88
16. Quick Start Guide
CAUTION
Check rooftop unit electrical power for proper voltage and phasing. Check gas train components.
a.
Turn on unit and dismiss alarm messages as necessary.
b.
Follow SETUP > INSTALL menu to properly configure unit
c.
Be sure unit is in normal operating mode as seen in display (COOLING, HEATING, IDLE, etc).
d.
To verify operation use SERVICE > TEST menu.
Control Mode
Menu Setup Needed
Tips
THERMOSTAT
(Factory set for 2-stage thermostat)
Check LEDs for signals.
BACnet
SETUP > NETWORK INTEGRATION > NETWORK WIZARD > NETWORK
TYPE = BACNET MS/TP
•
Setup information to be verified with
integrator.
•
Follow wiring instructions including network
termination
•
Remember to set MAC address 0-127
•
Expert level BACnet service manual available.
LonTalk
SETUP > NETWORK INTEGRATION > NETWORK WIZARD > = LONTALK
•
Setup information to be verified with
integrator.
•
Follow wiring instructions including network
termination
•
XIF file available. Neuron ID on sticker.
•
Expert level LonTalk service manual available.
Damper
SETUP > TEST & BALANCE > DAMPER
•
Verify damper minimum positions
•
Refer to Economizer section of manual for
more detail
Local Mode
SETUP > NETWORK INTEGRATION > NETWORK WIZARD > RTU
STANDALONE
•
Give unit time to start-up.
•
Humidity control requires sensor or error code
7649
Dehumidifier
Dehumidifier setup will be done during the SETUP >INSTALL wizard. It’s the
last part of that wizard.
•
Three possible connections, LOCAL
SENSOR, NETWORK SENSOR and
REHEAT DI4.
•
Analog sensor wiring is polarity sensitive
Blower
Change motor torque; see
SETUP > TEST & BALANCE > BLOWER
•
Final motor CFM should be set by Test and
Balance technician
•
Blower charts are located in the unit
installation instruction.