Fuel changes – valve calibration
Smart Energy Company
www.systemapolska.pl
Module C – G20, 20 mbar, min/max. CO
2
– 7,8 - 8,9%
1. Full open by turning right to the end
2. Set by turning 3.75 turns to the left
3. Target CO
2
– 8.7%
Lo
1. Full open by turning right to the end
2. Set by turning 4 turns to the left
3. Target CO2 – 8.6 %
Hi