background image

Page 27

Eroded electrode tips.
Improper electrode gap spacing.

Cracked or chipped insulators.

Cracked or burned lead insulators.

Improper position of electrode tips.

Low line voltage.

No spark or weak spark.

Low line voltage.

Pump or blower overloading motor.
Faulty motor.

Unbalanced fire.

Too much air - lean short fire.

Too little air - long dirty fire.

Excessive draft.

Too little draft or restriction.
Dirty cad cell face.
Faulty cad cell - exceeds 15000 ohms.

Loose or defective cad cell wires.

Primary control circuit defective.

Unbalanced fire.

Too much air - lean short fire.

Too little air - long dirty fire.

Excessive draft.

Too little draft or restriction.
Dirty cad cell face.
Faulty cad cell - exceeds 15000 ohms.

Loose or defective cad cell wires.

Pump loses prime - air slug.
Pump loses prime - air leak in supply

line.
Water slug in line.

Partially plugged nozzle or nozzle 

strainer.

Restriction in oil line.
Plugged fuel pump strainer.
Cold oil - outdoor tank.

Fouled or shorted electrodes.
Dirty electrodes and leads.

TROUBLE SOURCE

PROCEDURE

CAUSES

CORRECTION

PRIMARY

CONTROL

IGNITION

ELECTRODES

Remove gun assembly and 
inspect electrodes and leads

.

Clean electrode leads.

Dress-up electrode tips & reset gap to

1/8" (3.2mm) and correctly position tips

using the AFII multipurpose gauge

T-500.

Replace electrode.
Replace electrode Leads.

IGNITION

TRANSFORMER

BURNER

MOTOR

POOR FIRE

FLAME

DETECTOR

POOR FIRE

FLAME

DETECTOR

OIL SUPPLY

Connect ignition leads to
transformer. Start burner and
observe spark. Check line
voltage to transformer primary.

Check voltage at power source.

Correct cause of voltage drop or call

power company.

Properly ground transformer case.

Check voltage at power source.

Correct cause of voltage drop or call

power company.

Motor does not come up to

speed and trips out on

overload. Turn off power and

rotate blower wheel by hand

to check for binding or

excessive drag.

Correct cause of overloading.
Replace motor.

After burner

fires,

immediately

jumper

across flame

detector

terminals at

primary

control.

If burner continues

to run, fault may

be due to poor

fire. Inspect fire.

If fire is good, fault

is in the flame

detector. Check

detector circuit.

If burner locks out

on safety, fault is in

primary control.

Adjust Barometric damper for

correct draft.

Replace nozzle.
Reduce combustion air

Check combustion.

Increase combustion

airCheck combustion.

Correct draft or remove restriction.
Clean cad cell face.
Replace cad cell.
Secure connections or replace cad 

cell holder and wire leads.

Replace primary control.

After burner

fires,

immediately

jumper

across flame

detector

terminals at

primary

control.

Listen for pump whine.

If burner

continues to run

(does not lock

out on safety),

fault may be

poor fire

(marginal).

Inspect fire.

Replace nozzle.

Reduce combustion air - check 

combustion.

Increase combustion air - check 

combustion.
Adjust barometric damper for

correct draft.
Correct draft or remove restriction.

If fire is good fault

is in the flame

detector. Check

detector circuit.

Clean cad cell face.
Replace cad cell.
Secure connections or replace cad 

cell holder and wire leads.

If burner loses flame

(does not lock out

on safety), fault is in

fuel system.

Prime pump at bleed port.
Check supply line for loose

connections and tighten fittings.

Check oil tank for water (over 1"

[25.4mm]) pump or drain out water.

Replace nozzle.

Clear restriction.
Clean strainer or replace pump.
Change to number 1 oil.

Summary of Contents for Elite 80 Series

Page 1: ...furnaces use Beckett oil burners with heating capacities of 105 000 to 154 000 Btuh 30 8 kW to 45 1 kW OF24 units are suitable for residential or commercial application The drum type heat exchanger co...

Page 2: ...203 12 x 9 305 x 229 Blower Data Blower pulley in mm 7 178 Belt size in mm 40 1016 41 1041 cfm L s at 20 in wg 50 Pa external static pressure 820 390 1170 550 1550 730 Number and size of filters in mm...

Page 3: ...in mm 10 x 8 254 x 203 12 x 9 305 x 229 Blower Data Blower pulley in mm 7 178 Belt size in mm 41 1041 42 1067 cfm L s at 20 in wg 50 Pa external static pressure 1300 615 105 input 1220 575 120 input...

Page 4: ...URNER INDOOR BLOWER BLOWER MOTOR OBSERVATION PORT CLEAN OUT PORT FLUE OPENING HEAT EXCHANGER COMBUSTION AIR INTAKE FIGURE 2 OF24 GENERAL PARTS ORIENTA TION CLEAN OUT PORT FAN LIMIT SWITCH BECKETT AFII...

Page 5: ...identifies the burners used in Lennox units Figure 3 shows the typical layout of the burner assembly 1 Combustion Air Blower Pump Motor B6 The burner is activated by the primary control A com bustion...

Page 6: ...OZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET DOOR GASKET REAR ACCESS COUPLING OIL PUMP PLATE ESCUTCHEON NUT SPLINED DOOR ASSY REAR ACCESS ASSY HOUSING MAIN HOLE PLUG SCREWS AIR TUBE FLANGE ASSY EL...

Page 7: ...in the O24 OF24 The firing rate dictates which head is used See table 1 The greater the FB number the larger the slots on the head When combustion takes place the flame will be cylindrical compact sha...

Page 8: ...an air free fuel to the burner An oil filter is required for all models Use an oil filter of gener ous capacity for all installations Install filter inside the building between the tank shut off valve...

Page 9: ...g g Single Stage Two Stage Single Stage Two Stage 0 0 0 m 84 25 6 m 93 28 3 m 100 30 5 m 100 30 5 m 2 0 6 m 73 22 3 m 85 25 9 m 100 30 5 m 100 30 5 m 4 1 2m 63 19 2 m 77 23 5 m 100 30 5 m 100 30 5 m 6...

Page 10: ...not pass through a floor or ceiling Clear ances to single wall vent pipe should be no less than 6 152 mm more if local codes require it 8 The vent may pass through a wall where provisions have been m...

Page 11: ...rements for exhaust vents and oil piping Combustion Air Requirements CAUTION Insufficient combustion air can cause headaches nausea dizziness or asphyxiation It will also cause excess water in the hea...

Page 12: ...tilation the confined space shall be provided with two permanent openings One opening shall be within 12 305 mm of the top of the enclosure and one within 12 305 mm of the bottom These openings must...

Page 13: ...from confined space to out side combustion air simply remove the three screws at taching the inlet air scoop to the burner and insert 4 102 mm direct air intake piping The use of a barometric relief p...

Page 14: ...be located within 18 457 mm of the furnace vent outlet See figure 15 for barometric draft con trol location III START UP A Preliminary and Seasonal Checks 1 Inspect electrical wiring both field and f...

Page 15: ...inimum FIGURE 16 AFII ELECTRODE TIP GAP To position the electrode tips beyond the face of the nozzle and above the center line position the gauge as shown in figure 17 Align the center mark with the n...

Page 16: ...retention head burners Oil furnace installations also require careful inspection to make sure the chimney is in good condition and can ac commodate the products of combustion The temperature in uncon...

Page 17: ...mbly will come out of the furnace There is adequate wire to remove the burner without disconnecting wires Once removed just turn the burner around in the vest panel area NOTE Before disassembling any...

Page 18: ...rom the primary control If the motor and blower wheel only need to be removed to check and clean there is adequate wire in the motor wiring harness without disconnecting 3 Loosen two bolts securing mo...

Page 19: ...atmosphere 3 With only the blower motor running and the evapora tor coil dry observe the manometer reading Adjust blower motor speed to deliver the air desired accord ing to the job requirements 4 Pr...

Page 20: ...as described in section IV D Supply Air Blower 1 Disconnect power to unit 2 Check and clean blower wheel 3 Motors are prelubricated for extended life no further lu brication is required E Vent Pipe Th...

Page 21: ...close energizing combustion air blower pump B6 3 When 1K2 closes the electronic ignitor is energized When 1K1 closes the solid state switch and cad cell are energized When the cad cell senses light t...

Page 22: ...NCE 1 When 1K2 closes 120VAC is routed through the relay timer electronic ignitor A73 and the limit switch 2 The relay timer energizes the venter motor 3 After the venter motor establishes a draft the...

Page 23: ...RATION SEQUENCE 1 When 1K2 closes 120VAC is routed through the relay 2 The relay energizes the venter motor 3 After the venter motor establishes a draft the N O fan proving switch closes completing th...

Page 24: ...lution Close all leaks with cement Problem Failure to extend the length of the flue partition down to the floor Detected by inspection or smoke test Solution Extend partition to floor level Problem Sm...

Page 25: ...r leak around cover Be sure strainer cover screws are tightened securely Check for damaged cover gasket To determine the cause of improper cutoff insert a pressure gauge in the nozzle port of the fuel...

Page 26: ...r auxiliary control switch open Open circuit between disconnect switch and limit control Low line voltage or power failure Defective internal control circuit Jumper terminals if burner starts switch i...

Page 27: ...ll power company Properly ground transformer case Check voltage at power source Correct cause of voltage drop or call power company Motor does not come up to speed and trips out on overload Turn off p...

Page 28: ...hermostat in warm air draft Dirty furnace air filters Blower running too slow Blower motor seized or burned out Blower wheel in backwards Wrong motor rotation Restrictions in return or supply air syst...

Reviews: