BLOWER DATA Cont.
G60UH−60C−110
with 1 hp
PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Re-
turn Air from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
.00
0
2555
1205
1378
2300
1085
1027
1985
935
863
1655
780
678
.10
25
2490
1175
1354
2265
1070
1002
1980
935
839
1640
775
667
.20
50
2420
1140
1330
2225
1050
980
1975
930
832
1635
770
660
.30
75
2355
1110
1300
2175
1025
957
1945
915
810
1625
765
653
.40
100
2275
1075
1265
2115
1000
934
1915
905
785
1620
765
639
.50
125
2175
1025
1229
2040
960
903
1860
875
762
1595
750
623
.60
150
2085
985
1199
1965
925
873
1800
850
733
1565
740
608
.70
175
1990
940
1140
1870
880
843
1730
815
714
1525
720
590
.80
200
1890
890
1105
1770
835
807
1630
770
676
1455
685
567
.90
225
1760
830
1067
1655
780
777
1535
725
649
1370
645
541
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G60UH−60C−110
with 1 hp
PERFORMANCE − Single Side Return Air − Air volumes in bold require field fabricated transition
to accommodate 20 x 25 x 1 in. (508 x 635 x25 mm) cleanable air filter in order to maintain proper air velocity.
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
.00
0
2385
1125
1296
2185
1030
981
1915
905
836
1650
780
686
.10
25
2330
1100
1274
2150
1015
961
1900
895
815
1635
770
677
.20
50
2255
1065
1234
2095
990
930
1885
890
794
1625
765
664
.30
75
2190
1035
1207
2035
960
902
1855
875
769
1620
765
651
.40
100
2115
1000
1179
1970
930
876
1820
860
751
1605
755
639
.50
125
2055
970
1156
1905
900
853
1760
830
725
1575
745
622
.60
150
1985
935
1141
1830
865
827
1705
805
704
1525
720
602
.70
175
1910
900
1119
1745
825
797
1635
770
680
1475
695
582
.80
200
1810
855
1088
1650
780
772
1560
735
659
1430
675
571
.90
225
1715
810
1058
1570
740
751
1485
700
638
1355
640
549
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G60UH−60D−135
with 1 hp
PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Re-
turn Air from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Different Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
.00
0
2715
1280
1407
2255
1065
1070
1910
900
850
1660
785
674
.10
25
2640
1245
1403
2250
1060
1030
1900
895
834
1645
775
668
.20
50
2540
1200
1355
2245
1060
1006
1890
890
821
1630
770
665
.30
75
2480
1170
1319
2200
1040
975
1890
890
781
1625
765
656
.40
100
2390
1125
1282
2155
1015
940
1885
890
775
1615
760
642
.50
125
2320
1095
1251
2085
985
904
1860
875
758
1605
755
631
.60
150
2205
1040
1210
2020
955
876
1815
855
731
1595
750
611
.70
175
2080
980
1161
1935
915
839
1760
830
707
1545
730
588
.80
200
2010
950
1122
1855
875
810
1690
795
679
1495
705
568
.90
225
1880
885
1071
1755
830
781
1585
745
646
1430
675
545
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.