CLIMATIC™ 60 – AIRCOOLED CHILLERS
MUL
41E
-0610/
06-2011
Page 43
LENNOX units implement Modbus slave protocol with the following settings:
Serial Line
RS485 (EIA/ TIA - 485 Standard)
Transmission Mode
RTU (Remote Terminal Unit)
Baudrate
1200
19200 Bauds
Data bits
8 bits
Parity
None
Stop bits
1 bit
24.3 - Settings
The different settings to configure the BMS are available in the menu:
•
(
3826
): Unit identification number on the BMS network,
•
(
3827
): Protocol communication with the BMS,
•
(
3828
): Baudrate with the BMS.