• 30 •
1/2”
7/8”
108
5/8”
1-1/8”
177
5/8”
1-3/8”
182
3/4”
1-3/8”
265
3/4”
1-5/8”
271
7/8”
1-5/8”
374
025S
035S
045S 060D 075D 085D 025S
035S
045S 060D 075D 085D
C1
1/2”
5/8”
5/8”
5/8”
5/8”
5/8”
1/2”
5/8”
5/8”
5/8”
5/8”
5/8”
C2
n/a
n/a
n/a
5/8”
5/8”
5/8”
n/a
n/a
n/a
5/8”
5/8”
5/8”
C1
7/8”
1 1/8”
1 3/8”
1 1/8”
1 1/8”
1 3/8”
5/8”
7/8”
1 1/8”
7/8”
7/8”
1 1/8”
C2
n/a
n/a
n/a
1 1/8”
1 3/8”
1 3/8”
n/a
n/a
n/a
7/8”
7/8”
1 1/8”
12
12
12
12
12
12
12
12
12
12
12
12
C1
5/8”
5/8”
3/4”
5/8”
5/8”
3/4”
5/8”
5/8”
3/4”
5/8”
5/8”
3/4”
C2
n/a
n/a
n/a
5/8”
5/8”
3/4”
n/a
n/a
n/a
5/8”
5/8”
3/4”
C1
1 1/8”
1 3/8”
1 5/8”
1 3/8”
1 3/8”
1 5/8”
5/8”
7/8”
1 1/8”
7/8”
7/8”
1 1/8”
C2
n/a
n/a
n/a
1 3/8”
1 5/8”
1 5/8”
n/a
n/a
n/a
7/8”
7/8”
1 1/8”
12
12
18
18
18
18
12
12
18
18
18
18
Installation Manual •
COMPACTAIR ADV IOM-MIL157E-0418
TABLE 1: REFRIGERANT LINES SELECTION
n/a: not available
The unit is supplied with brazing connections. As an option , the unit can be supplied with gas precharge from the fac-
tory ; in that case only the TABLE 2 has to be taken into account. ( this option includes the service valves).
TABLE 2 : EXTRA REFRIGERANT CHARGE R410A BY METER OF COPPER PIPE
Liquid
Gas
gr/m
The unit is precharged from factory with nytrogene . The installer should remove this gas and charge the units
with the charge of refrigerant R410A , shown in the following tables plus the charge by additional meter shown in
the TABLE 2
In the double circuit units , check before connecting C1 and C2 circuits , that they are the same circuit for the indoor
and the outdoor section
REFRIGERANT LINES
UNIT - MODEL
UNIT -MODEL Position A
Vertical line
Total line length
(refrigerant line
length between
indoor and
ourtoor units)
0 to 30 m.
(Standard
conection
unit)
Ø Lquid
Ø Gas
Max. n
er
of bends
30 to 45 m.
Ø Liquid
Ø Gas
Max. n
er
of bends
2.7- REFRIGERANT CONNECTIONS
2.- INSTALLATION
Legislation does not allow refrigerant gas emissions to the atmosphere, so the refrigerants have to be
recycled to avoid being released to the atmosphere. Those recycled refrigerants shall be processed afte-
rwards by an authorized waste manager.
Those components derived from the recycling of the unit have to be managed by authorized waste manager
or be left in local waste facilities according the local normative in each country.