background image

Page 5

Refrigerant Line Connections 

LINE SIZES

The refrigerant line sets should be sized according to the 

recommendations given in the air conditioner or heat pump 

unit installation instructions. Use table 1 to determine cor-

rect braze connection sizes. A field-provided adapter may 

be required to match line set connections.

TABLE 1

 Refrigerant Line Connections – 

 

Model CHX35

Model Number

Suction

Liquid

18-2F
24-2F
30-2F
36-2F

3/4 Inch

3/8 Inch

42-2F
48-2F
51-2F
60-2F

7/8 Inch

REPLACEMENT PARTS

If replacement parts are necessary, order kit 69J46. The 

kit includes:

• 

10 – Brass nuts for liquid line assemblies

• 

20 – Teflon rings

• 

10 – Liquid line orifice housings

•  10 Liquid line assemblies

TEFLON RINGS (20)

BRASS NUTS (10)

LIQUID LINE ASSEMBLIES

(INCLUDES STRAINER) (10)

LIQUID LINE ORIFICE HOUSINGS (10)

LIQUID LINE

ASSEMBLY

COPPER

TUBE

PISTON

RETAINER

STRAINER

FIGURE 6. 69J46 Kit Components

BRAZING GUIDELINES

Use a silver alloy brazing rod (5 or 6 percent silver alloy 

for copper-to-copper connections or 45 percent silver al-

loy for copper-to-brass or copper-to-steel connections). 

Before making brazed connections, place a field-provided 

heat shield, such as a wet rag, against the unit cabinet 

and around the piping stubs, expansion valve and sensing 

bulb (or remove the sensing bulb temporarily). The heat 

shield must be in place to prevent heat damage during 

brazing. See figure 7.

WATER-

SATURATED

RAGS

PLACE A WET RAG AGAINST

COIL CABINET AND AROUND

THE SUCTION LINE

CONNECTION.

BRAZE CONNECTION. ALLOW

PIPE TO COOL BEFORE

REMOVING WET RAG.

1

2

USE A WET RAG TO PROTECT

THE TXV SENSING BULB

(OR REMOVE THE BULB)

WHEN BRAZING THE 

SUCTION LINE.

3

FIGURE 7. Braze Refrigerant Lines

SUCTION LINE CONNECTION

Use the following procedure to connect the suction line to 

the indoor coil: 

1 -  Remove rubber plug from the stubbed connection. 
2 -   Position the properly sized refrigerant piping and 

make the brazed connection following the brazing 

guidelines. 

3 -   Do not remove the water-saturated rags from the 

cabinet and piping until the piping has cooled 

completely. 

Summary of Contents for CHX35 Series

Page 1: ...ts for shipping damage if found im mediately contact the last carrier INSTALLATION INSTRUCTIONS INDOOR COILS 507835 01 067198001 4 2018 CHX35 Series Coils General Information CHX35 horizontal evaporat...

Page 2: ...3 8 3 8 3 8 3 8 Condensate drain fpt in 3 4 3 4 3 4 3 4 3 4 Evaporator Coil Net face area sq ft 1 75 3 5 3 5 4 33 4 67 Tube diameter in 3 8 3 8 3 8 3 8 3 8 Number of rows 2 3 2 3 3 Fins per inch 18 14...

Page 3: ...et to the drain Position the coil in the left to right configuration on the service access side of the furnace Insert a field provided spacer between the furnace and the coil Use field provided screws...

Page 4: ...NIT REAR TEST HOLE AIR FLOW FIELD FABRICATED INSULATED BLOCK OFF PLATE FIGURE 2 D Width Coil with C Width Furnace Top View SUPPLY AIR UNIT FRONT PLUMBING CONNECTIONS SUPPLY AIR UNIT REAR AIR FLOW TEST...

Page 5: ...brazing rod 5 or 6 percent silver alloy for copper to copper connections or 45 percent silver al loy for copper to brass or copper to steel connections Before making brazed connections place a field...

Page 6: ...uld be properly sized and installed according to the ASHRAE Standard Manual D The supply and return air duct systems should be designed for the cfm and static requirements of the job Consult the blowe...

Page 7: ...lations Blower Speed Selection Proper air volume must be provided over the evaporator coil Select a blower motor speed tap that will provide 400 50 CFM per 12 000 Btuh of cooling capacity wet coil A s...

Page 8: ...the distributor lines are not rubbing together or kinked All tubes must have enough clearance from other metal parts Use wire ties to secure tubes to prevent movement that could cause the refrigerant...

Reviews: