background image

Page 10

NOTE

 - 

When installing refrigerant lines longer than 15.2 

meters, see the Lennox Refrigerant Piping Design and 

Fabrication Guidelines, CORP. 9351-L9, or contact Len-

nox Technical Support Product Applications for assis-

tance. To obtain the correct information from Lennox, be 

sure to communicate the following information: Model and 

capacity. 

1 - 

 Route the suction and liquid lines from the fittings 

on the indoor coil to the fittings on the outdoor unit. 

Run the lines in a direct path, avoiding unnecessary 

turns and bends. 

2 -   Make sure that the suction line is insulated over the 

entire exposed length and that neither suction nor 

liquid  lines  are  in  direct  contact  with  floors,  walls, 

duct system, floor joists, or other piping. 

3 -   To avoid damaging the rubber grommets in the 

cabinet while brazing, slide the rubber grommets 

over the refrigerant lines until they are away from 

the heat source. 

NOTE

 - 

Place wet rags against piping plate and around 

suction line connections.

 

4 -   Connect the suction and liquid lines to the evaporator 

coil. Take care to protect the cabinet and internal 

components as detailed in figure 14. 

5 -   

Braze using an alloy of silver or copper and 

phosphorus with a melting point above 1,100°F 

(593°C). 

NOTE 

Do not use soft solder.

 

6 -  Allow refrigerant pipes to cool to room temperature. 

NOTE

 - 

Make sure to route copper refrigerant tubing away 

from sharp edges and make sure that it does not touch 

other metal surfaces. This prevents damage caused by 

vibration or metal-on-metal contact

7 -   Reinstall the rubber grommets into the refrigerant 

piping panel. 

NOTE

 - 

Make sure expansion valve capillary tube is not 

touching metal edges or copper tubing.

 

8 -   Make sure outdoor unit has been placed according 

to the Installation Instructions and is connected to 

the refrigerant lines

Summary of Contents for CBX25UH-024

Page 1: ...Check the air handler for shipping damage if found im mediately contact the last carrier Check the unit rating plate to confirm that delivered unit matches order General Information The CBX25UH air ha...

Page 2: ...Page 2 CBX25UH Unit Dimensions Upflow Inches mm...

Page 3: ...e instructions can result in death explosion or fire IMPORTANT Excessive condensation may occur if the unit is installed in a warm humid place When the unit is installed in an unconditioned space appl...

Page 4: ...n HORIZONTAL DRAIN PAN MUST BE REMOVED UP FLOW DOWN FLOW DRAIN PAN FIGURE 1 Upflow Configuration HORIZONTAL APPLICATIONS IMPORTANT When removing the coil there is a possibility of danger of equipment...

Page 5: ...ssembly bottom drain pan and horizontal drain pan as one unit from the air handler FIGURE 5 Remove Coil Assembly Bottom Drain Pan and Horizontal Drain Pan as a Unit 4 Remove the blow off prevention br...

Page 6: ...ck into the air handler FIGURE 8 Slide Coil Assembly Bottom Drain Pan and Horizontal Drain Pan Back Into the Air Handler as a Unit 7 Reinstall the brackets that hold the coil and horizontal drain pan...

Page 7: ...LOCATED ABOVE A FINISHED SPACE THE SECONDARY DRAIN PAN MUST HAVE A LARGER FOOTPRINT THAN THE AIR HANDLER MAIN DRAIN TO APPROVED DRAIN FOR NEGATIVE PRESSURE COILS BLOWER AFTER COIL TRAPS ARE REQUIRED...

Page 8: ...n is provided in Service and Application Note ACC002 August 2000 INSTALL CONDENSATE DRAIN The air handler is provided with 3 4 NPT condensate drain connections IMPORTANT On some pans the primary and s...

Page 9: ...completed WARNING Polyol ester POE oils used with HFC 410A refrigerant absorb moisture very quickly It is very important that the refrigerant system be kept closed as much as possible DO NOT remove li...

Page 10: ...azing slide the rubber grommets over the refrigerant lines until they are away from the heat source NOTE Place wet rags against piping plate and around suction line connections 4 Connect the suction a...

Page 11: ...LLOW FILTER ACCESSIBILITY NOTE CBX25UH SERIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED CHECK THE COIL FOR LEAKS BEFORE INSTALLING REF...

Page 12: ...te electric power supplies before opening access panel Unit may have multiple power supplies WARNING Electric Shock Hazard Can cause injury or death Foil faced insulation has conductive characteristic...

Page 13: ...ND 5 5 Replace the air handler access panel SIDE TOP FIGURE 15 Electrical Connections Upflow Configuration NOTE To avoid the possibility of moisture damage to the control in some right hand discharge...

Page 14: ...U BLK BLK GRN BLUE BLUE BLU BLK GND 1032 1030 1031 1060 NOTES 1 FACTORY SPEED SET TO MEDIUM BLUE FOR 024 030 036 048 AND 060 2 ALL WIRES NOT LABELED ARE PART OF ITEM 1010 240 FIGURE 17 Typical Wiring...

Page 15: ...r filter in place All factory settings are medium speed All data given while air handler is operating with a dry DX coil All downflow applications run on high speed when utilizing electric heat NOTE R...

Page 16: ...eeds High Medium Low Pa in w g L s cfm L s cfm L s cfm 25 0 10 675 1430 597 1265 517 1095 50 0 20 632 1340 562 1190 486 1030 75 0 30 585 1240 521 1105 451 955 100 0 40 533 1130 472 1000 394 835 125 0...

Page 17: ...seconds 4 Motor ramps down to stop 1 SECOND DELAY OFF 100 L s 100 L s 45 SECS COOLING DEMAND 1 2 3 4 FIGURE 20 Blower Time Delay COOLING COOLING ONLY OR HEAT PUMP When the thermostat calls for coolin...

Page 18: ...e cabinet which leads to sheet metal corrosion and subsequently component failure REPAIRING DAMAGED INSULATION Areas of condensation on the cabinet surface are an indi cation that the insulation is in...

Page 19: ...Duct Temperature ___________ THERMOSTAT Adjusted and Programmed Return External Static ______ ______ Total External Static ______ ______ 6 Supply Duct Temperature ___________ Temperature Drop _______...

Page 20: ...ternal Static ______ ______ 6 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature __________ Tem...

Reviews: