AQUA
4
–AGU-1405-E
- 23 -
Table 3 – General data of AQUA
4
M and AQUA
4
P standard S version from AQUA
4
214 to AQUA
4
324 in nominal conditions :
Unit M (2 pipe) and P (4 pipe) version S
AAH214 AAH244 AAH274 AAH294 AAH324
Cooling at 12/7°C with air ambient at 35°C
Cooling capacity
kW
216.3
236
258.6
295.8
313.8
Total absorbed power
kW
74.6
83.3
91.6
101.9
115.1
EER
2.90
2.83
2.82
2.90
2.73
ESEER
4.44
4.24
4.19
4.33
4.29
Water flow
l/h
37147
40528
44403
50805
53885
Total pressure drop
kPa
57
57
37
47
63
Available pressure head - Pump(s) LP single or normal/backup
switching (option)
kPa
134
169
176
154
127
Available pressure head - Pump(s) HP single or normal/backup
switching (option)
kPa
221
289
295
273
246
Available pressure head - Twin pumps LP parallel operating
(option)
kPa
113
173
183
165
140
Available pressure head - Twin pumps HP parallel operating
(option)
kPa
177
206
215
197
173
Heating at 40/45°C with air ambient at 7°C
Heating capacity
kW
229.4
254.6
280.8
316.6
342.4
Total absorbed power
kW
73.1
78.5
87.5
97.3
108.2
COP
3.14
3.24
3.21
3.25
3.16
Water flow
l/h
39872
44244
48801
55013
59504
Total pressure drop
kPa
66
67
55
67
77
Available pressure head - Pump(s) LP single or normal/backup
switching (option)
kPa
92
139
138
109
81
Available pressure head - Pump(s) HP single or normal/backup
switching (option)
kPa
175
258
256
227
199
Available pressure head - Twin pumps LP parallel operating
(option)
kPa
90
147
149
124
100
Available pressure head - Twin pumps HP parallel operating
(option)
kPa
153
179
181
156
133
Cooling 12/7°C and Heating at 40/45°C
Cooling capacity
kW
217.9
242.9
263.4
302.2
326.1
Heating capacity
kW
281.8
312.8
340.1
388.3
422.3
Total absorbed power
kW
67.2
73.6
80.7
90.6
101.2
TER
7.44
7.55
7.48
7.62
7.40
Water flow of cold circuit
l/h
37426
41722
45233
51902
56007
Water flow of hot circuit
l/h
48977
54367
59098
67488
73387
Available pressure head - Pump(s) LP single or normal/backup
switching (option) - cold circuit
kPa
131
163
173
149
117
Available pressure head - Pump(s) HP single or normal/backup
switching (option) - cold circuit
kPa
218
283
292
268
236
Available pressure head - Twin pumps LP parallel operating
(option) - cold circuit
kPa
112
168
180
161
131
Available pressure head - Twin pumps HP parallel operating
(option) - cold circuit
kPa
176
201
213
193
164
Available pressure head - Pump(s) LP single or normal/backup
switching (option) - hot circuit
kPa
28
93
94
53
14
Available pressure head - Pump(s) HP single or normal/backup
switching (option) - hot circuit
kPa
106
211
212
171
132
Available pressure head - Twin pumps LP parallel operating
(option) - hot circuit
kPa
54
106
111
75
41
Available pressure head - Twin pumps HP parallel operating
(option) - hot circuit
kPa
118
138
143
109
76