CLIMATIC™ 60 – AIRCOOLED CHILLERS
MUL
41E
-0610/
06-2011
Page 65
Level 1 Item
Level 2 Item
Level 3 Item
Level 4 Item
R/W/Z Unit
Min
Std
Max
Description
Expert
3500
Condenser
3510
Circuit 1
3511
Config
R
*
*
*
*
Configuration condenser circuit
1
Expert
Condenser
Circuit 1
3512
Status
R
*
*
*
*
Status condenser circuit 1
Expert
Condenser
Circuit 1
3513
Sw State
R
*
0
*
1
Input condenser circuit 1
Expert
Condenser
Circuit 1
3514
Input
R
°C
-50,0
*
67,0
Condensing T° circuit 1
Expert
Condenser
Circuit 1
3515
Setpoint
R
°C
25,0
*
45,0
Condensing T° set point
Expert
Condenser
Circuit 1
3516
Capacity
R
%
0,0
*
100,0
Condensing fan capacity circuit
1
Expert
Condenser
Circuit 1
3517
Speed Low
R
*
0
*
1
Condensing fan low speed
circuit 1
Expert
Condenser
Circuit 1
3518
Speed High
R
*
0
*
1
Condensing fan high speed
circuit 1
Expert
Condenser
3520
Circuit 2
3521
Config
R
*
*
*
*
Configuration condenser circuit
2
Expert
Condenser
Circuit 2
3522
Status
R
*
*
*
*
Status condenser circuit 2
Expert
Condenser
Circuit 2
3523
Sw State
R
*
0
*
1
Input condenser circuit 2
Expert
Condenser
Circuit 2
3524
Input
R
°C
-50,0
*
67,0
Condensing T° circuit 2
Expert
Condenser
Circuit 2
3525
Setpoint
R
°C
25,0
*
45,0
Condensing T° set point
Expert
Condenser
Circuit 2
3526
Capacity
R
%
0,0
*
100,0
Condensing fan capacity circuit
2
Expert
Condenser
Circuit 2
3527
Speed Low
R
*
0
*
1
Condensing fan low speed
circuit 2
Expert
Condenser
Circuit 2
3528
Speed High
R
*
0
*
1
Condensing fan high speed
circuit 2
Expert
Condenser
3530
Circuit 1/2
3531
Config
R
*
*
*
*
Configuration condenser circuit
1&2
Expert
Condenser
Circuit 1/2
3532
Status
R
*
*
*
*
Status condenser circuit 1&2
Expert
Condenser
Circuit 1/2
3533
Sw State
R
*
0
*
1
Input condenser circuit 1&2
Expert
Condenser
Circuit 1/2
3534
Input
R
°C
0,0
*
100,0
Condensing capacity circuit
1&2
Expert
Condenser
Circuit 1/2
3535
Setpoint
R
°C
*
*
*
*
Expert
Condenser
Circuit 1/2
3536
Capacity
R
%
*
*
*
*
Expert
Condenser
3540
Fan
3541
Outside
R
°C
-50,0
*
105,0
Outside air T°
Expert
Condenser
Fan
3542
Capacity Max
R
%
0,0
*
100,0
Condenser fan capacity
maximum
Expert
Condenser
Fan
3543
Unloading
R
°C
50,0
*
65,0
Condenser unloading T°
Expert
Condenser
Fan
3544
Mode
R/W
*
0=Not Set,
1=Quiet,
2=Quiet++.
Condenser fan accoustic mode
Expert
Condenser
Fan
3545
Noise
R/W
dBa
82,0
*
94,0
Condenser fan accoustic noise
Expert
Condenser
Fan
3546
Setpoint
R/W
°C
35,0
40,0
45,0
Condenser fan set point