Page 47
NOTE-
To obtain accurate reading, shut off all other gas
appliances connected to meter.
TABLE 21
GAS METER CLOCKING CHART
EL296
Unit
Seconds for One Revolution
Natural
LP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
Dial
-045
80
160
200
400
-070
55
110
136
272
-090
41
82
102
204
-110
33
66
82
164
Natural-1000 btu/cu ft LP-2500 btu/cu ft
IMPORTANT
For safety, connect a shut-off valve between the
manometer and the gas tap to permit shut off of gas
pressure to the manometer.
G- Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking com
-
bustion. See sections E- and F-. Take combustion sample
beyond the flue outlet. Table 22 shows acceptable com
-
bustions. The maximum carbon monoxide reading should
not exceed 100 ppm.
TABLE 22
EL296
Mode
l
CO
2
% For Nat
CO
2
% For L.P
Low Fire
High Fire
Low Fire
High Fire
045
5.6 - 6.6
7.8 - 8.8
6.6 - 7.6 9.1 - 10.1
070
5.5 - 6.5
7.3 - 8.3
6.5 - 7.5
8.6 - 9.6
090
5.9 - 6.9
7.8 - 8.8
6.9 - 7.9 9.1 - 10.1
110
6.3 - 7.3
8.2 - 9.2
7.3 - 8.3 9.5 - 10.5
The maximum carbon monoxide reading should not exceed 100ppm.
H- High Altitude
The manifold pressure, gas orifice and pressure switch
may require adjustment or replacement to ensure proper
operation at higher altitudes. See table 23 for gas conver
-
sion and pressure switch kits. See table 24 for manifold
pressures
TABLE 23
Conversion Kit and Pressure Switch Requirements at Varying Altitudes
Unit
Natural to
LP/Propane
High Altitude
Natural Burner
Orifice Kit
High Altitude LP/
Propane Burner
Orifice Kit
High Altitude Pressure Switch
0 - 7500 ft
7501 - 10,000 ft
7501 - 10,000 ft
4501 - 7500 ft
7501 - 10,000 ft
-045
*11K51
73W37
*11K46
14A47
14A50
-070-1, -2
14A46
14A51
-070-3 & later
14A55
14A56
-090
14A54
14A53
-110
14A46
14A51
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit. Pressure switch is factory
set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).
TABLE 24
Conversion Kit and Pressure Switch Requirements at Varying Altitudes
Unit
Natural to
LP/Propane
High Altitude
Natural Burner
Orifice Kit
High Altitude LP/
Propane Burner
Orifice Kit
High Altitude Pressure Switch
0 - 7500 ft
7501 - 10,000 ft
7501 - 10,000 ft
4501 - 7500 ft
7501 - 10,000 ft
-045
*11K51
73W37
*11K46
14A47
14A50
-070-1, -2
14A46
14A51
-070-3 & later
14A55
14A56
-090
14A54
14A53
-110
14A46
14A51
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit. Pressure switch is factory
set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).