background image

Page 7

ABOVE

FINISHED

SPACE?

OVERFLOW DRAIN LINE

ALWAYS RUN AN OVERFLOW DRAIN LINE. IF NOT POSSIBLE TO

ROUTE  OVERFLOW  DRAIN  LINE,  INSTALL  LOW  VOLTAGE

OVERFLOW  SWITCH  KIT. WIRE  KIT  TO  SHUT  DOWN

COMPRESSOR PER INSTRUCTIONS.

NO

YES

OEM CATALOG#

X3169

CLEAN OUT

VENT

PRESS IN

(DO NOT GLUE)

VENT MUST EXTEND

ABOVE HEIGHT OF

COIL DRAIN PAN BY

TWO INCHES

1” X 3/4” X 3/4”

REDUCING

TEE WITH

PLUG

OEM CATALOG

NUMBERS* P-TRAP

49P66, J-TRAP #

91P90 OR ANY PVC

SCH 40 P- OR

J-TRAP 3/4”

OVERFLOW

DRAIN

OPTIONAL

SAFETY

PAN

COIL DRAIN PAN

WHEN A COIL IS LOCATED  ABOVE  A FINISHED SPACE, A 3/4” SECONDARY DRAIN LINE

MUST BE:
  ●

CONNECTED TO SECONDARY DRAIN PAN
OR

  ●

CONNECTED TO THE OVERFLOW DRAIN OUTLET OF THE AIR HANDLER DRAIN PAN.

TRAPS  MUST  BE  DEEP  ENOUGH  TO  OFFSET  MAXIMUM  STATIC  DIFFERENCES  —

GENERALLY, TWO INCHES.

DRAIN  LINE  SHOULD

SLOPE A MINIMUM OF

ONE INCH PER 10 FT.

NOTE 

—  WHEN  A  AIR  HANDLER  IS  LOCATED  ABOVE  A  FINISHED  SPACE  THE  SECONDARY

DRAIN PAN MUST HAVE A LARGER FOOTPRINT THAN THE AIR HANDLER.

MAIN

DRAIN

TO APPROVED

DRAIN

FOR  NEGATIVE  PRESSURE  COILS  (BLOWER

AFTER COIL) TRAPS ARE REQUIRED ON ALL

DRAIN LINES CONNECTED TO COIL.

COMPACT OVERFLOW SWITCH WITH 3/4” FEMALE SLIP INLET

AND  MALE  ADAPTER,  TWO  PART  DESIGN  FOR  USE  WHERE

OBSTRUCTIONS PREVENT DIRECT THREADING

SECONDARY

DRAIN PAN

2”

(51MM)

TRAP DEPTH

*OEM CATALOG # P-TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J-TRAP 91P90.

FIGURE 8

. Typical Main and Overflow Drain Installations

Blower Speed Selection 

Proper air volume must be provided over the evaporator 

coil. Select a blower motor speed tap that will provide 400 

± 50 CFM per 12,000 Btuh of cooling capacity (wet coil). 

A static pressure reading must be taken to see if the pres-

sure drop falls within the proper range. 
To ensure accuracy, static pressure must be read from the 

air entry side of the coil to the air exit side of the coil. See 

figure 9 for an example to obtain an accurate reading. 

LEFT-HAND AIR DISCHARGE (TOP VIEW)

SUPPLY AIR UNIT FRONT

SUPPLY AIR UNIT REAR

AIR

FLOW

TEST HOLE 1

TEST HOLE

2

SUPPLY

AIR DUCT

RETURN AIR

DUCT

FIGURE 9. Static Pressure Test

 CAUTION

Take care when drilling test holes into the furnace flange 

and the duct. Drill holes away from refrigerant piping. 

Test holes should be drilled where specified in order to 

avoid unit damage. 

1 -   Drill a 5/16" test hole in the coil case 1" from the 

furnace flange (test hole 1, figure 9).

2 -   Drill a 5/16" test hole into the supply air duct (test 

hole 2, figure 9).

3 -   Connect the zero end of the draft gauge scale to the 

furnace end of the coil. Insert the hoses so that 1/4" 

extends inside the duct or end seal. Seal around 

holes with Permagum.

4 -   Turn on electrical power to the furnace and set the 

thermostat to initiate a cooling demand. 

5 -   Table 2 lists the range of air volumes and equivalent 

draft gauge readings for this unit. Observe the draft 

gauge reading. If the reading is below the required 

air volume, increase the blower speed; if the reading 

is above the required air volume, decrease the 

blower speed. Refer to the furnace wiring diagram 

for blower speed settings.

Summary of Contents for CHX35 Series

Page 1: ...ts for shipping damage if found im mediately contact the last carrier INSTALLATION INSTRUCTIONS INDOOR COILS 507835 01 067198001 4 2018 CHX35 Series Coils General Information CHX35 horizontal evaporat...

Page 2: ...3 8 3 8 3 8 3 8 Condensate drain fpt in 3 4 3 4 3 4 3 4 3 4 Evaporator Coil Net face area sq ft 1 75 3 5 3 5 4 33 4 67 Tube diameter in 3 8 3 8 3 8 3 8 3 8 Number of rows 2 3 2 3 3 Fins per inch 18 14...

Page 3: ...et to the drain Position the coil in the left to right configuration on the service access side of the furnace Insert a field provided spacer between the furnace and the coil Use field provided screws...

Page 4: ...NIT REAR TEST HOLE AIR FLOW FIELD FABRICATED INSULATED BLOCK OFF PLATE FIGURE 2 D Width Coil with C Width Furnace Top View SUPPLY AIR UNIT FRONT PLUMBING CONNECTIONS SUPPLY AIR UNIT REAR AIR FLOW TEST...

Page 5: ...brazing rod 5 or 6 percent silver alloy for copper to copper connections or 45 percent silver al loy for copper to brass or copper to steel connections Before making brazed connections place a field...

Page 6: ...uld be properly sized and installed according to the ASHRAE Standard Manual D The supply and return air duct systems should be designed for the cfm and static requirements of the job Consult the blowe...

Page 7: ...lations Blower Speed Selection Proper air volume must be provided over the evaporator coil Select a blower motor speed tap that will provide 400 50 CFM per 12 000 Btuh of cooling capacity wet coil A s...

Page 8: ...the distributor lines are not rubbing together or kinked All tubes must have enough clearance from other metal parts Use wire ties to secure tubes to prevent movement that could cause the refrigerant...

Reviews: