Page 59
IS THERMOSTAT PROPERLY SET?
YES
NO
ARE LIMITS CLOSED?
MAKE OHMMETER CHECK.
REPLACE SWITCH.
SEE GAS CHECKS ON
NEXT PAGE.
DOUBLE CHECK WIRING CONNECTIONS
AND DOOR INTERLOCK SWITCH.
ELECTRICAL CHECKOUT
YES
NO
YES
NO
IS DIFFERENTIAL SWITCH CLOSED?
MAKE OHMMETER CHECK.
TURN OFF POWER TO UNIT.
3.AFTER 30 TO 35 SECONDS PRE−PURGE, IS 24VAC PRESENT AT GAS
VALVE TERMINALS FOR APPROXIMATELY 7 SECONDS?
2. BREAK & REMAKE THERMOSTAT DEMAND TO RESTART UNIT CYCLE.
1. CONNECT 24VAC METER ACROSS GAS VALVE TERMINAL.
CHECKOUT & REPAIR
THERMOSTAT AND/OR WIRING.
NO
YES
CHECK FOR HEAT DEMAND AT UNIT. IS 24VAC
PRESENT ACROSS TERMINALS C & W ON
LOW VOLTAGE STRIP?
YES
IS 24VAC PRESENT ACROSS TERMINAL
R & C ON LOW VOLTAGE STRIP?
YES
YES
NO
IS 120VAC PRESENT AT TRANSFORMER PRIMARY?
NO
CLOSE DOOR TO ACTUATE SWITCH.
NO
IS BLOWER DOOR CLOSED PROPERLY ON INTERLOCK SWITCH?
CHECK FOR 120VAC POWER TO UNIT & ADEQUATE GROUNDING.
(GROUNDING REQUIRED FOR PROPER OPERATION OF IGNITION SYS
TEM.)
SYSTEM MAY BE LOCKED OUT. TURN THERMOSTAT HEATING DEMAND
OFF AND ON AGAIN. NOTECONTINUE THROUGH TROUBLESHOOTING
FLOW CHART TO LOCATE REASON FOR LOCKOUT.
SET FOR HEAT DEMAND
1
2
3
4
5
IS UNIT FUSE BLOWN?
YES
NO
RE
PLACE
FUSE.
REPLACE
TRANSFORMER.
NOTE− Numbered steps refer to illustrations on page 61.
REPAIR WIRING CONNECTION BETWEEN PRIMARY
CONTROL &
R
SIDE OF TRANSFORMER.
NO
YES
NO
YES
YES
NO
REPLACE
PRIMARY
CONTROL.
IS 24VAC PRESENT ACROSS
TERMINAL C OF LOW VOLTAGE
STRIP & BLUE WIRE TO PRIMARY
CONTROL PLUG (JP1−4)?
IS 24VAC PRESENT ACROSS TERMINAL
C
OF LOW VOLTAGE STRIP & BROWN WIRE
TO PRIMARY CONTROL PLUG (JP1−1)?
TURN ON POWER. SET THERMOSTAT FOR HEAT DEMAND.
CHECK ALL WIRING CONNECTION
INTERNAL AND EXTERNAL TO UNIT. REPAIR
ANY LOOSE OR DAMAGED CONNECTIONS.
REPAIR WIRING CONNECTION
BETWEEN LIMIT & PRIMARY
CONTROL PLUG
(BROWN WIRE).
6
7
DETERMINE CAUSE OF OPEN LIMIT
AND/OR REPLACE IF DEFECTIVE.