Specifications – cont’d

48B – 60D 

General Data

Model No.

CHX35

-48B-2F

CHX35

-48C-2F

CHX35

-51C-2F

CHX35

-60D-2F

Nominal size - tons

3.5 / 4

3.5 / 4

4

5

Line

Connections

Suction/Vapor o.d. - in. sweat

7/8

7/8

7/8

7/8

Liquid o.d. - in. sweat

3/8

3/8

3/8

3/8

Condensate drain (fpt) - in.

3/4

3/4

3/4

3/4

Evaporator

Coil

Net face area - sq. ft.

5.78

5.83

7.22

7.94

Tube diameter - in.

3/8

3/8

3/8

3/8

Number of rows

3

2

3

3

Fins per inch

12

12

13

12

Horizontal

Matching

Furnace

Cabinet Designation

B

C

C

D

Coil and Furnace Height

17-1/2

21

21

24-1/2

Shipping Data

lbs. - 1 package

60

59

69

78

FOAM

TAPE

FIGURE 1. Insulate Suction Line Inside Cabinet 

1 -   

Left-Hand  and  Right-Hand  Discharge  –  The 

coil must have a 1/2" slope from the rear of the 

cabinet to the drain. 

Position the coil adjacent 

to the furnace cabinet and align the six screw 

clearance holes in the coil casing with the furnace 

engagement holes. Use six field-provided #8 X 1” 

screws to secure the coil casing to the furnace (see 

figures 3 and 4). 

2 -   

Right-Hand Air Discharge with Field-Provided 

Spacer – The coil must have a 1/2

"

 slope from 

the rear of the cabinet to the drain.

 Position the 

coil in the left-to-right configuration on the service 

access side of the furnace. Insert a field-provided 

spacer between the furnace and the coil. Use field-

provided screws to secure the coil casing, spacer 

and the furnace together. The spacer should be 

long enough to allow room for proper installation 

(approximately 6 inches minimum). See figure 5.

Releasing Air Charge 

 CAUTION

The coil is shipped from the factory pressurized with dry 

air. Pierce a hole in the rubber plug that seals the vapor 

line to relieve the pressure before removing the plugs.

NOTE -

 

If there is no pressure released when the vapor 

line rubber plug is pierced, check the coil for leaks before 

continuing with the installation.

 

The CHX35 coils are shipped with a 9 ± 2 psi dry air hold-

ing charge. Puncture the suction line rubber plug to re-

lease the charge. Remove the rubber plug. Ensure that 

the coil is void of pressure.

Installation 

 WARNING

Risk of explosion or fire.

Can cause injury or death.
Recover all refrigerant to relieve pressure before 

opening the system.

Install the furnace or air handler according to the installa-

tion instructions provided with the unit. 

NOTE

 – 

In areas of high humidity, use foam tape to in-

sulate the suction line section in the cabinet as shown in 

figure 1.

Summary of Contents for CHX35 Series

Page 1: ...ts for shipping damage if found im mediately contact the last carrier INSTALLATION INSTRUCTIONS INDOOR COILS 507835 01 067198001 4 2018 CHX35 Series Coils General Information CHX35 horizontal evaporat...

Page 2: ...3 8 3 8 3 8 3 8 Condensate drain fpt in 3 4 3 4 3 4 3 4 3 4 Evaporator Coil Net face area sq ft 1 75 3 5 3 5 4 33 4 67 Tube diameter in 3 8 3 8 3 8 3 8 3 8 Number of rows 2 3 2 3 3 Fins per inch 18 14...

Page 3: ...et to the drain Position the coil in the left to right configuration on the service access side of the furnace Insert a field provided spacer between the furnace and the coil Use field provided screws...

Page 4: ...NIT REAR TEST HOLE AIR FLOW FIELD FABRICATED INSULATED BLOCK OFF PLATE FIGURE 2 D Width Coil with C Width Furnace Top View SUPPLY AIR UNIT FRONT PLUMBING CONNECTIONS SUPPLY AIR UNIT REAR AIR FLOW TEST...

Page 5: ...brazing rod 5 or 6 percent silver alloy for copper to copper connections or 45 percent silver al loy for copper to brass or copper to steel connections Before making brazed connections place a field...

Page 6: ...uld be properly sized and installed according to the ASHRAE Standard Manual D The supply and return air duct systems should be designed for the cfm and static requirements of the job Consult the blowe...

Page 7: ...lations Blower Speed Selection Proper air volume must be provided over the evaporator coil Select a blower motor speed tap that will provide 400 50 CFM per 12 000 Btuh of cooling capacity wet coil A s...

Page 8: ...the distributor lines are not rubbing together or kinked All tubes must have enough clearance from other metal parts Use wire ties to secure tubes to prevent movement that could cause the refrigerant...

Reviews: