Lennox CBX25UH-024 Installation Instructions Manual Download Page 8

Page 8

NOTE

 - 

Check local codes before connecting the drain 

line to an existing drainage system. Insulate the drain 

lines where sweating could cause water damage.

 

TEST CONDENSATE DRAIN 

Test the drain pan and drain line after installation: 

1 -   Pour several quarts of water into drain pan. Use 

enough water to fill both the drain trap and the line. 

2 -   Check the installed drain pan. Drain pan must be 

draining completely. Drain line fittings must not be 

leaking. Water must be draining from the end of the 

primary drain line. 

3 -  Correct any leaks found.

Duct System and Filters  

DUCT SYSTEM 

The air handler is provided with flanges for the connection 

of the supply plenum. 
Supply and return duct system must be adequately sized 

to meet the system’s air requirements and static pressure 

capabilities. The duct system should be insulated with a 

minimum of 25mm thick insulation with a vapor barrier in 

conditioned areas or 51mm minimum in unconditioned ar-

eas. 

Supply plenum should be the same size as the flanged 

opening provided around the blower outlet and should ex-

tend at least .9m from the air handler before turning or 

branching off plenum into duct runs. The plenum forms an 

extension of the blower housing and minimizes air expan-

sion losses from the blower.

FILTERS

A filter is provided. Table 1 lists the filter size for each unit.

TABLE 1

. Unit Air Filter Size Chart

CBX25UH

Filter Size – Cm 

-018, -024, -030

38 x 51 x 2.5 

-036, -042, -048, -060

46 x 51 x 2.5 

 IMPORTANT

If a high efficiency filter is being installed as part of this 

system to ensure better indoor air quality, the filter must 

be properly sized. High efficiency filters have a higher 

static pressure drop than standard efficiency glass/foam 

filters. If the pressure drop is too great, system capacity 

and performance may be reduced. The pressure drop 

may also cause the limit to trip more frequently during 

the winter and the indoor coil to freeze in the summer, 

resulting in an increase in the number of service 

calls.  Before  using  any  filter  with  this  system,  check 

the  specifications  provided  by  the  filter  manufacturer 

against the data given in the appropriate Lennox Product 

Specifications bulletin. Additional information is provided 

in Service and Application Note ACC002 (August 2000)..

INSTALL CONDENSATE DRAIN

The air handler is provided with 3/4" NPT condensate 

drain connections.

 IMPORTANT

On some pans, the primary and secondary drain holes 

have knockouts.

Confirm primary and secondary drains are open.

1 -   

CBX25UH

 units are equipped with a drain pan, which 

includes green (main drain) and red (secondary 

drain) plugs. Unscrew the plugs to remove them 

before inserting condensate drain fittings.

DRAIN PAN

ALL CBA25UH MODELS

RED SECONDARY

DRAIN PLUG

UNSCREW PLUGS

AND CONNECT

PROPERLY SIZED

FIELD-PROVIDED

FITTINGS AND

DRAIN LINES.

GREEN MAIN

DRAIN PLUG

FIGURE 12

. Drain Line Connections

2 - 

 Install  properly  sized,  field-provided  connection 

fittings and connect primary drain line to the main 

drain pan connection. 

NOTE

 - 

When  installing  drain  line  connection  fittings  to 

the  drain  pan,  hand  tighten  the  fitting  and  use  a  thread 

sealant. Over-tightening the fittings can split connections 

on the drain pan.

 

3 -   If the secondary drain line is to be used, remove the 

plug or the knockout and route the drain line so that 

water draining from the outlet will be easily noticed 

by the homeowner. Refer to local codes for drain 

trap requirements on the secondary drain line. 

4 -   Check again to ensure drain ports and drain pan 

are free of all debris. 

5 -   Plug and check any unused drain pan openings for 

tightness. Torque plugs to 3.4 newton to prevent 

water leaks or seepage from the drain pan. 

6 -   Install a 2" trap in the main (primary) drain lines as 

close to the unit as practical (see figure 10). Make 

sure the top of the trap is below the connection to 

the drain pan to allow complete drainage of the pan. 

NOTE

 - 

Horizontal runs must have an anti-siphon air vent 

(standpipe) installed ahead of the horizontal run. See fig

-

ure 10. An extremely long horizontal run may require an 

oversized drain line to eliminate air traps.

 

NOTE

 - 

Do not operate air handler without a trap in the 

main (primary) drain. The condensate drain is on the 

negative pressure side of the blower; therefore, air being 

pulled through the condensate line will not allow positive 

drainage without a proper trap.

 

7 -   

Route the drain line to the outside or to an 

appropriate drain. Drain lines must be installed so 

they do not block service access to the front of the 

air handler. A 61cm clearance is required for filter, 

coil, or blower removal and service access. 

Summary of Contents for CBX25UH-024

Page 1: ...Check the air handler for shipping damage if found im mediately contact the last carrier Check the unit rating plate to confirm that delivered unit matches order General Information The CBX25UH air ha...

Page 2: ...Page 2 CBX25UH Unit Dimensions Upflow Inches mm...

Page 3: ...e instructions can result in death explosion or fire IMPORTANT Excessive condensation may occur if the unit is installed in a warm humid place When the unit is installed in an unconditioned space appl...

Page 4: ...n HORIZONTAL DRAIN PAN MUST BE REMOVED UP FLOW DOWN FLOW DRAIN PAN FIGURE 1 Upflow Configuration HORIZONTAL APPLICATIONS IMPORTANT When removing the coil there is a possibility of danger of equipment...

Page 5: ...ssembly bottom drain pan and horizontal drain pan as one unit from the air handler FIGURE 5 Remove Coil Assembly Bottom Drain Pan and Horizontal Drain Pan as a Unit 4 Remove the blow off prevention br...

Page 6: ...ck into the air handler FIGURE 8 Slide Coil Assembly Bottom Drain Pan and Horizontal Drain Pan Back Into the Air Handler as a Unit 7 Reinstall the brackets that hold the coil and horizontal drain pan...

Page 7: ...LOCATED ABOVE A FINISHED SPACE THE SECONDARY DRAIN PAN MUST HAVE A LARGER FOOTPRINT THAN THE AIR HANDLER MAIN DRAIN TO APPROVED DRAIN FOR NEGATIVE PRESSURE COILS BLOWER AFTER COIL TRAPS ARE REQUIRED...

Page 8: ...n is provided in Service and Application Note ACC002 August 2000 INSTALL CONDENSATE DRAIN The air handler is provided with 3 4 NPT condensate drain connections IMPORTANT On some pans the primary and s...

Page 9: ...completed WARNING Polyol ester POE oils used with HFC 410A refrigerant absorb moisture very quickly It is very important that the refrigerant system be kept closed as much as possible DO NOT remove li...

Page 10: ...azing slide the rubber grommets over the refrigerant lines until they are away from the heat source NOTE Place wet rags against piping plate and around suction line connections 4 Connect the suction a...

Page 11: ...LLOW FILTER ACCESSIBILITY NOTE CBX25UH SERIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED CHECK THE COIL FOR LEAKS BEFORE INSTALLING REF...

Page 12: ...te electric power supplies before opening access panel Unit may have multiple power supplies WARNING Electric Shock Hazard Can cause injury or death Foil faced insulation has conductive characteristic...

Page 13: ...ND 5 5 Replace the air handler access panel SIDE TOP FIGURE 15 Electrical Connections Upflow Configuration NOTE To avoid the possibility of moisture damage to the control in some right hand discharge...

Page 14: ...U BLK BLK GRN BLUE BLUE BLU BLK GND 1032 1030 1031 1060 NOTES 1 FACTORY SPEED SET TO MEDIUM BLUE FOR 024 030 036 048 AND 060 2 ALL WIRES NOT LABELED ARE PART OF ITEM 1010 240 FIGURE 17 Typical Wiring...

Page 15: ...r filter in place All factory settings are medium speed All data given while air handler is operating with a dry DX coil All downflow applications run on high speed when utilizing electric heat NOTE R...

Page 16: ...eeds High Medium Low Pa in w g L s cfm L s cfm L s cfm 25 0 10 675 1430 597 1265 517 1095 50 0 20 632 1340 562 1190 486 1030 75 0 30 585 1240 521 1105 451 955 100 0 40 533 1130 472 1000 394 835 125 0...

Page 17: ...seconds 4 Motor ramps down to stop 1 SECOND DELAY OFF 100 L s 100 L s 45 SECS COOLING DEMAND 1 2 3 4 FIGURE 20 Blower Time Delay COOLING COOLING ONLY OR HEAT PUMP When the thermostat calls for coolin...

Page 18: ...e cabinet which leads to sheet metal corrosion and subsequently component failure REPAIRING DAMAGED INSULATION Areas of condensation on the cabinet surface are an indi cation that the insulation is in...

Page 19: ...Duct Temperature ___________ THERMOSTAT Adjusted and Programmed Return External Static ______ ______ Total External Static ______ ______ 6 Supply Duct Temperature ___________ Temperature Drop _______...

Page 20: ...ternal Static ______ ______ 6 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature __________ Tem...

Reviews: