background image

Page 6

# 48283B006

Figure 8

Refrigerant Line Sets: Installing Vertical Runs (new construction shown)

Outside Wall

Wood Block

Between Studs

IMPORTANT: Refrigerant
lines must not contact wall.

Vapor Line

Liquid Line

Wire Tie

Inside Wall

Strap

Sleeve

Wire Tie

Wire Tie

Strap

Wood Block

Sleeve

Vapor Line Wrapped

with Armaflex

Liquid Line

Caulk

PVC Pipe

Fiberglass
Insulation

Outside Wall

IMPORTANT:

Refrigerant

lines must not

contact structure.

NOTE: Similar installation practices
should be used if line set is to be
installed on exterior of outside wall.

3. Use silver alloy brazing rods (5% or 6% silver alloy for

copper-to-copper brazing or 45% silver alloy for
copper-to-brass or copper-to-steel brazing) which are
rated for use with HCFC-22 refrigerant.

4.

Remove the Schrader core assemblies before brazing
to protect them from damage due to extreme heat.
Replace the cores when brazing is complete.

5. Wrap a wet cloth around the valve body and copper tube

stub to protect them from heat damage during brazing.

6. Braze the line set to the service valve. Quench the joints

with water or a wet cloth to prevent heat damage to the
valve core and opening port. 

The tube end must stay

bottomed in the fitting during final assembly to
ensure proper seating, sealing, and rigidity.

7. Install the factory-supplied fixed orifice (or thermal

expansion valve which is sold separately and which is
approved for use with HCFC-22 refrigerant) in the
liquid line at the indoor coil.

Refrigerant Metering Device

2SCU13 units are designed for use with either fixed orifice
or TXV systems. Refer to the appropriate following section
for information on installing the chosen refrigerant meter-
ing device.

Fixed Orifice Systems

2SCU13 units are shipped with a fixed orifice refrigerant
metering device. Replace the existing indoor unit fixed
orifice with the orifice supplied with this unit. Place the
supplied fixed orifice sticker on the indoor cabinet after
installation. See Table 3 for the proper fixed orifice size for
each unit. In nonstandard applications, the provided fixed
orifice may not be appropriately sized.

Install the fixed orifice as shown in Figure 9. Do not twist cap
tubes when loosening the seal nut from the orifice housing.
Use wrench to back up the distributor.

Expansion Valve Systems

Expansion valves equipped with Chatleff-type fittings are
available from the manufacturer. See Table 4 for proper
TXV for each unit.

Summary of Contents for 2SCU13 Series

Page 1: ...trical shock Disconnect all remote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury or death W...

Page 2: ...or inspection by the carrier s agent If any damages are discovered and reported to the carrier DO NOT INSTALL THE UNIT as claim may be denied Check the unit rating plate to confirm specifications are...

Page 3: ...rcuit connections are made to the low voltage pigtails A complete unit wiring diagram is located inside the unit control box cover see also pages 16 and 17 of this instruction 3 Install room thermosta...

Page 4: ...although vertical lift applications and trapping require ments need to be reviewed with Technical Services for line sets over 50 energy or vibration can be expected Close attention to line set isolat...

Page 5: ...line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter Tape or Wire Tie Wire Tie around vapor line only Refrigerant Line Sets Installing Horizontal Runs Figure 7 Refrigerant Line Sets...

Page 6: ...t damage to the valve core and opening port The tube end must stay bottomed in the fitting during final assembly to ensure proper seating sealing and rigidity 7 Install the factory supplied fixed orif...

Page 7: ...id and Suction Line Service Valves The liquid line and suction line service valves and service ports are used for leak testing evacuating charging and checking charge Each valve is equipped with a ser...

Page 8: ...e line set connections and indoor unit must be checked for leaks Ball Type Service Valve Valve Open Figure 11 Use adjustable wrench To open rotate stem counterclockwise 1 4 turn 90 To close rotate ste...

Page 9: ...HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the HCFC 22 cylinder and the valve...

Page 10: ...d has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and suction line temperatures 6 The ou...

Page 11: ...e F _____ Saturation Temperature F _____ Liquid Line Temperature F _____ Subcooling Value F r o o d t u O p m e T F F 1 g n i l o o c b u S d i u q i L 8 1 4 2 0 3 6 3 2 4 8 4 0 6 5 6 3 1 3 1 7 4 1 5...

Page 12: ...e 7 Approach Values for TXV Systems Approach value is the liquid line temperature minus the outdoor ambient temperature 1 F NOTE For best results use the same digital thermometer to check both outdoor...

Page 13: ...1 8 8 6 2 9 7 8 6 2 4 8 5 6 2 5 8 7 7 2 1 8 F 5 1 1 4 9 2 6 8 7 0 3 5 8 9 9 2 3 8 9 0 3 1 8 8 0 3 5 8 3 0 3 6 8 8 1 3 3 8 C F R e c i f i r O d e x i F F 5 6 4 4 1 3 7 7 4 1 8 6 0 4 1 6 6 0 5 1 7 6 7...

Page 14: ...or correct voltage at unit with unit operating 6 Check amp draw outdoor fan motor Unit nameplate _________ Actual _________ NOTE If owner complains of insufficient cooling the unit should be gauged an...

Page 15: ...nician ________________________________________ Nameplate Voltage ______________ Rated Load Ampacity ________ Compressor _______________ Outdoor Fan ___________________ Maximum Fuse or Circuit Breaker...

Page 16: ...OCAL CODES OUTDOOR FAN F C H 1 2 3 R S C C 2 3 1 EQUIPMENT GROUND HR1 L2 208 230 60 1 L1 K1 1 BLACK YELLOW RED RED C12 BLACK ORANGE B4 PURPLE K1 S4 S24 A4 C Y1 TO 24 VAC POWER SOURCE 20 VA MINIMUM NEC...

Page 17: ...2 L3 EQUIPMENT GROUND HR1 S40 K1 1 BLACK BLACK B1 BLACK ORANGE BLACK B4 C1 PURPLE RED 1 FOR USE WITH COPPER CONDUCTORS ONLY REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURR...

Page 18: ...the only warranty made by the warrantor this warranty is in lieu of and excludes all other warranties express or implied The warrantor does not authorize any person to provide any other warranty or to...

Reviews: