background image

Page 8

IMPORTANT

If a high­efficiency filter is being installed as part of this
system to ensure better indoor air quality, the filter must
be properly sized. High­efficiency filters have a higher
static pressure drop than standard­efficiency glass/foam
filters. If the pressure drop is too great, system capacity
and performance may be reduced. The pressure drop
may also cause the limit to trip more frequently during the
winter and the indoor coil to freeze in the summer, result­
ing in an increase in the number of service calls.

Before using any filter with this system, check the spe­
cifications provided by the filter manufacturer against the
data given in the appropriate Lennox Product Specifica­
tions bulletin. Additional information is provided in Ser­
vice and Application Note ACC­00­2 (August 2000).

Supply plenum should be the same size as the flanged
opening provided around the blower outlet and should
extend at least 3 ft. from the air handler before turning or
branching off plenum into duct runs. The plenum forms an
extension of the blower housing and minimizes air
expansion losses from the blower.

INSTALLING DUCT SYSTEM

Connect supply air duct to the flange on top of the air
handler. If an isolation connector is used, it must be
nonflammable.

A return air duct system is recommended. If the unit is
installed in a confined space or closet, a return connection
must be run, full size, to a location outside the closet.

Connecting Refrigerant Lines

Refrigerant lines must be connected by a qualified
technician in accordance with established procedures.

IMPORTANT

Refrigerant lines must be clean, dehydrated, refrig­
erant-grade copper lines. Air handler coils should be
installed only with specified line sizes for approved sys­
tem combinations.

Handle the refrigerant lines gently during the installation
process. Sharp bends or possible kinking in the lines will
cause a restriction.

Do not remove the caps from the lines or system connec­
tion points until connections are ready to be completed.

1. Route the suction and liquid lines from the fittings on

the indoor coil to the fittings on the outdoor unit. Run
the lines in as direct a path as possible avoiding
unnecessary turns and bends.

2. Make sure that the suction line is insulated over the

entire exposed length and that neither suction nor
liquid lines are in direct contact with floors, walls, duct
system, floor joists, or other piping.

3. Connect the suction and liquid lines to the evaporator

coil.

4. To avoid damaging the rubber grommets in the cabinet

while brazing, slide the rubber grommets over the
refrigerant lines until they are away from the heat
source.

5. Braze using an alloy of silver or copper and

phosphorus with a melting point above 1,100°F
(593°C).

NOTE — Do not use soft solder.

6. Reinstall the rubber grommets after brazing is

finished.

7. Make sure outdoor unit has been put in place

according to the Installation Instructions and is
connected to the refrigerant lines.

Sealing the Unit

Seal the unit so that warm air is not allowed into the
cabinet. Warm air introduces moisture, which results in
water blow-off problems. This is especially important when
the unit is installed in an unconditioned area.

If installed in an unconditioned space, sealant should be
applied around the electrical wires, refrigerant tubing, and
condensate lines where they enter the cabinet.

WARNING

There must be an airtight seal between the bottom of the
air handler and the return air plenum. Use fiberglass
sealing strips, caulking, or equivalent sealing method
between the plenum and the air handler cabinet to
ensure a tight seal. Return air must not be drawn from a
room where this air handler or any gas-fueled appliance
(i.e., water heater), or carbon monoxide-producing
device (i.e., wood fireplace) is installed.

IMPORTANT

When sealing the cabinet, be sure to seal closed any
space around the holes where the drain lines exit the
cabinet using duct tape and/or Permagum. Warm air
must not be allowed to enter through any gaps or holes
in the cabinet.

Make sure the liquid line and suction line entry points are
sealed with either ARMAFLEX material or with
Permagum. Permagum may also be used to seal around
the main and auxiliary drains and around open areas of
electrical inlets.

Summary of Contents for CBX25UH Series

Page 1: ...12 Table of Contents Shipping and Packing List 1 CBX25UH Series Units 1 Requirements 3 Installation Clearances 3 Installation 4 Condensate Drain 6 Duct System and Filters 7 Connecting Refrigerant Line...

Page 2: ...4 451 17 432 16 1 2 419 20 3 4 527 16 406 5 1 2 140 40 1 2 1029 18 1 2 470 22 559 6 152 14 357 5 1 2 140 13 1 2 343 17 3 4 451 17 432 16 1 2 419 20 3 4 527 16 406 3 5 8 92 inches mm inches mm inches m...

Page 3: ...tely assembled The unit is provided with flanges for the connection of the duct system Do not remove the cabinet knockouts until it has been determined which knockouts will need to be removed for the...

Page 4: ...that is at least 14 from the floor This will allow proper air return HORIZONTAL DRAIN PAN IMPORTANT REMOVE PAN FOR BEST EFFICIENCY AND AIR FLOW UPFLOW DRAIN PAN UPFLOW DRAIN CON NECTIONS BOTH SIDES U...

Page 5: ...Drain Pan Mounting Bracket 018 through 036 REMOVE BRACKETS SECURING BOTH DRAIN PANS TO UNIT Figure 5 Remove Horizontal and Main Drain Pan Mounting Brackets 042 through 060 3 Remove coil assembly bott...

Page 6: ...OR J TRAP 3 4 OVERFLOW DRAIN AIR HANDLER DRAIN PAN WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE A 3 4 19 1MM SECONDARY DRAIN LINE MUST BE S CONNECTED TO SECONDARY DRAIN PAN OR S CONNECTED TO THE OVE...

Page 7: ...trap in the primary drain lines as close to the unit as practical see figure 9 Make sure the top of the trap is below the connection to the drain pan to allow complete drainage of the pan NOTE Horizon...

Page 8: ...he suction and liquid lines from the fittings on the indoor coil to the fittings on the outdoor unit Run the lines in as direct a path as possible avoiding unnecessary turns and bends 2 Make sure that...

Page 9: ...oltage S The power supply must be sized and protected according to the specifications supplied on the product S This air handler is factory configured for 240 volt single phase 60 cycles For 208 volt...

Page 10: ...rating of the air handler If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler the cooling blower speed may need to be changed Refer to blower performance chart...

Page 11: ...d Med Blue High Black 510 670 905 495 650 865 475 630 820 420 595 770 325 505 705 24 Low Red Med Blue High Black 630 885 1130 625 875 1100 615 850 1070 610 820 1010 580 780 950 30 Low Red Med Blue Hig...

Page 12: ...not call for heat Allow up to 5 minutes for all sequencers to cycle off Operation TIME DELAY RELAY Blower time delay operation 1 When cooling demand is initiated there is a 1 second motor on delay 2 A...

Page 13: ...corrected Contact a qualified service technician Cabinet Insulation IMPORTANT DAMAGED INSULATION MUST BE REPAIRED OR REPLACED before the unit is put back into operation In sulation loses its insulati...

Page 14: ...Duct Temperature ___________ THERMOSTAT Adjusted and Programmed Return External Static ______ ______ Total External Static ______ ______ 6 Supply Duct Temperature ___________ Temperature Drop _______...

Page 15: ...Total External Static ______ ______ 6 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature ______...

Page 16: ......

Reviews: