Installation Figure 7 Connected to a Masonry Chimney Floor Protector Floor Protector Fasten each stove pipe connecti...

Page 11: ...tallations require a spark arrestor at the chimney termination All mobile home installations require an outside air kit see Page 27 for ordering information and the stove must be secured to the floor...

Page 12: ...ll be 12 in 305 mm Chimney section concentric with and spaced 1 in 25 4 mm away from connector by means of sheet steel support plates on both ends of chimney section Opening shall be covered and chimn...

Page 13: ...elow that the stove in located on Leg Installation Figure 11 Pedestal Installation Residential and Mobile Homes Tieing down and grounding are required only in mobile homes Open all cartons if any and...

Page 14: ...FLOOR THE STOVE MUST BE ATTACHED TO THE FLOOR AT NO LESS THAN TWO POINTS Pedestal Locate the two holes on the back of the pedestal Figure 12 Secure the pedestal to the floor using two field provided 1...

Page 15: ...t not be installed more than ten 10 feet 3050 mm above the base of the stove C The fresh air must come from outside the house The air intake must not draw air from the attic from the basement or garag...

Page 16: ...de x 1 5 16 33mm Thick 6 5 7 7 Back Baffle Board Back Baffle Board 7 7 196mm 6 5 165mm Front Baffle Board Front Baffle Board 1 Install firebox bottom brick spacers on both the left and right side of f...

Page 17: ...nd baffle boards are properly installed If plated accessories are used be sure surfacesarecleanpriortofiringthestove See Page 18 FOR YOUR OWN PROTECTION AND INSURANCE PURPOSES HAVE YOUR CHIMNEY AND CO...

Page 18: ...to an imbal ance in the indoor air quality avoid the stove during the curing process Your new Grandview 230 is painted with a high temperature paint that cures during the first few firings We recomme...

Page 19: ...TLY OPEN CAUTION Do Not alter the adjustment range of the draft control for increased firing for any reason Operate only with fuel door and ash drawer closed Maintain all seals in good condition Do no...

Page 20: ...t slightly open during start up 6 For best results use smaller pieces of wood to get the stove tem perature very high before loading larger wood for sustained burns If necessary crack the door to allo...

Page 21: ...gh level of heat transfer efficiency Slowing the rate of flow through the stove or insert enhances heat transfer thus allowing more time for heat to be transferred into your home To do this be sure to...

Page 22: ...r being moved by the blower before the blower is turned on Likewise when the stove cools off the blower is turned off to prevent circulating cool air Depending on the size and intensity of the fire it...

Page 23: ...e chimney and baffle monthly to make sure they are clean DO Burn seasoned dry wood only RAIN WET WOOD DO Open the door frequently during Burn In Period to keep gasket from adhering to the curing paint...

Page 24: ...e back of the stove Using a L shaped 5 32 allen wrench loosen the locking screw in the latch assemblyasshowninFigure31 Withthelockingscrewloosened adjust the top 5 32 allen screw Figure 31 in the fron...

Page 25: ...n above and Cleaning Glass on Page 24 SMOKES WHEN 1 If smoke is entering the room check to make sure your baffle boards are properly installed DOOR IS OPEN and that the baffle blankets are pushed back...

Page 26: ...lack Cast Leg single leg H8382 Leg Hardware Bolt Kit PEDESTAL PARTS H5564 Ash Plug Remover and Rake H8381 Removable Ash Plug BLOWER PARTS Cat No Description H8374 Blower Snap Switch H8375 Blower Blade...

Page 27: ...sh Drawer Kit 6 H8345 ASHDR KIT LEG GV Leg Ash Drawer Kit LOUVERS 7 H8348 LVP GV230 BLK Louvers Black 7 H8349 LVR GV230 BRNKL Louvers Brushed Nickel DOOR TRIM Item Cat No Model Description 8 H8346 DRT...

Page 28: ...LENGTH 3 9 4 6DL36A 6DL36A ADJUSTABLE LENGTH 3 34 2 6DT 6DT TEE TEE CAP INCLUDED 4 6DE45 6DE45 ELBOW 45 DEGREE 4 6DE90 6DE90 ELBOW 90 DEGREE 4 6DMA 6DMA MASONRY ADAPTOR 1 6UP 6UP FLUE EXTENSION 10 6D...

Page 29: ...FC FINISHING SUPPORT W COUPLER 1 Cat No Model Description Pc Container Supports continued 6SM 6SM TEE SUPPORT 1 6SMA 6SMA GALVALUME ADJUSTABLE TEE SUPPORT 2 TO 6 5 SO SO OFFSET SUPPORT WALL SUP PORT 1...

Page 30: ...only parts sup plied from the manufacturer Normally all parts should be ordered through your Lennox distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repa...

Reviews: