background image

Page 9

New or Replacement Line Set

This section provides information on new installation or re-

placement of existing line set. If a new or replacement line 

set is not required, then proceed to Brazing Connections 

on page 11. 
If refrigerant lines are routed through a wall, seal and 

isolate the opening so vibration is not transmitted to the 

building. Pay close attention to line set isolation during 

installation of any HVAC system. When properly isolated 

from building structures (walls, ceilings. floors), the refrig

-

erant lines will not create unnecessary vibration and sub-

sequent sounds. 

REFRIGERANT LINE SET 

Field refrigerant piping consists of liquid and suction lines 

from  the  outdoor  unit  (braze  connections)  to  the  indoor 

unit  coil  (flare  or  braze  connections).  Use  Lennox  L15 

(braze,  non-flare)  series  line  set,  or  use  field-fabricated 

refrigerant lines as listed in table 2.

TABLE 2. Refrigerant Line Set – in. (mm)

Model

Valve Field  

Connections

Recommended Line Set

Liquid  

Line

Vapor  

Line

Liquid  

Line

Vapor  

Line

L15 Line Sets

-018

3/8 in. 

(10 mm)

3/4 in. 

(19 mm)

3/8 in. 

(10 mm)

3/4 in. 

(19 mm)

L15-41

 

15 ft. - 50 ft. 

(4.6 m - 15 m)

-024
-030
-036

3/8 in. 

(10 mm)

7/8 in. 

(22 mm)

3/8 in. 

(10 mm)

7/8 in. 

(22 mm)

L15-65

 

15 ft. - 50 ft. 

(4.6 m - 15 m)

-042
-048

-060

3/8 in. 

(10 mm)

1-1/8 in. 

(28 mm)

3/8 in. 

(10 mm)

1-1/8 in. 

(28 mm) Field Fabricated

NOTE - Some applications may require a field-provided 7/8"

 to 

1-1/8

"

 adapter.

NOTE

 – 

When installing refrigerant lines longer than 50 

feet, contact Lennox Technical Support Product Applica-

tions for assistance or Lennox piping manual. To obtain 

the correct information from Lennox, be sure to communi-

cate the following points

:  

• 

Model (EL16XP1) and size of unit (e.g. -060).  

• 

 Line set diameters for the unit being installed as listed in 

table 4 and total length of installation.  

•   Number of elbows and if there is a rise or drop of the piping.

 IMPORTANT

Mineral oils are not compatible with HFC-410A. If oil 

must be added, it must be a Polyol ester oil.

The compressor is charged with sufficient Polyol ester oil 

for line set lengths up to 50 feet. Recommend adding oil to 

system based on the amount of refrigerant charge in the 

system. No need to add oil in system with 20 pounds of 

refrigerant or less. For systems over 20 pounds - add one 

ounce for every five pounds of refrigerant. 
Recommended topping-off POE oils are Mobil EAL ARC

-

TIC 22 CC or ICI EMKARATE RL32CF. 

MATCHING WITH NEW OR EXISTING INDOOR COIL 

AND LINE SET 

The RFC1-metering line consisted of a small bore copper 

line that ran from condenser to evaporator coil. Refrig-

erant  was  metered  into  the  evaporator  by  utilizing  tem

-

perature/pressure evaporation effects on refrigerant in the 

small RFC line. The length and bore of the RFC line cor-

responded to the size of cooling unit. If the EL16XP1 is 

being used with either a new or existing indoor coil which 

is equipped with a liquid line which served as a meter-

ing device (RFCI), the liquid line must be replaced prior to 

the installation of the EL16XP1 unit. Typically a liquid line 

used to meter flow is 1/4” in diameter and copper. 

LINE SET INSTALLATION AND ISOLATION

 IMPORTANT

The Clean Air Act of 1990 bans the intentional venting 

of refrigerant (CFC’s and HCFC’s) as of July 1, 1992. 

Approved methods of recovery, recycling or reclaiming 

must be followed. Fines and/or incarceration may be 

levied for non-compliance.

 IMPORTANT

If this unit is being matched with an approved line set 

or indoor unit coil that was previously charged with 

mineral oil, or if it is being matched with a coil which 

was manufactured before January of 1999, the coil and 

line set must be flushed prior to installation. Take care to 

empty all existing traps. Polyol ester (POE) oils are used 

in  Lennox  units  charged  with  HFC-410A  refrigerant. 

Residual mineral oil can act as an insulator, preventing 

proper  heat  transfer.  It  can  also  clog  the  expansion 

device and reduce system performance and capacity.

Failure to properly flush the system, per this instruction 

and  the  detailed  Installation  and  Service  Procedures 

manual will void the warranty.

Summary of Contents for EL16XP1 Series

Page 1: ...cation 2 Dimensions 3 Specifications 4 Typical Unit Parts Arrangement 6 Operating Gauge Set and Service Valves 6 Unit Placement 8 New or Replacement Line Set 9 Brazing Connections 11 Flushing Line Set...

Page 2: ...ides may be A clearance of 24 in must be maintained between two units 48 in 1219 mm clearance required on top of unit Model Number Identification Nominal SEER Unit Type P Heat Pump Outdoor Unit Refrig...

Page 3: ...SUPPORT FEET EL16XP1 018 TO 030 BASE SECTION Medium Base EL16XP1 036 TO 060 BASE SECTION Large Base 13 7 8 352 3 5 8 92 20 5 8 524 7 3 4 197 27 1 8 689 4 1 2 114 3 1 4 83 Depth Width Model No A B C in...

Page 4: ...0 98 0 98 0 96 0 99 Outdoor Fan Motor Full load amps 1 0 1 0 1 0 2 6 Locked rotor amps 1 9 1 9 1 9 CONTROLS iComfort E30 Smart Wi Fi Thermostat 15S63 Remote Outdoor Temperature Sensor X2658 OPTIONAL A...

Page 5: ...99 0 99 Outdoor Fan Motor Full load amps 2 6 2 6 2 6 CONTROLS iComfort E30 Smart Wi Fi Thermostat 15S63 Remote Outdoor Temperature Sensor X2658 OPTIONAL ACCESSORIES ORDER SEPARATELY Compressor Hard S...

Page 6: ...stripping of the various caps used the appropriately sized wrench should be used and fitted snugly over the cap before tightening TABLE 1 Torque Requirements Parts Recommended Torque Service valve cap...

Page 7: ...7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately...

Page 8: ...ent of unit in relation to a window see the provided illustration in figure 3 detail A PLACING UNIT ON SLAB When installing unit at grade level the top of the slab should be high enough above grade so...

Page 9: ...be a Polyol ester oil The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet Recommend adding oil to system based on the amount of refrigerant charge in the sys...

Page 10: ...be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Page 11: ...dous to your health Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns...

Page 12: ...SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AND D...

Page 13: ...tions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE...

Page 14: ...ISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN HCFC22 TO BE USED FOR FLUSHING LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE...

Page 15: ...reads and expose surface of the Teflon ring with refrigerantoil E Attach the liquid line assembly to the expansion valve Finger tighten and use an appropriately sized wrench to turn an additional 1 2...

Page 16: ...gauge set Disconnect the HFC 410A cylinder C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set D Adjust dry nitrogen pressure to 150 psig...

Page 17: ...r unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the...

Page 18: ...to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air han dler for low voltage control power 24...

Page 19: ...CY HEAT EMERGENCY HEAT RELAY OUTDOOR THERMOSTAT THERMOSTAT INDOOR UNIT OUTDOOR UNIT COMMON 1ST STAGE AUXILIARY HEAT INDOOR BLOWER COMPRESSOR COMMON 1ST STAGE AUXILIARY HEAT R E W O P V 4 2 R E W O P V...

Page 20: ...ressure switches Defrost Thermostat S6 The defrost thermostat is located on the liquid line be tween the check expansion valve and the distributor When defrost thermostat senses 42 F 5 5 C or cooler t...

Page 21: ...CONNECTIONS TEST PINS P1 Note Component locations vary by board manufacturer SENSOR CONNECTION COIL AND AMBIENT SENSORS P4 REVERSING VALVE O OUT DELAY PINS P5 LOW AMBIENT THERMOSTAT PINS P3 DEFROST T...

Page 22: ...of the defrost mode When a jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out of the defrost mode Units are shipped with jumper installed on DELAY...

Page 23: ...ature probe is de signed with a spring clip to allow mounting to the outside coil tubing The location of the coil sensor is important for proper defrost operation NOTE The demand defrost control accur...

Page 24: ...tem Remove any blockages or restrictions from coils and or fans Check indoor and outdoor fan motor for proper current draws Check system charge using subcooling method Check system operating pressures...

Page 25: ...e outdoor unit s coil should be performed by a trained service technician Contact your dealer and set up a schedule preferably twice a year but at least once a year to inspect and service your outdoor...

Page 26: ...ur dealer show you the location of the drain line and how to check for obstructions This would also apply to an auxiliary drain if installed Thermostat Operation See the thermostat homeowner manual fo...

Page 27: ...Page 27 Wiring and Sequence of Operation FIGURE 13 Typical Unit Wiring...

Page 28: ...Page 28 FIGURE 14 Typical Factory Wiring...

Page 29: ...emand cycle If the coil sensor temperature is still below the selected termination temperature the control will continue the defrost cycle until the cycle is terminated in one of the methods mentioned...

Page 30: ...um Fuse or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Discharge Pressure Vapor P...

Reviews: