• 24 •
Installation Manual •
COMPACTAIR ADV IOM-MIL157E-0418
Compressor acoustic insulation.
Attenuates the sound level produced by the unit through an insulation that covers the compressor.
Insulation air treatment unit.
This insulation, which covers the indoor unit, provides a
fi
re propagation rating A1.
OTHER OPTIONS.
1.12- OPTIONS.
1.- GENERAL CHARACTERISTICS
REFRIGERANT CIRCUIT.
Service valves.
Refrigerant precharged.
COILS TREATMENT.
Anticorrosion protection condensor & evaporator coils.
Indoor air quality sensor.
The indoor air quality is controlled with the CLIMATIC ™ main controller through a COV (volatile organic compound)
sensor which detects the amount of CO2 in the air between 0 and 2000 ppm. (This value varies depending on the occu-
pancy levels of the space). The sensor sends a signal (0-20 mA) to the controller to modulate the outside air.
Environment remote sensor.
It can be used when you want to regulate through the temperature where the sensor is situated and not through the
return temperature, which is how the standard unit comes out.
Freecooling.
It is a energy saving system through a regulation of dampers, through which outside air is introduced to the local when
the outside temperature is lower than the local. This option is composed of regulating gate or gates and a servomotor.
Available in two versions with an external air damper, or adding a second damper for the return of the local.
Smoke detector.
Three phases relay for unit electrical protection.
ELECTRIC AND SECURING OPTIONS.