Installation Manual •
COMPACTAIR ADV IOM-MIL157E-0418
2.9.2.- TERMINAL CONNECTION WITH SPLIT UNIT.
2.- INSTALLATION
2.9.- TERMINAL CONNECTION.
¡ IMPORTANT !
THE SHIELDED CONNECTING CABLE BETWEEN THE CONTROL PANEL AND THE UNIT MUST BE SEPARA-
TED FROM ANY OTHER TYPE OF ELECTRICAL WIRING. CONNECT IT TO THE ELECTRIC PANEL LOCATED
IN THE OUTDOOR UNIT.
NOTES:
- For securing and connecting the Control Panel, consult the control panel Manual supplied with the unit.
- Connection between the DC and the unit must be made using shielded twisted pair cables and shielded
(where the
screens is connected to ground by the side of the electrical panel) and with a hose of two cables.
- The Tx+ and Tx- polarity must strictly comply with the electrical diagram supplied with the unit.
- Wiring the hose separated from the power cables a minimum of 500mm.
- Wiring the hose separated from the halogen lamps a minimum of 500mm.
- Wiring the hose separated from switchboard, antennas, transmitters... a minimum of 500mm.
- NEVER ROLL UP THE EXCESSING HOSE, CUT THE HOSE FROM THE SIDE OF THE TERMINAL.