AQUA
4
–AGU-1405-E
- 19 -
Table 1 – General data of AQUA
4
M and AQUA
4
P standard S version from AQUA
4
041 to AQUA
4
081 in nominal conditions :
Unit M (2 pipes) et P (4 pipes) version S
AAH041 AAH051 AAH061 AAH071 AAH081
Cooling at 12/7°C with air ambient at 35°C
Cooling capacity
kW
49.7
54.3
65
71.3
81.4
Total absorbed power
kW
15.9
18
20.4
23
26.6
EER
3.13
3.02
3.19
3.10
3.06
ESEER
4.13
4.08
4.24
4.19
4.09
Water flow
l/h
8533
9324
11165
12243
13985
Total pressure drop
kPa
27
31
32
38
31
Available pressure head - Pump(s) LP single or normal/backup
switching (option)
kPa
155
147
138
126
126
Available pressure head - Pump(s) HP single or normal/backup
switching (option)
kPa
190
182
198
189
194
Available pressure head - Twin pumps LP parallel operating
(option)
kPa
128
121
117
107
112
Available pressure head - Twin pumps HP parallel operating
(option)
kPa
178
171
164
154
158
Heating at 40/45°C with air ambient at 7°C
Heating capacity
kW
51.9
57.2
67.9
74.4
84.6
Total absorbed power
kW
16
17.8
20.8
23.2
26.1
COP
3.24
3.21
3.26
3.21
3.24
Water flow
l/h
9022
9945
11794
12930
14701
Total pressure drop
kPa
30
36
36
43
35
Available pressure head - Pump(s) LP single or normal/backup
switching (option)
kPa
144
134
125
110
111
Available pressure head - Pump(s) HP single or normal/backup
switching (option)
kPa
179
169
188
177
183
Available pressure head - Twin pumps LP parallel operating
(option)
kPa
119
111
107
95
101
Available pressure head - Twin pumps HP parallel operating
(option)
kPa
168
159
153
140
145
Cooling 12/7°C and Heating at 40/45°C
Cooling capacity
kW
48.9
53.9
63.6
70.3
82.3
Heating capacity
kW
63.3
70
81.9
90.9
105.5
Total absorbed power
kW
15.1
16.9
19.3
21.7
24.4
TER
7.43
7.33
7.54
7.43
7.70
Water flow of cold circuit
l/h
8395
9259
10916
12077
14138
Water flow of hot circuit
l/h
10993
12168
14237
15798
18336
Available pressure head - Pump(s) LP single or normal/backup
switching (option) - cold circuit
kPa
157
148
140
128
125
Available pressure head - Pump(s) HP single or normal/backup
switching (option) - cold circuit
kPa
191
183
200
191
193
Available pressure head - Twin pumps LP parallel operating
(option) - cold circuit
kPa
129
122
119
109
111
Available pressure head - Twin pumps HP parallel operating
(option) - cold circuit
kPa
179
171
167
156
156
Available pressure head - Pump(s) LP single or normal/backup
switching (option) - hot circuit
kPa
127
112
102
81
78
Available pressure head - Pump(s) HP single or normal/backup
switching (option) - hot circuit
kPa
162
147
171
156
162
Available pressure head - Twin pumps LP parallel operating
(option) - hot circuit
kPa
105
94
89
73
79
Available pressure head - Twin pumps HP parallel operating
(option) - hot circuit
kPa
153
140
134
117
120