Table 1. System Status Icons

Icon

Description

NOTE: 

Touching the icon will display a 

text description.

Indicates the system is running in 

auxiliary heat mode.

Is only available with heat pump 

system. If outdoor temperature is above 

the high balance point, only the heat 

pump will operate - default 50°F (10°C) 

high. If outdoor temperature is below 

the low balance point, only auxiliary 

heating will operate - default 25°F 

(-4.0°C) low. If outdoor temperature is 

in-between the high and low balance 

point, both the heat pump and auxiliary 

heat sources can operate.

Transitioning to next schedule 

temperature setting. This icon will only 

appear if smooth setback recovery is 

enabled under the installer setup. When 

enabled, it will begin recovery up to 

two hours before the programmed time 

so that the programmed temperature 

is reached at the corresponding 

programmed event time. Assume 12°F 

per hour for gas/electric heating and 

6°F per hour for first stage compressor 

based cooling. When smooth set back 

recovery is disabled, the control will 

start recovery at the programmed time 

set in the schedule.

L. 

Holiday Mode

 - Selecting this option allows for 

overriding schedules for holidays and special 

days. When in this mode the thermostat will not 

follow regular schedules. This override can be 

setup for up to four days. Go to menu > user 

settings > edit schedules and select Holiday. To 

exit Holiday mode, touch the cancel button on 

the home screen.

M.  Indicates whether in occupied or unoccupied 

mode when running a regular schedule. This will 

be displayed when running schedule 1 or 2 and 

holiday. Under edit schedules, either occupied 

or unoccupied can be set under the day time 

event (occ1, unocc1, occ2 and unocc2).

Operating Mode Selection

Touch anywhere in the area indicated below to se-

lect how the system will operate.

holiday

heat−to

78

inside 57%

schedule 1

away

68°

outside

32°

waiting

0

2:31 am   thur

occupied

Figure 3. Operating Mode Selection

S

elect

 M

odeS

1. 

HEAT/COOL

 allows the thermostat to switch 

between heating and cooling automatically.

Summary of Contents for ComfortSense 7500 Series

Page 1: ...507505 02 6 2018 Supersedes 5 2017 ComfortSense 7500 Commercial Thermostat User Guide...

Page 2: ...free memory storage feature menu driven touch screen display dehumidification measurement and control Humiditrol EDA capability Home Screen Temperature Indicator 2 31 am thurs heat to cool to 80 insid...

Page 3: ...emperature dial position indicator will take you to the temperature setting detail screen The temperature dial will change from white to red when heating is active F This allows you to set the cool to...

Page 4: ...ifying next to the icon Red flames indicates the system is heating Table 1 System Status Icons Icon Description NOTE Touching the icon will display a text description Blue flames indicates the system...

Page 5: ...nd 6 F per hour for first stage compressor based cooling When smooth set back recovery is disabled the control will start recovery at the programmed time set in the schedule L Holiday Mode Selecting t...

Page 6: ...ng scheduling for the current period the ther mostat will indicate the current fan mode in the in formation display FAN ON or FAN CIRC In the CIRCULATE mode the fan will follow the setting configured...

Page 7: ...or set a future reminder Any active history for notifications critical errors or reminders will be listed under settings notification If critical errors occur they will also be displayed under notifi...

Page 8: ...Selection on page 5 to run a specific schedule From the HOME screen touch the MENU and touch edit schedules option The edit schedules screen will allow section of up too three separate schedules On th...

Page 9: ...end all 7 days All days wake rename time cool to heat to fan occupancy time select time or delete period If period deleted A maximum of four time periods can be used If any time periods are deleted an...

Page 10: ...age s of heat pump heating and goes directly to the heat stage used for maximum heating to more quickly warm a very cold house set point range Heating limit with a default of 0 F Range is 45 F to 90 F...

Page 11: ...ngs for screen lock date time and language about Displays information concerning thermostat model number serial number hardware and software revisions screen lock Setting options are unlocked partiall...

Page 12: ...displayed on the home screen Outdoor temperature display or discharged air display what is displayed here depends on sensor used and configured by installer Options are off or sensor screen saver Opti...

Reviews: