Heat exchanger gas unit – ALARM E4
Smart Energy Company
www.systemapolska.pl
Reason
Solution
Poor grounding
Check the grounding
Burner controller faulty
Check burner controller corect operation and / or replace it
Gas valve does not work
1. Check the way of operation the gas supply on the valve,
replace with the orginal one, if it is necessary
2. Main board faulty replace with original spare parts
3. Check the operation of gas valve coils and replace with
original one
4. Check the operation of control unit, replace withoriginal
one if necessary