58
Table 12. CORE Control System Unit Parameters
Control
Parameter
No
Screen Name
Parameter Short
Description
Control Value
Units
Description
Min.
Default
Max.
140
UNOCC COOL
STPT
Unoccupied
Cooling Set Point
40
85
95
°F
•
Backup unoccupied cooling set
point.
•
Used if the communications link
is lost for 5 minutes between the
CORE Unit Controller and network
control panel. Used only in room
sensor applications.
•
Set point temperature must be
greater than or equal to Parameter
138 plus Parameter 152).
141
AFTERHOUR
OVRRD DLY
After Hours
Override Time
Delay
0
60
480
Minutes
•
After hours override timer.
•
Only used on room sensor
applications without a network
control panel.
142
HEAT STAGE
DEADBAND
Heat Stage
Deadband
1
1
3.75
°F
•
Heating dead-band. Used only with
CORE Unit Controller room sensor
applications.
•
Dead band must be less than or
equal to Parameter 152 minus
Parameter 143.
143
COOL STAGE
DEADBAND
Cool Stage
Deadband
1
1
3.75
°F
•
Cooling dead-band. Used only with
room sensor applications.
•
Dead band must be less than or
equal to Parameter 152 minus
Parameter 142.
144
COOL STAGE1
DIFFER
Cooling Stage 1
Differential
0
0.5
3
°F
•
Cooling stage 1 differential. Used
only with room sensor applications.
•
Differential temperature must be
less than or equal to Parameter 145.
145
COOL STAGE2
DIFFER
Cooling Stage 2
Differential
0
1
3
°F
•
Cooling stage 2 differential. Used
only with room sensor applications.
•
Differential temperature must be
greater than or equal to Parameter
144 and less than or equal to
Parameter 146.
146
COOL STAGE3
DIFFER
Cooling Stage 3
Differential
0
1.5
3
°F
•
Cooling stage 3 differential. Used
only with room sensor applications.
•
Differential temperature must be
greater than or equal to Parameter
145 and less than or equal to
Parameter 147.
147
COOL STAGE4
DIFFER
Cooling Stage 4
Differential
0
2
3
°F
•
Cooling stage 4 differential. Used
only with room sensor applications.
•
Differential temperature must be
greater than or equal to Parameter
146.
148
HEAT STAGE1
DIFFER
Heating Stage 1
Differential
0
0.5
3
°F
•
Heating stage 1 differential. Used
only with room sensor applications.
•
Differential temperature must be
less than or equal to Parameter 149.
149
HEAT STAGE2
DIFFER
Heating Stage 2
Differential
0
1
3
°F
•
Heating stage 2 differential. Used
only with room sensor applications.
•
Differential temperature must be
greater or equal to Parameter 148.
150
HEAT STAGE3
DIFFER
Heating Stage 3
Differential
0
1.5
3
°F
•
Heating stage 3 differential
temperature. Used only with room
sensor applications.
•
Differential temperature must be
greater than or equal to Parameter
149.