background image

Page 9

CGA-B149.1 and -B149.2 in Canada. The effective area

of the chimney serving a single appliance must be no

less than the effective area of the draft hood outlet. The

chimney must extend vertically at least 5 feet above the

flue collar.
The  G20R  gas  furnace  must  not  be  connected  to  a

chimney  servicing  a  separate  appliance  designed  to

burn solid fuel.
Masonry chimneys serving fireplaces cannot be used

for venting purposes unless the fireplace opening is

permanently sealed. See figure 10.
When inspection reveals that an existing chimney is

not safe for the intended purpose, it shall be rebuilt to

conform to nationally recognized standards, lined or

relined with suitable materials or replaced with a gas

vent or chimney suitable for venting G20R series units.

The chimney passageway must be checked periodicalĆ

ly to ensure that it is clear and free of obstructions.

G20R

FURNACE

PERMANENTLY

SEALED FIREĆ

PLACE OPENING

H

L

VERTICAL VENT

USING LINED

MASONRY CHIMNEY

FIGURE 10

Removal of Unit from Common Venting System

In the event that an existing furnace is removed from a

venting system commonly run with separate gas apĆ

pliances, the venting system is likely to be too large to

properly vent the remaining attached appliances. The

following  test  should  be  conducted  while  each  apĆ

pliance in operation and the other appliances not in opĆ

eration remain connected to the common venting sysĆ

tem.  If  the  venting  system  has  been  installed

improperly, the system must be corrected as outlined

in the previous section.

 1- Seal any unused openings in the common venting

system.

 2- Visually inspect the venting system for proper size and

horizontal pitch and determine there is no blockage or

restriction,  leakage,  corrosion  and  other  deficiencies

which could cause an unsafe condition.

 3- Insofar as is practical, close all building doors and

windows and all doors between the space in which

the appliances remaining connected to the common

venting system are located and other spaces of the

building. Turn on clothes dryers and any appliances

not connected to the common venting system. Turn

on any exhaust fans, such as range hoods and bathĆ

room  exhausts,  so  they  will  operate  at  maximum

speed. Do not operate a summer exhaust fan. Close

fireplace dampers.

 4- Follow the lighting instructions. Place the appliance

being inspected in operation. Adjust thermostat so

appliance will operate continuously.

 5- Test for spillage at the draft hood relief opening after 5

minutes of main burner operation. Use the flame of a

match or candle, or smoke from a cigarette, cigar or pipe.

 6- After it has been determined that each appliance reĆ

maining connected to the common venting system

properly vents when tested as outlined above, return

doors, windows, exhaust fans, fireplace dampers and

any other gas-burning appliance to their previous

condition of use.

 7- If improper venting is observed during any of the above

tests, the common venting system must be corrected.

Horizontal Venting

This furnace is design certified by the American Gas

Association for horizontal venting through an outside

wall  only  with  the  use  of  a  Field  Controls  Company

Model #SWG-5L side wall venting kit available from

Lennox  Dealer  Service Center.  No  other  Field  brand

venting kit or any other manufacturer's venting kit is acĆ

ceptable. Horizontal venting of this furnace without the

use of the above stated kit is prohibited. See figure 11

for field wiring of side wall horizontal venting kit.
When horizontally vented, minimum clearance for terĆ

mination from electric meters, gas meters, regulators

and relief equipment is 4 ft. (1.2m).
At vent termination, care must be taken to maintain proĆ

tective coatings over building materials (prolonged exĆ

posure to exhaust condensate can destroy protective

coatings). It is recommended that the exhaust outlet not

be located within 6 ft. (1.8m) of a condensing unit beĆ

cause the condensate can damage the painted coating.

SIDE WALL VENTING KIT WIRING

C

L1
L2

120VAC

3
1

PPC-5

(OPTIONAL)

M

L1

M

N

T1 T2 T3

W

R

Y

G

W

G

R

Y

24 VAC

THERMOSTAT

THERMOSTAT CONNECTIONS

TERMINAL IN FURNACE

JUNCTION BOX

RELAY

CK-40 CONTROL BOX

PRESSURE

SWITCH

SWG

POWER

VENTER

MOTOR

A
B

7

5

FIGURE 11

T

FIELD INSTALLED WIRING

FACTORY INSTALLED WIRING

NO

Summary of Contents for G20R series

Page 1: ...BLESHOOTING 20 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WHAT TO DO IF YOU SMELL GAS If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life WARNING Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Installation and service must be performed ...

Page 2: ...ecĆ tion or to help in alignment with cooling coil ă Dimensions before flanges are bent as shipped Dimensions after flanges are bent Dimension after flange furnished is field installed on unit M d l N A B C C D D E Model No inch mm inch mm inch mm inch mm inch mm inch mm inch mm G20RQ2 3 X EĆ50 G20RQ3 X EĆ75 16Ć1 4 413 14Ć1 8 359 10Ć3 4 273 12 305 1Ć1 2 38 2Ć1 8 54 3Ć1 8 79 G20RQ4 X EĆ75 21Ć1 4 54...

Page 3: ...Y LIMIT CONTROL CABINET ROLL OUT SWITCH GAS VALVE PILOT ELECTRODE ASSEMBLY FLUE TRANSITION LOWER ACCESS PANEL FILTER ACCESS DOOR DOOR INTERLOCK SWITCH BCC CONTROL REMOVABLE STRIP BLOCKED VENT SHUT OFF SWITCH DAMPER MOTOR GEAR PATCH PLATE PATCH PLATE SPRING DAMPER SWITCH DAMPER SWITCH COVER ROLL OUT SWITCH DAMPER BURNER BOX DAMPER BOX PARTS ARRANGEMENT G20R Units Shown REMOVABLE BURNER BOX TOP FIGU...

Page 4: ...stible material other than wood flooring For installation in a residential garage unit must be installed so that burner s and ignition source are loĆ cated no less than 18 in 457 mm above floor Furnace must be located or protected to avoid physical damage by vehicles Unit must be adjusted to obtain a temperature rise within the range specified on appliance rating plate The draft hood shall be inst...

Page 5: ...xhaust vents and gas pipĆ ing A portion of this information has been reprinted with permission from the National Fuel Gas Code ANSI Z223 1 This reprinted material is not the complete and official position of the ANSI on the referenced subject which is represented only by the standard in its entirety In Canada refer to the standard CAN CGA B149 1 and B149 2 installation codes Combustion Air Require...

Page 6: ...ATER HEATER OPENINGS To Adjacent Room FIGURE 3 NOTE Each opening shall have a free area of at least one square inch per 1 000 Btu per hour of the total input rating of all equipment in the enclosure but not less than 100 square inches G20R FURNACE CHIMĆ NEY OR GAS VENT Air from Outside If air from outside is brought in for combustion and venĆ tilation the confined space must have two permanent ope...

Page 7: ... FLOOR UNIT Front to Rear Side to Side in mm in mm Q2 3 50 Q3 75 Q4 75 Q3 4 100 Q5 100 Q3 125 Q4 5 125 Q4 5 150 20 1 2 20 1 2 20 1 2 20 1 2 520 520 520 520 12 1 4 17 1 4 22 1 4 27 1 4 311 438 565 692 NOTE Floor opening dimensions listed are 1 4 6mm larger than unit openings 2 Flange warm air plenum and lower into opening 3 Use duckbill pliers to bend unit flanges out from openĆ ing Install provide...

Page 8: ...turn air plenum A door must never be used as a portion of the return air duct system Allow absolutely no sagging cracks gaps etc For no reason should return and supply air duct systems ever be connected to or from other heatĆ ing devices such as a fireplace or stove etc Fire explosion carbon monoxide poisoning personal injury and or property damage could result WARNING Blower door must be securely...

Page 9: ...lothes dryers and any appliances not connected to the common venting system Turn on any exhaust fans such as range hoods and bathĆ room exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Follow the lighting instructions Place the appliance being inspected in operation Adjust thermostat so appliance will operate continuously 5 Test for spill...

Page 10: ... properly labeled by the inĆ staller FIGURE 12 GROUND JOINT UNION AUTOMATIC GAS VALVE with manual shut off valve FIELD PROVIDED AND INSTALLED GROUND JOINT UNION LEFT SIDE PIPING STANDARD RIGHT SIDE PIPING ALTERNATE AUTOMATIC GAS VALVE with manual shut off valve DRIP LEG DRIP LEG MANUAL MAIN SHUT OFF VALVE With 1 8 NPT Plugged Tap Shown MANUAL MAIN SHUT OFF VALVE With 1 8 NPT Plugged Tap Shown TABL...

Page 11: ...0 110 43 3700 104 77 3450 97 69 3250 92 03 4 101 6 4 026 102 260 23000 651 27 15800 447 39 12800 362 44 10900 308 64 9700 274 67 8800 249 18 8100 229 36 7500 212 37 7200 203 88 6700 189 72 NOTE Capacity given in cubic feet of gas per hour kilo liters of gas per hour and based on 0 60 specific gravity gas ...

Page 12: ...plugs are provided on both sides of cabinet to facilitate wiring 3 Install room thermostat according to instructions proĆ vided with thermostat 4 Install a separate fused disconnect switch near the unit so power can be turned off for servicing 5 Route thermostat wire as shown in figure 14 Keep wire away from draft hood and flue pipe Do not route wire across draft hood 6 Complete wiring connections...

Page 13: ...NAL COOLING SPEED TAP TERMINAL DUMMY TERMINALS CONTINUOUS FAN TERMINAL THERMOSTAT JUMPER Electronic or Mechanical FIGURE 16 Y R W G G W Y T R BCC CONTROL THERMOSTAT IGNITION CONTROL GAS VALVE DAMPER DOOR SWITCH FLAME ROLLOUT SWITCH PRIMARY LIMIT BLOCKED VENT SHUTOFF SWITCH BLACK WHITE TO COMPRESSOR CONTACTOR FIELD INSTALLED LOW VOLTAGE FIELD INSTALLED LINE VOLTAGE TYPICAL G20R FIELD WIRING DIAGRAM...

Page 14: ...Page 14 FIGURE 17 TYPICAL G20R WIRING DIAGRAM ...

Page 15: ...l automatically light The pilot goes out when there is no demand for heat WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life Gas Valve Operation Figures 19 20 1 STOP Read the safety information at the beginning of this section 2 Set thermostat to lowest setting See figure 18 3 Turn off all electrical power ...

Page 16: ... Gas Pressure 1 Check gas line pressure with unit firing at maximum rate A minimum of 4 5 w c 1 12kPa for natural gas or 10 5 w c 2 61kPa for LP propane gas should be maintained 2 After line pressure has been checked and adjusted check manifold pressure Correct manifold presĆ sure for LP propane gas is 9 5 w c 2 36kPa No adĆ justment is needed in high altitude applications A natural gas to LP prop...

Page 17: ...ning 5 Grasp blower motor harness connector located on back on motor Depress lock tab and pull connector from motor 6 Pull harness connector and wires through blower acĆ cess panel opening 7 Select desired taps for heating and cooling White common Red heating Black cooling 8 Depress harness connector tab to release wire termiĆ nal Select connector location for new speed refer to unit wiring diagra...

Page 18: ...wing procedure and figure 27 to clean filter TABLE 5 MODEL NO FILTER SIZE Q2 3 50 Q3 75 Q4 75 Q3 4 100 Q5 100 Q3 125 Q4 5 125 20 X 10 X 1 20 X 12 X 1 20 X 14 X 1 Q4 5 150 20 X 16 X 1 FIGURE 27 BLOWER RIGHT FILTER LEFT FILTER LEFT SUPPORT ANGLE RIGHT FILTER SUPPORT ANGLE ON THREE SIDES 150 UNITS MAKE SURE FILTER IS PLACED INTO THIS CHANNEL 150 UNITS ROTATE FILTER TO REMOVE TAB 1 Turn off electric p...

Page 19: ...h Continue with items 13 through 15 below and reinstall flame rods and springs 13 Clean top of burner ports with a wire brush See figĆ ure 29 14 Clean burner ports by inserting a cleaning tool made from a piece of sheet metal cut to fit the burner ports and work in and out of each port See figure 30 15 Clean inside of each burner with a bottle cleaning brush See figure 31 CLEANING TOP FIGURE 29 CL...

Page 20: ... burner with pilot mount Flue baffles Pilot electrode assembly Primary limit control Flame roll out switch Blocked vent shut off switch Damper motor Damper switch Couplings Damper spring Grommets G20RE START UP AND PERFORMANCE CHECK LIST Filter Clean Secure Supply Voltage Electrical Connections Tight START UP AND PERFORMANCE CHECK LIST Job Name Job Location Installer Unit Model No Furnace Btu Inpu...

Page 21: ... REPLACE BCC NO IS 120VAC ACROSS N CAB CHECK DAMPER MOTOR WIRING AND DAMPER MOTOR YES YES IS UNIT LIT NO CHECK 1 DAMPER MOTOR 2 IGNITION CONTROL 3 GAS VALVE 4 IGNITOR 5 LIMIT SWITCHES 6 PROVE SWITCH YES IS BLOWER RUNNING ON LOW SPEED 45 SEC AFTER FURNACE LIGHTS NO IS 120VAC ACROSS N H YES IS 24VAC ACROSS C V REPLACE BCC NO NO CHECK WIRING YES IS 120VAC ACROSS N ACC YES REMOVE R W JUMPER AFTER THE ...

Reviews: