CLIMATIC™ 60 – AIRCOOLED CHILLERS
MUL
41E
-0610/
06-2011
Page 17
10 - PUMP EVAPORATOR FLOW CONTROL
10.1 - Function
The ClimaticTM60 offers the possibility to have a flow control in option.
10.2 - Description
There is up to 4 modes to manage the evaporator water flow.
10.2.1 - Fix speed
The CLIMATIC™ 60 maintains a fix flow according to the maximum speed desired. The flow is set to the minimum
flow desired only when none compressor is running.
10.2.2 - Fix delta T°
The CLIMATIC™ 60 maintains a fix delta of temperature according to the inlet and outlet temperature probe on the
evaporator. The delta of temperature desired is customized in the menu (
3374
).