CBX25UH SERIES

2

BLUE (MED)

RED (L0)

BLACK (HI)

YELLOW (COM)

5

BLOWER RELAY

BLOWER RELAY

PLASTIC CAPS

4-PIN

BLOWER CONNECTOR

HARNESS

CHANGING BLOWER SPEED

Figure 13. Changing Blower Speed

NOTE — Refer to wiring diagram  located on the unit access panel (or figure 13 above) and blower performance (table 2).

S

All air data measured external to unit with 1 inch non-pleated air filter in place.

S

All factory settings are medium speed except the -48 which is set to low speed from the factory.

S

All data given while air handler is operating with a dry DX coil.

Table 2. CBX25UH Blower Performance (3-Speed PSC) - 240V (CFM @ ESP. - in. W. C.)

Air Handler

Model

Blower Speed

.10” WC

.20” WC

.30” WC

.40” WC

.50” WC

18

Low (Red)
Med (Blue)
High (Black)

510
670
905

495
650
865

475
630
820

420
595
770

325
505
705

24

Low (Red)
Med (Blue)
High (Black)

630
885

1130

625
875

1100

615
850

1070

610
820

1010

580
780
950

30

Low (Red)
Med (Blue)
High (Black)

900

1075
1240

865

1060
1210

830

1030
1170

780
985

1135

740
940

1085

36

Low (Red)
Med (Blue)
High (Black)

1160
1500
1660

1140
1445
1575

1115

1385
1495

1085
1300
1405

990

1200
1390

42

Low (Red)
Med (Blue)
High (Black)

1325
1490
1820

1315
1465
1770

1300
1440
1690

1275
1395
1600

1225
1315
1500

48

Low (Red)
Med (Blue)
High (Black)

1775
1995
2070

1710
1895
1970

1645
1800
1850

1565
1685
1719

1470
1560
1595

60

Low (Red)
Med (Blue)
High (Black)

1675
1965
2140

1630
1925
2085

1580
1875
2000

1520
1800
1895

1450
1695
1795

S

Blower Performance (CFM vs. ESP inches H2O)

S

Cooling speeds should not be reduced below factory setting.

S

Units with electric heat approved at 0.5” maximum and medium blower speed minimum.

Summary of Contents for CBX25UH Series

Page 1: ...12 Table of Contents Shipping and Packing List 1 CBX25UH Series Units 1 Requirements 3 Installation Clearances 3 Installation 4 Condensate Drain 6 Duct System and Filters 7 Connecting Refrigerant Line...

Page 2: ...4 451 17 432 16 1 2 419 20 3 4 527 16 406 5 1 2 140 40 1 2 1029 18 1 2 470 22 559 6 152 14 357 5 1 2 140 13 1 2 343 17 3 4 451 17 432 16 1 2 419 20 3 4 527 16 406 3 5 8 92 inches mm inches mm inches m...

Page 3: ...tely assembled The unit is provided with flanges for the connection of the duct system Do not remove the cabinet knockouts until it has been determined which knockouts will need to be removed for the...

Page 4: ...that is at least 14 from the floor This will allow proper air return HORIZONTAL DRAIN PAN IMPORTANT REMOVE PAN FOR BEST EFFICIENCY AND AIR FLOW UPFLOW DRAIN PAN UPFLOW DRAIN CON NECTIONS BOTH SIDES U...

Page 5: ...Drain Pan Mounting Bracket 018 through 036 REMOVE BRACKETS SECURING BOTH DRAIN PANS TO UNIT Figure 5 Remove Horizontal and Main Drain Pan Mounting Brackets 042 through 060 3 Remove coil assembly bott...

Page 6: ...OR J TRAP 3 4 OVERFLOW DRAIN AIR HANDLER DRAIN PAN WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE A 3 4 19 1MM SECONDARY DRAIN LINE MUST BE S CONNECTED TO SECONDARY DRAIN PAN OR S CONNECTED TO THE OVE...

Page 7: ...trap in the primary drain lines as close to the unit as practical see figure 9 Make sure the top of the trap is below the connection to the drain pan to allow complete drainage of the pan NOTE Horizon...

Page 8: ...he suction and liquid lines from the fittings on the indoor coil to the fittings on the outdoor unit Run the lines in as direct a path as possible avoiding unnecessary turns and bends 2 Make sure that...

Page 9: ...oltage S The power supply must be sized and protected according to the specifications supplied on the product S This air handler is factory configured for 240 volt single phase 60 cycles For 208 volt...

Page 10: ...rating of the air handler If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler the cooling blower speed may need to be changed Refer to blower performance chart...

Page 11: ...d Med Blue High Black 510 670 905 495 650 865 475 630 820 420 595 770 325 505 705 24 Low Red Med Blue High Black 630 885 1130 625 875 1100 615 850 1070 610 820 1010 580 780 950 30 Low Red Med Blue Hig...

Page 12: ...not call for heat Allow up to 5 minutes for all sequencers to cycle off Operation TIME DELAY RELAY Blower time delay operation 1 When cooling demand is initiated there is a 1 second motor on delay 2 A...

Page 13: ...corrected Contact a qualified service technician Cabinet Insulation IMPORTANT DAMAGED INSULATION MUST BE REPAIRED OR REPLACED before the unit is put back into operation In sulation loses its insulati...

Page 14: ...Duct Temperature ___________ THERMOSTAT Adjusted and Programmed Return External Static ______ ______ Total External Static ______ ______ 6 Supply Duct Temperature ___________ Temperature Drop _______...

Page 15: ...Total External Static ______ ______ 6 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature ______...

Page 16: ......

Reviews: