ROTATE BRACKET TO THIS
POSITION AND REINSTALL

REMOVE 2 SCREWS
SECURING BLOW OFF
PREVENTION BRACKET

HORIZONTAL LEFT

(FACTORY DEFAULT)

HORIZONTAL RIGHT

Figure 8. Blow-Off Prevention Plate

Condensate Drain

IMPORTANT

On units of this type, where the blower “draws” rather than “blows” air through the coil, traps must be installed in the con­
densate drain lines (primary and auxiliary, if used). Traps prevent the blower from drawing air through the drain lines into
the air supply.

ABOVE

FINISHED

SPACE?

OVERFLOW DRAIN LINE

ALWAYS RUN AN OVERFLOW DRAIN LINE. IF NOT POSSIBLE TO
ROUTE OVERFLOW DRAIN LINE, INSTALL LOW VOLTAGE
OVERFLOW SWITCH KIT. WIRE KIT TO SHUT DOWN
COMPRESSOR PER INSTRUCTIONS.

NO

YES

LENNOX #

X3169

CLEAN OUT

VENT

PRESS IN

(DO NOT GLUE)

VENT MUST EXTEND

ABOVE HEIGHT OF

COIL DRAIN PAN BY

TWO INCHES (51MM)

1” X 3/4” X 3/4”

REDUCING

TEE WITH

PLUG

LENNOX

1

 P-TRAP

49P66, J-TRAP #

91P90 OR ANY

PVC SCH 40 P- OR

J-TRAP 3/4”

OVERFLOW

DRAIN

AIR HANDLER DRAIN PAN

WHEN A COIL IS LOCATED ABOVE A FINISHED
SPACE, A 3/4” (19.1MM) SECONDARY DRAIN LINE
MUST BE:

S

CONNECTED TO SECONDARY DRAIN PAN 

OR

S

CONNECTED TO THE OVERFLOW DRAIN
OUTLET OF THE AIR HANDLER DRAIN PAN.

TRAPS MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES —
GENERALLY, TWO INCHES (51MM).

DRAIN LINE SHOULD
SLOPE A MINIMUM OF
ONE INCH PER 10
FEET (25MM PER 3
METERS)

NOTE 

— WHEN A AIR HANDLER IS LOCATED

ABOVE A FINISHED SPACE THE SECONDARY
DRAIN PAN MUST HAVE A LARGER FOOTPRINT
THAN THE AIR HANDLER.

MAIN

DRAIN

TO APPROVED

DRAIN

FOR NEGATIVE PRESSURE COILS (BLOWER
AFTER COIL) TRAPS ARE REQUIRED ON ALL
DRAIN LINES CONNECTED TO COIL.

COMPACT OVERFLOW SWITCH WITH 3/4” FEMALE SLIP INLET
AND MALE ADAPTER, TWO PART DESIGN FOR USE WHERE
OBSTRUCTIONS PREVENT DIRECT THREADING

SECONDARY

DRAIN PAN

2”

(51MM)

TRAP DEPTH

1

 LENNOX P-TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J-TRAP 91P90.

2

 PIPE NIPPLE PROVIDED IN BAG ASSEMBLY - SCH 80, 3/4” I. D. X 5” - 34K7401 (1): CUT THE PIPE

IN HALF AND USE IT TO ROUTE THE MAIN DRAIN.

Figure 9. Typical Main and Overflow Drain

Summary of Contents for CBX25UH Series

Page 1: ...12 Table of Contents Shipping and Packing List 1 CBX25UH Series Units 1 Requirements 3 Installation Clearances 3 Installation 4 Condensate Drain 6 Duct System and Filters 7 Connecting Refrigerant Line...

Page 2: ...4 451 17 432 16 1 2 419 20 3 4 527 16 406 5 1 2 140 40 1 2 1029 18 1 2 470 22 559 6 152 14 357 5 1 2 140 13 1 2 343 17 3 4 451 17 432 16 1 2 419 20 3 4 527 16 406 3 5 8 92 inches mm inches mm inches m...

Page 3: ...tely assembled The unit is provided with flanges for the connection of the duct system Do not remove the cabinet knockouts until it has been determined which knockouts will need to be removed for the...

Page 4: ...that is at least 14 from the floor This will allow proper air return HORIZONTAL DRAIN PAN IMPORTANT REMOVE PAN FOR BEST EFFICIENCY AND AIR FLOW UPFLOW DRAIN PAN UPFLOW DRAIN CON NECTIONS BOTH SIDES U...

Page 5: ...Drain Pan Mounting Bracket 018 through 036 REMOVE BRACKETS SECURING BOTH DRAIN PANS TO UNIT Figure 5 Remove Horizontal and Main Drain Pan Mounting Brackets 042 through 060 3 Remove coil assembly bott...

Page 6: ...OR J TRAP 3 4 OVERFLOW DRAIN AIR HANDLER DRAIN PAN WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE A 3 4 19 1MM SECONDARY DRAIN LINE MUST BE S CONNECTED TO SECONDARY DRAIN PAN OR S CONNECTED TO THE OVE...

Page 7: ...trap in the primary drain lines as close to the unit as practical see figure 9 Make sure the top of the trap is below the connection to the drain pan to allow complete drainage of the pan NOTE Horizon...

Page 8: ...he suction and liquid lines from the fittings on the indoor coil to the fittings on the outdoor unit Run the lines in as direct a path as possible avoiding unnecessary turns and bends 2 Make sure that...

Page 9: ...oltage S The power supply must be sized and protected according to the specifications supplied on the product S This air handler is factory configured for 240 volt single phase 60 cycles For 208 volt...

Page 10: ...rating of the air handler If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler the cooling blower speed may need to be changed Refer to blower performance chart...

Page 11: ...d Med Blue High Black 510 670 905 495 650 865 475 630 820 420 595 770 325 505 705 24 Low Red Med Blue High Black 630 885 1130 625 875 1100 615 850 1070 610 820 1010 580 780 950 30 Low Red Med Blue Hig...

Page 12: ...not call for heat Allow up to 5 minutes for all sequencers to cycle off Operation TIME DELAY RELAY Blower time delay operation 1 When cooling demand is initiated there is a 1 second motor on delay 2 A...

Page 13: ...corrected Contact a qualified service technician Cabinet Insulation IMPORTANT DAMAGED INSULATION MUST BE REPAIRED OR REPLACED before the unit is put back into operation In sulation loses its insulati...

Page 14: ...Duct Temperature ___________ THERMOSTAT Adjusted and Programmed Return External Static ______ ______ Total External Static ______ ______ 6 Supply Duct Temperature ___________ Temperature Drop _______...

Page 15: ...Total External Static ______ ______ 6 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature ______...

Page 16: ......

Reviews: