BLOWER DATA Cont.
G60UH−48B−090 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
1970
930
790
1810
855
735
1585
750
670
1340
630
565
0.05
12
1940
915
780
1785
840
715
1580
745
650
1335
630
555
0.10
25
1915
905
765
1760
830
695
1570
740
630
1325
625
540
0.15
37
1880
885
745
1730
815
660
1560
735
615
1325
625
530
0.20
50
1840
870
730
1700
800
620
1545
730
600
1320
625
520
0.25
62
1805
850
715
1670
790
625
1520
715
585
1310
620
510
0.30
75
1765
835
695
1640
775
625
1490
705
565
1295
610
500
0.40
100
1695
800
670
1570
740
595
1440
680
540
1260
595
480
0.50
125
1600
755
635
1490
705
560
1360
640
505
1195
565
450
0.60
150
1505
710
600
1400
660
530
1285
605
480
1140
540
425
0.70
175
1395
660
565
1265
595
485
1170
550
440
990
465
380
0.80
200
1250
590
520
1100
520
445
975
460
390
905
425
355
0.90
225
1005
475
460
870
410
385
900
425
365
810
380
325
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
NOTE − Air volumes based on bottom return air. Actual air volume may vary on side return air applications.
G60UH−48C−110 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
2015
950
895
1620
765
780
1340
630
640
1150
545
525
0.05
12
1990
940
870
1615
760
760
1340
630
640
1150
545
525
0.10
25
1965
925
850
1610
760
745
1340
630
640
1150
545
525
0.15
37
1930
910
825
1605
755
725
1335
630
630
1150
545
525
0.20
50
1895
895
805
1600
755
710
1335
630
615
1150
545
525
0.25
62
1860
880
785
1590
750
695
1330
630
605
1150
545
520
0.30
75
1820
860
765
1580
745
675
1330
630
590
1145
540
515
0.40
100
1740
820
725
1530
720
635
1320
625
560
1140
540
490
0.50
125
1665
785
695
1475
695
600
1285
605
525
1120
530
470
0.60
150
1575
745
650
1405
665
555
1230
580
490
1075
505
445
0.70
175
1475
695
610
1310
620
515
1165
550
470
1015
480
415
0.80
200
1350
635
560
1210
570
485
1080
510
430
930
440
380
0.90
225
1210
570
520
1070
505
430
870
410
365
740
350
325
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
NOTE − Air volumes based on bottom return air. Actual air volume may vary on side return air applications.
G60UH−60C−110
with 3/4 hp
PERFORMANCE − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Re-
turn Air from Both Sides or Return Air from Bottom and One Side.
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
2450
1155
1220
2300
1085
1060
2056
970
905
1725
815
735
0.05
12
2410
1135
1205
2265
1070
1045
2040
965
895
1715
810
725
0.10
25
2370
1120
1195
2230
1050
1030
2020
955
890
1710
810
720
0.15
37
2325
1095
1175
2200
1040
1015
1995
940
875
1700
800
715
0.20
50
2280
1075
1165
2170
1025
1005
1975
935
870
1695
800
710
0.25
62
2245
1060
1150
2130
1005
990
1950
920
855
1680
795
705
0.30
75
2205
1040
1135
2095
990
975
1925
910
845
1665
785
700
0.40
100
2115
995
1105
2010
950
940
1860
875
820
1625
770
685
0.50
125
2025
955
1060
1945
920
920
1810
855
805
1605
755
675
0.60
150
1910
900
1015
1850
875
885
1715
810
780
1540
730
670
0.70
175
1835
865
1005
1775
840
865
1655
780
765
1495
705
655
0.80
200
1745
825
975
1655
780
835
1540
725
730
1400
660
635
0.90
225
1610
760
945
1540
725
805
1475
695
715
1310
620
615
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.