Page 32
Intake Piping
The EL296DFE furnace may be installed in either
direct
vent
or
non-direct vent
applications. In non-direct vent
applications, when intake air will be drawn into the furnace
from the surrounding space, the indoor air quality must be
considered. Guidelines listed in Combustion, Dilution and
Ventilation Air section must be followed.
Follow the next two steps when installing the unit in
Direct
Vent applications
, where combustion air is taken from
outdoors and flue gases are discharged outdoors.
The
provided air intake screen must not be used in direct
vent applications (outdoors)
.
1 -
Use cement or a sheet metal screw to secure the
intake pipe to the inlet air connector.
2 -
2 - If intake air is drawn from a ventilated crawlspace
(FIGURE 28) or ventilated attic (FIGURE 27) the
exhaust vent length must not exceed those listed
in table 9. If 3” diameter pipe is used, reduce
to 2” diameter pipe to accommodate the debris
screen.
3 - 3 - Route piping to outside of structure. Continue
with installation following instructions given in
general guide lines for piping terminations and
intake and exhaust piping terminations for direct
vent sections. Refer to TABLE 17 for pipe sizes.
CAUTION
If this unit is being installed in an application with
combustion air coming in from a space serviced by
an exhaust fan, power exhaust fan, or other device
which may create a negative pressure in the space,
take care when sizing the inlet air opening. The
inlet air opening must be sized to accommodate the
maximum volume of exhausted air as well as the
maximum volume of combustion air required for all
gas appliances serviced by this space.
NOTE
-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Furnace
Ventilation
Louvers
(Crawl space)
*Intake Debris Screen Provided)
Inlet Air
(Minimum
12 in.(305mm)
Above crawl
space floor)
Coupling or
3 in. to 2 in.
Transition
(Field Provided)
FIGURE 27
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
NOTE
-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
Ventilation Louvers
Inlet Air
(Minimum
12 in.(305mm) Above
attic floor)
Roof Terminated
Exhaust Pipe
Furnace
*Intake Debris
Screen
(Provided)
FIGURE 28