Page 5
BLOWER DATA
G60UH−24A−045 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
1090
515
460
905
425
390
725
340
300
0.05
12
1080
510
450
900
425
390
720
340
300
0.10
25
1065
505
445
895
420
385
710
335
295
0.15
37
1050
495
435
895
420
380
700
330
290
0.20
50
1030
485
425
890
420
375
690
325
290
0.25
62
1015
480
415
875
415
370
680
320
285
0.30
75
995
470
410
860
405
365
665
315
280
0.40
100
960
455
395
840
395
350
650
305
270
0.50
125
910
430
380
795
375
335
610
290
260
0.60
150
840
395
355
750
355
315
540
255
245
0.70
175
770
365
340
665
315
295
490
230
235
0.80
200
660
310
315
555
260
275
420
200
225
0.90
225
560
265
295
480
225
260
355
170
210
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
NOTE − Air volumes based on bottom return air. Actual air volume may vary on side return air applications.
G60UH−24A−070 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
1075
505
445
905
425
375
730
345
290
0.05
12
1070
505
445
900
425
375
725
340
290
0.10
25
1065
505
440
895
420
370
720
340
285
0.15
37
1060
500
435
890
420
365
715
335
285
0.20
50
1055
500
430
885
420
360
710
335
280
0.25
62
1045
495
425
880
415
360
700
330
280
0.30
75
1030
485
415
875
415
355
690
325
270
0.40
100
1010
475
400
860
405
350
675
320
270
0.50
125
975
460
390
840
395
340
660
310
265
0.60
150
940
445
375
805
380
325
640
300
255
0.70
175
890
420
360
755
355
305
605
285
240
0.80
200
830
390
340
700
330
285
565
265
225
0.90
225
765
360
305
640
300
265
515
245
205
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
NOTE − Air volumes based on bottom return air. Actual air volume may vary on side return air applications.
G60UH−36A−070 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External Static
Pressure
High
Medium−High
Medium−Low
Low
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
0.00
0
1500
710
705
1290
610
565
985
465
455
830
390
375
0.05
12
1475
695
695
1275
600
555
980
465
445
820
385
365
0.10
25
1450
685
680
1255
590
545
970
460
440
810
380
360
0.15
37
1425
675
670
1240
585
535
965
455
430
805
380
355
0.20
50
1400
660
655
1225
580
525
955
450
425
795
375
350
0.25
62
1370
645
645
1205
570
510
945
445
415
790
375
345
0.30
75
1340
630
630
1180
555
500
930
440
405
780
370
335
0.40
100
1285
605
610
1140
540
475
900
425
390
745
350
325
0.50
125
1215
575
580
1080
510
450
865
410
375
705
335
310
0.60
150
1150
545
560
1015
480
430
810
380
355
655
310
290
0.70
175
1060
500
535
940
445
405
730
345
330
585
275
270
0.80
200
955
450
515
800
375
370
655
310
305
480
225
260
0.90
225
785
370
475
605
285
325
585
275
270
410
195
255
NOTE − All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
NOTE − Air volumes based on bottom return air. Actual air volume may vary on side return air applications.