background image

506470-01

Issue 1007

START-UP

1.  Rotate fan to check for frozen bearings or binding.

2.  Inspect all factory and field-installed wiring for loose
connections.

3.  After evacuation is complete, open liquid line and suction
line service valves to release refrigerant charge (contained
in outdoor  unit) into system.

4.  Replace the stem caps and secure finger tight, then
tighten an additional 1/6 of a turn.

5.  Check voltage supply at the disconnect switch.  The
voltage must be within the range listed on the unit nameplate.
If not, do not start equipment until the power company has
been consulted and the voltage condition corrected.

6.  Set thermostat for cooling demand, turn on power to
indoor blower, and close the outdoor unit disconnect switch
to start the unit.

7.  Recheck unit voltage with unit running.  Power must be
within range shown on unit nameplate.

Refrigerant Charging

This system is charged with R410A refrigerant which
operates at much higher pressures than R-22.  The liquid
line drier provided with the unit is approved for use with
R410A. Do not replace it with one designed for use with R-
22.  

This unit is NOT approved for use with coils which

use capillary tubes as a refrigerant metering device.

R410A refrigerant cylinders are rose colored.
Refrigerant should be added through the suction valve
in the liquid state.

Certain R410A cylinders are identified as being equipped
with a dip tube.  These allow liquid refrigerant to be
drawn from the bottom of the cylinder without inverting
the cylinder.  Do not turn this type of cylinder upside
down to draw refrigerant.

Units are factory charged with the amount of R410A
refrigerant indicated on the unit rating plate.  This charge is
based on a matching indoor coil and outdoor coil with 15’
line set.  For varying lengths of line set, refer to Table 4 for
refrigerant charge adjustment.  A blank space is provided
on the unit rating plate to list the actual field charge.

If the system is void of refrigerant, clean the system using
the procedure described below.

1.  Use dry nitrogen to pressurized the system and check
for leaks.  Repair leaks, if possible.

2.  Evacuate the system to remove as much of the moisture
as possible.

3.  Use dry nitrogen to break the vacuum.

4.  Evacuate the system again.

5.  Weigh the appropriate amount of R410A refrigerant (listed
on unit nameplate) into the system.

6.  Monitor the system to determine the amount of moisture
remaining in the oil.  Use a test kit to verify that the moisture
content is withing the kit’s dry color range.  It may be
necessary to replace the filter drier  several times to achieve
the required dryness level.  

If system dryness is not

verified, the compressor will fail in the future.

The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur in
the colder months.  The method of charging is determined
by the unit’s 

refrigerant metering device

 and the 

outdoor

ambient temperature.

Measure the liquid line temperature and the outdoor ambient
temperature as outlined below:

Page  13

If unit is equipped with a crankcase heater, it should be
energized 24 hours before unit start-up to prevent
compressor damage as a result of slugging.

  CAUTION

Mineral oils are not compatible with R410A.  If oil must
be added, it must be a polyolester oil.

  IMPORTANT

Table 4

3/8 in.

3 oz. Per 5 ft.

Liquid Line Set
      Diameter

Oz. per 5 ft. adjust
from 15 ft. line set*

Refrigerant Charge Adjustment

*  If line length is greater than 15 ft., add this amount.
   If line length is less than 15 ft., remove this amount.

Summary of Contents for 4HP18LT

Page 1: ...may cause personal injury death or property damage Use appropriate safety gear including safety glasses and gloves when installing this equipment WARNING Installation and servicing of air conditioning...

Page 2: ...S or Canadian Electrical Code Canada Compliance should be determined prior to installation 4HP18LT condensing units use R410A which is an ozone friendly HFC refrigerant The unit must be installed wit...

Page 3: ...This will prevent ice from building up under the unit during a defrost cycle Refer to following roof mounting section for barrier construction if unit must face prevailing winter winds If unit coil ca...

Page 4: ...tion as well as the section that follows entitled Flushing Existing Line Set and Indoor Coil If this unit is being matched with an approved line set or indoor coil which was previously charged with R...

Page 5: ...a tion and the introduction of moisture into the system 3 Use silver alloy brazing rods 5 or 6 silver alloy for copper to copper brazing or 45 silver alloy for copper to brass or copper to steel brazi...

Page 6: ...sure to empty all existing traps Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog thethermalexpansionvalve reducingsystemperformance and capacity Failure...

Page 7: ...Vertical to Horizontal Outside Wall Wood Block Between Studs IMPORTANT Refrigerant lines must not contact wall Vapor Line Liquid Line Wire Tie Inside Wall Strap Sleeve Wire Tie Wire Tie Strap Wood Blo...

Page 8: ...existing system Refer to the gauges after shutdown to confirm that the entire system is completely void of refrigerant Disconnect the liquid and suction lines from the existing outdoor unit If the exi...

Page 9: ...Close the valve on the inverted R 22 cylinder and the gauge set valves Pump the remaining refrigerant out of the recovery machine and turn the machine off 10 Use nitrogen to break the vacuum on the r...

Page 10: ...ak seal To Access the Schrader Port 1 Remove the service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger tigh...

Page 11: ...erant requirements will vary with lenths Check all joints for leaks Purge nitrogen and R410A mixture Correct any leaks and rechecks Evacuation Evacuating the system of noncondensables is critical for...

Page 12: ...nter port hose to a nitrogen cylinder with pressure regulator set to 150 psig and purge the hose Open the manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold g...

Page 13: ...ing plate This charge is based on a matching indoor coil and outdoor coil with 15 line set For varying lengths of line set refer to Table 4 for refrigerant charge adjustment A blank space is provided...

Page 14: ...ure is cool use the weigh in method to charge the unit Do this after any leaks have been repaired 1 Recover the refrigerant from the unit 2 Conduct a leak check then evacuate as previously outlined 3...

Page 15: ...ure from the liquid line temperture to determine the approach temperature Page 15 Table 6 Subcooling Values Table 5 R410A Temperature Pressure Chart T em p F P ressure P sig T em p F P ressure P sig T...

Page 16: ...ecover refrigerant from the system to increase the approach temperature Check Charge Using Normal Operating Pressures Use Table 7 to perform maintenance checks Table 7 is not a procedure for charging...

Page 17: ...506470 01 Issue 1007 Page 17 Table 8 L Liquid S Suction Values provided above are typical pressures Indoor unit matchup indoor air quality equipment and indoor load will case pressures to vary...

Page 18: ...below 50 F System should be left in the emergency heat mode at least 6 hours to allow the crankcase heater sufficient time to prevent compressor slugging Defrost System The defrost system includes two...

Page 19: ...rost mode when the compressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The timed off delay is 5 minutes long The delay helps to pr...

Page 20: ...er of times consecutively pause and then repeat the process The number of consecutive flashes correlates to a paticular abnormal condition TRIP LED Red indicates there is a demand signal from the ther...

Page 21: ...removed from the module TRIP and ALERT LEDs flashing at the same time means control circuit voltage is too low for operation 24VAC Power Wiring The diagnostic module requires a constant nominal 24VAC...

Page 22: ...When the coil is not energized the demand signal input should be less than 0 5VAC Miswired Module Codes Depending on the system configuration some ALERT flash codes may not be active The presence of...

Page 23: ...at the outdoor fan motor compressor and indoor blower motor Values should be compared with those given on unit nameplate Check clean or replace indoor unit filters Check the refrigerant charge and ga...

Page 24: ...t urine cottonwood seeds etc Heat Pump Operation Heat pump units have several characteristics you should be aware of Heat pumps satisfy heating demand by delivering large amounts of warm air into the...

Page 25: ...y heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode Temperature Indicator The temperture indicator display...

Page 26: ...__________ Maximum Fuse or Circuit Breaker ________________________ Electical Connections Tight Indoor Filter Clean Supply Voltage Unit Off __________ Indoor Blower RPM ___________________ S P Drop Ov...

Page 27: ...UIPMENT GROUND HR1 L2 208 230 60 1 L1 K1 1 BLACK YELLOW RED RED C12 ORANGE B4 PURPLE B1 GROUND LUG GROUND L2 L1 208 230 60 1 DUAL CAPACITOR RED COMPRESSOR CONTACTOR BLACK COMPRESSOR CRANKCASE HEATER R...

Page 28: ...506470 01 Issue 1007 Page 28 NOTES...

Reviews: