background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

12

Figure 20

Purging Air from Appliance 

Purge air from appliance by holding gas control valve down in the pilot 
position until pilot will light (see Figure 20). 

DO NOT LIGHT A MATCH IF 

YOU SMELL GAS. 

Light a match then allow gas fl ow to pilot.  If the Match 

“blows”, there is air in the line (purge line). If the fl ame is straight and tall, 
there is no gas pressure.

Purging Air from Supply Line 

a. Turn gas supply line valve off.
b. Loosen setscrew at inlet pressure tap on control valve (see Figures 32 & 33).
c. Turn gas supply line valve on.
d. When gas fl ows, turn supply valve off.
e. Close the inlet pressure tap.

Figure 18

Factory Built Fireplace Installation Diagram

Storm Collar

Roof
Flashing

Remove or Secure 
Damper Open

Note:  Final gas connection should be made after unit is in place to avoid 
damage to line when pushing the unit into position.

Step 9. CONNECTING GAS LINE 

G

AS CONNECTION

This appliance is equipped with a gas fl ex line for use (where permit-
ted) in connecting the unit to the gas line.  A gas fl ex line is provided 
to aid in attaching the B-Vent appliance to the gas supply.  The gas fl ex 
line can only be used where local codes permit. See Figure 19 for fl ex 
line description. The fl ex line is rated for both natural and propane gas. 
A manual shut off valve is also provided with the fl ex line. The gas con-
trol valve is located in the lower control compartment. To access the 
valve, open the lower access door. The millivolt control valve has a 3/8" 
(10 mm) NPT thread inlet port fi tting. 

Make gas line connections. All codes require a shut-off valve mounted in 
the supply line. Figure 19 illustrates two methods for connecting the gas 
supply. The fl ex-line method is acceptable in the U.S., however, Canadian 
requirements vary depending on locality. Installation must be in compliance 
with local codes.

Figure 19

4" diameter vent, 
type B-Vent or listed 
gas fuel type vent 
liner (listed to UL 
1777) 

SEE FIREPLACE 

REQUIREMENTS 

ON PAGE 4

The fl exible vent pipe must 
NOT be allowed to sag behind  
insert or in fi replace fl ue.

Flashing

Termination Cap

Liner

2 Hose 
Clamps

Vertical 
Term. Cap

Collar

Vent Kits, HO906 (25')
& H0907 (35') includes:
1 ea. fl ex liner
1 ea. fl ashing
1 ea. collar
2 ea. hose clamps
(see table 9)

Liner Requirements:
Exhaust  Vent = 4" Dia. 
B-Vent or Liner listed to 
UL 1777
Vertical Height Min. 
     = 12 ft. (3.66 M)
Vertical Height Max. 
     = 40 ft. (10.7 M)

AIR PURGING PROCEDURES MUST BE PERFORMED BY A QUALIFIED 
TECHNICIAN ONLY.

Step 10. PURGING AIR

When lighting the appliance for the fi rst time, 
it will take a few minutes to purge air from the 
gas line. Once purging is complete, the pilot 
and burner will light and operate as indicated 
in the instruction manual. Subsequent light-
ings of the appliance will not require such 
purging. Inspect the pilot fl ame (remove logs, 
if necessary, handling carefully).

                   IMPORTANT

Under no circumstances, may separate sections of 
concentric fl exible vent pipe be joined together.

Gas Valve

3/8" NPT  x

Flare Fitting

3/8" Flex Tubing

3/8" Nipple

3/8" Union

3/8" Close Nipple

3/8" Shut-Off Valve

1/2" x 3/8"

Reducer

Gas

Stub

1/2" x 3/8" Flare

Shut-Off Valve

Gas Flex Line Connector

Summary of Contents for EVB125

Page 1: ...DONN DANS CETTE NOTICE POURR DUIREAUMINIMUMLERISQUED INCENDIE OUPOUR VITERTOUTDOMMAGEMAT RIEL TOUTE BLESSURE OU LA MORT POUR VOTRE S CURIT Que faire si vous sentez une odeur de gaz Ne pas tenter d all...

Page 2: ...ermiculite one propane conversion kits One Warranty Certificate One Fireplace Warning Label One Draft Hood Sliding Tool This gas fireplace heater is a natural con vection heat circulating gas fireplac...

Page 3: ...SUPPLY TO THE APPLIANCE AND HAVE IT SERVICED BY A QUALIFIED PROFES SIONAL AS IT MAY NOT BE OPERATING PROPERLY WARNING CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OFHIGHSURFACETEMPERATURES USE...

Page 4: ...irements Familiarity with these requirements before installation is essential Some important considerationstodiscusswithlocalbuilding officials include 1 Applicablecodes i e UniformMechanical Code Sta...

Page 5: ...5 8 702 mm L 10 7 8 276 mm F 19 3 8 493 mm M 24 7 8 632 mm G 1 15 16 49 mm The total glass viewing area equals approx 270 1 2 Sq In SPECIFICATIONS Natural Gas BTU Input 17 000 to 25 000 Propane Gas BT...

Page 6: ...D 30 1 4 768 mm LG 30 762 mm L 12 3 8 314 mm F 20 7 8 530 mm M 23 7 16 595 mm G 1 13 16 46 mm SPECIFICATIONS Natural Gas BTU Input 21 500 to 30 000 Propane Gas BTU Input 22 000 to 28 000 B Vent Size 4...

Page 7: ...ight Side Wall A G E C B Hearth Protection Side View TopofInsert Mantel Clearance Model EBVI30 The mantel should be located in the shaded area light gray shown below Existing Fireplace Hearth F 15 14...

Page 8: ...pipe Refer to table 7 for suggested sizing of the gas supply line if black iron pipe is being used The gas supply line should be connected to the appliance at step 9 page 12 The gas supply line shoul...

Page 9: ...OR MECHANICAL WEAKNESSES SUCH AS CRACKS LEAKY JOINTS CORRODED OR WARPED SURFACES THE FAULTY POR TION MUST BE REPAIRED OR REPLACED PRIOR TO INSTALLING THIS APPLIANCE Step 3 UNPACK THE INSERT Remove the...

Page 10: ...termiation below the wall or parapet when distance is less than 10 ft as shown below wall or parapet wall or parapet No height above wall or parapet is required when dis tance is greater than 10 ft 7...

Page 11: ...e it forward aligning with guide brackets until the screw hole in the spill tube aligns with the screw hole in the top of the firebox see Figure 12 Secure two parts in place with removed screw While p...

Page 12: ...access door The millivolt control valve has a 3 8 10 mm NPT thread inlet port fitting Make gas line connections All codes require a shut off valve mounted in the supply line Figure 19 illustrates two...

Page 13: ...d fit onto corresponding pins and or log stoppers This will ensure a proper flame and safe combustion 1 Place the rear log onto the 2 corresponding locating pins at the back of the firebox as shown in...

Page 14: ...ont of the forward logs Figure 29 Figure 30 9 Place some vermiculite around the logs as shown in Figure 30 the entire bag of vermiculite will NOT be used Vermiculite Figure 27 7 Install the Top Right...

Page 15: ...donthe surround assembly see Figure 34 or operate the burner with the optional remote control wall thermostat or control switch Control Compartment Access Pull down hinged door to access control compa...

Page 16: ...e the dial down clockwise just past the click the first ON position for the highest speed setting Turning the knob further clockwise will provide slower blower speeds Note If the rheostat is not turne...

Page 17: ...ansparent These weak blue and transparent flames are termed anemic If the air shutter openings are too small sooting may develop IMPORTANT ENSURE THAT THE FRONT GLASS PANEL IS IN PLACE AND SEALED DURI...

Page 18: ...N 9 1466A SERIAL NUMBER NOMBRE DE SERIE XXX XXX IIIIIIIIIIIIIIIIIIII XXX P N 9 1466A MANTEAU DU DESSUS DE L APPAREIL MAX MAX MODEL NO EBVI25 MANUFACTURED AT Lynwood CA FOR USE WITH NATURAL GAS EQUIPE...

Page 19: ......

Page 20: ...time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for code requirements for your area LHP 1110 West Taft A...

Reviews: