background image

Page 29

EL16XP1 OPERATING SEQUENCE

This  is  the  sequence  of  operation  for  EL16XP1  series 

units. The sequence is outlined by numbered steps which 

correspond to circled numbers on the adjacent diagram. 

The  steps  are  identical  for  both  cooling  and  first  stage 

heating  demand  with  the  exception  reversing  valve  L1 

is  energized  during  cooling  demand  and  de-energized 

during heating demand. 

NOTE

 – 

Transformer in indoor unit supplies power (24 

VAC) to the thermostat and outdoor unit controls.

 

COOLING: 

Internal thermostat wiring energizes terminal O by cooling 

mode selection, energizing the reversing valve L1. 

1 - 

Demand initiates at Y1 in the thermostat. 

2 - 

24VAC energizes compressor contactor K1. 

3 - 

 K1-1 N.O. closes, energizing compressor (B1) and 

outdoor fan motor (B4). 

END OF COOLING DEMAND: 

4 - 

Demand is satisfied. Terminal Y1 is de-energized. 

5 - 

Compressor contactor K1 is de-energized. 

6 -   K1-1 opens and compressor (B1) and outdoor fan 

motor (B4) are de-energized and stop immediately. 

FIRST STAGE HEAT: 

Internal  thermostat  wiring  de-energizes  terminal  O  by 

heating mode selection, de-energizing the reversing valve 

L1. 
See steps 1, 2 and 3. 

End of FIRST STAGE HEAT: 

See steps 4, 5 and 6. 

DEFROST MODE: 

When  a  defrost  cycle  is  initiated,  the  control  energizes 

the reversing valve solenoid and turns off the condenser 

fan. The control will also put 24VAC on the “W1” (auxil

-

iary heat) line. The unit will stay in this mode until either 

the coil sensor temperature is above the selected termi-

nation temperature, the defrost time of 14 minutes has 

been completed, or the room thermostat demand cycle 

has been satisfied. (If the temperature select shunt is not 

installed, the default termination temperature will be 90°F.) 

If the room thermostat demand cycle terminates the cycle, 

the defrost cycle will be held until the next room thermo

-

stat demand cycle. If the coil sensor temperature is still 

below the selected termination temperature, the control 

will continue the defrost cycle until the cycle is terminated 

in one of the methods mentioned above. If a defrost is ter-

minated by time and the coil temperature did not remain 

above 35°F (2°C) for 4 minutes the control will go to the 

30-minute Time/Temperature mode.

Servicing Units Void of Charge  

If the outdoor unit is void of refrigerant, clean the system 

using the procedure described below.

1 - 

 Leak  check  system  using  procedure  outlined  on 

page 16.

2 -   Evacuate the system using procedure outlined on 

page 17.

3 -   Use nitrogen to break the vacuum and install a new 

filter drier in the system.

4 -   

Evacuate the system again using procedure 

outlined on page 17.

5 -   Weigh in refrigerant. 

Start-Up  

 IMPORTANT

If unit is equipped with a crankcase heater, it should 

be  energized  24  hours  before  unit  start-up  to  prevent 

compressor damage as a result of slugging.

1 -  Rotate fan to check for binding. 
2 - 

 Inspect all factory and field-installed wiring for loose 

connections. 

3 -   After evacuation is complete, open the liquid line 

and suction line service valves to release the 

refrigerant charge (contained in outdoor unit) into 

the system. 

4 - 

 Replace the stem caps and tighten as specified in 

Operating Service Valves on page 7. 

5 -   Check voltage supply at the disconnect switch. The 

voltage must be within the range listed on the unit's 

nameplate. If not, do not start the equipment until 

you have consulted with the power company and 

the voltage condition has been corrected. 

6 - 

 Set  the  thermostat  for  a  cooling  demand.  Turn 

on power to the indoor indoor unit and close the 

outdoor unit disconnect switch to start the unit. 

7 -   Recheck voltage while the unit is running. Power 

must be within range shown on the nameplate. 

8 - 

 Check  system  for  sufficient  refrigerant  by  using 

the procedures listed under Start-Up and Charging 

Procedures. 

9 -   Recheck voltage while the unit is running. Power 

must be within range shown on the nameplate.

Summary of Contents for EL16XP1 Series

Page 1: ...cation 2 Dimensions 3 Specifications 4 Typical Unit Parts Arrangement 6 Operating Gauge Set and Service Valves 6 Unit Placement 8 New or Replacement Line Set 9 Brazing Connections 11 Flushing Line Set...

Page 2: ...ides may be A clearance of 24 in must be maintained between two units 48 in 1219 mm clearance required on top of unit Model Number Identification Nominal SEER Unit Type P Heat Pump Outdoor Unit Refrig...

Page 3: ...SUPPORT FEET EL16XP1 018 TO 030 BASE SECTION Medium Base EL16XP1 036 TO 060 BASE SECTION Large Base 13 7 8 352 3 5 8 92 20 5 8 524 7 3 4 197 27 1 8 689 4 1 2 114 3 1 4 83 Depth Width Model No A B C in...

Page 4: ...0 98 0 98 0 96 0 99 Outdoor Fan Motor Full load amps 1 0 1 0 1 0 2 6 Locked rotor amps 1 9 1 9 1 9 CONTROLS iComfort E30 Smart Wi Fi Thermostat 15S63 Remote Outdoor Temperature Sensor X2658 OPTIONAL A...

Page 5: ...99 0 99 Outdoor Fan Motor Full load amps 2 6 2 6 2 6 CONTROLS iComfort E30 Smart Wi Fi Thermostat 15S63 Remote Outdoor Temperature Sensor X2658 OPTIONAL ACCESSORIES ORDER SEPARATELY Compressor Hard S...

Page 6: ...stripping of the various caps used the appropriately sized wrench should be used and fitted snugly over the cap before tightening TABLE 1 Torque Requirements Parts Recommended Torque Service valve cap...

Page 7: ...7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately...

Page 8: ...ent of unit in relation to a window see the provided illustration in figure 3 detail A PLACING UNIT ON SLAB When installing unit at grade level the top of the slab should be high enough above grade so...

Page 9: ...be a Polyol ester oil The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet Recommend adding oil to system based on the amount of refrigerant charge in the sys...

Page 10: ...be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Page 11: ...dous to your health Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns...

Page 12: ...SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AND D...

Page 13: ...tions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE...

Page 14: ...ISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN HCFC22 TO BE USED FOR FLUSHING LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE...

Page 15: ...reads and expose surface of the Teflon ring with refrigerantoil E Attach the liquid line assembly to the expansion valve Finger tighten and use an appropriately sized wrench to turn an additional 1 2...

Page 16: ...gauge set Disconnect the HFC 410A cylinder C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set D Adjust dry nitrogen pressure to 150 psig...

Page 17: ...r unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the...

Page 18: ...to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air han dler for low voltage control power 24...

Page 19: ...CY HEAT EMERGENCY HEAT RELAY OUTDOOR THERMOSTAT THERMOSTAT INDOOR UNIT OUTDOOR UNIT COMMON 1ST STAGE AUXILIARY HEAT INDOOR BLOWER COMPRESSOR COMMON 1ST STAGE AUXILIARY HEAT R E W O P V 4 2 R E W O P V...

Page 20: ...ressure switches Defrost Thermostat S6 The defrost thermostat is located on the liquid line be tween the check expansion valve and the distributor When defrost thermostat senses 42 F 5 5 C or cooler t...

Page 21: ...CONNECTIONS TEST PINS P1 Note Component locations vary by board manufacturer SENSOR CONNECTION COIL AND AMBIENT SENSORS P4 REVERSING VALVE O OUT DELAY PINS P5 LOW AMBIENT THERMOSTAT PINS P3 DEFROST T...

Page 22: ...of the defrost mode When a jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out of the defrost mode Units are shipped with jumper installed on DELAY...

Page 23: ...ature probe is de signed with a spring clip to allow mounting to the outside coil tubing The location of the coil sensor is important for proper defrost operation NOTE The demand defrost control accur...

Page 24: ...tem Remove any blockages or restrictions from coils and or fans Check indoor and outdoor fan motor for proper current draws Check system charge using subcooling method Check system operating pressures...

Page 25: ...e outdoor unit s coil should be performed by a trained service technician Contact your dealer and set up a schedule preferably twice a year but at least once a year to inspect and service your outdoor...

Page 26: ...ur dealer show you the location of the drain line and how to check for obstructions This would also apply to an auxiliary drain if installed Thermostat Operation See the thermostat homeowner manual fo...

Page 27: ...Page 27 Wiring and Sequence of Operation FIGURE 13 Typical Unit Wiring...

Page 28: ...Page 28 FIGURE 14 Typical Factory Wiring...

Page 29: ...emand cycle If the coil sensor temperature is still below the selected termination temperature the control will continue the defrost cycle until the cycle is terminated in one of the methods mentioned...

Page 30: ...um Fuse or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Discharge Pressure Vapor P...

Reviews: