background image

# 48283B006

Page 7

To install an expansion valve (see Figure 9):

1. Separate the distributor assembly and remove the

piston orifice and used teflon seal. Insert nozzle end of

Figure 9

Metering Device Installation

the expansion valve along with a new teflon seal into the
distributor and tighten to 20 – 30 ft. lbs. Use backup
wrench on all wrench flats. 

Overtightening will crush

the teflon seal and may cause a leak.

2. Attach liquid line portion of distributor assembly along

with new teflon seal to the inlet of the expansion
valve. Tighten to 20 – 30 ft. lbs. Use backup wrench
on all wrench flats. 

Overtightening will crush the

teflon seal and may cause a leak.

3. Connect the external equalizer line to the equalizer

port on the suction line and tighten to 8 ft. lbs.

4. Strap the superheat sensing bulb to the suction header.

If installing an expansion valve on an indoor coil that
previously used a fixed orifice, be sure to remove the
existing fixed orifice. Failure to remove a fixed orifice
when installing an expansion valve to the indoor coil will
result in improper operation and damage to the system.

Manifold Gauge Set

When checking the unit charge, use a manifold gauge set
that is equipped with “low loss” hoses. Do not use a manifold
gauge set with anything other than a “low loss” hose.

Liquid and Suction Line Service Valves

The liquid line and suction line service valves and service
ports are used for leak testing, evacuating, charging, and
checking charge.

Each valve is equipped with a service port which has a
factory-installed Schrader valve (see Figure 10 on page 8).
A service port cap protects the Schrader valve from con-
tamination and serves as the primary leak seal.

To Access the Schrader Port:

1. Remove the service port cap with an adjustable wrench.

2. Connect gauge to the service port.

3. When testing is completed, replace service port cap.

Tighten finger tight, then an additional 1/6 turn.

To Open Liquid or Suction Line Service Valve:

1. Remove stem cap with an adjustable wrench.

2. Use a service wrench with a hex-head extension to

back the stem out counterclockwise  as far as it will
go. Use a 3/16" hex head extension for liquid line
service valves and a 5/16" extension for suction line
service valves.

3. Replace the stem cap. Tighten finger tight, then

tighten an additional 1/6 turn.

Fixed Orifice Data

Table 3

l

e

d

o

M

t

r

a

P

r

e

b

m

u

N

l

l

i

r

D

e

z

i

S

8

1

-

3

1

U

C

S

2

7

0

-

4

8

4

0

0

1

3

5

0

.

4

2

-

3

1

U

C

S

2

2

1

-

4

8

4

0

0

1

2

6

0

.

0

3

-

3

1

U

C

S

2

9

1

-

4

8

4

0

0

1

0

7

0

.

6

3

-

3

1

U

C

S

2

4

2

-

4

8

4

0

0

1

6

7

0

.

2

4

-

3

1

U

C

S

2

0

3

-

4

8

4

0

0

1

2

8

0

.

8

4

-

3

1

U

C

S

2

8

3

-

4

8

4

0

0

1

1

9

0

.

0

6

-

3

1

U

C

S

2

5

4

-

4

8

4

0

0

1

9

9

0

.

Table 4

TXV Data

l

e

d

o

M

t

r

a

P

r

e

b

m

u

N

6

3

-

,

0

3

-

,

4

2

-

,

8

1

-

3

1

U

C

S

2

4

3

K

6

2

8

4

-

,

2

4

-

3

1

U

C

S

2

5

3

K

6

2

0

6

-

3

1

U

C

S

2

1

0

M

1

9

Summary of Contents for 2SCU13 Series

Page 1: ...trical shock Disconnect all remote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury or death W...

Page 2: ...or inspection by the carrier s agent If any damages are discovered and reported to the carrier DO NOT INSTALL THE UNIT as claim may be denied Check the unit rating plate to confirm specifications are...

Page 3: ...rcuit connections are made to the low voltage pigtails A complete unit wiring diagram is located inside the unit control box cover see also pages 16 and 17 of this instruction 3 Install room thermosta...

Page 4: ...although vertical lift applications and trapping require ments need to be reviewed with Technical Services for line sets over 50 energy or vibration can be expected Close attention to line set isolat...

Page 5: ...line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter Tape or Wire Tie Wire Tie around vapor line only Refrigerant Line Sets Installing Horizontal Runs Figure 7 Refrigerant Line Sets...

Page 6: ...t damage to the valve core and opening port The tube end must stay bottomed in the fitting during final assembly to ensure proper seating sealing and rigidity 7 Install the factory supplied fixed orif...

Page 7: ...id and Suction Line Service Valves The liquid line and suction line service valves and service ports are used for leak testing evacuating charging and checking charge Each valve is equipped with a ser...

Page 8: ...e line set connections and indoor unit must be checked for leaks Ball Type Service Valve Valve Open Figure 11 Use adjustable wrench To open rotate stem counterclockwise 1 4 turn 90 To close rotate ste...

Page 9: ...HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the HCFC 22 cylinder and the valve...

Page 10: ...d has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and suction line temperatures 6 The ou...

Page 11: ...e F _____ Saturation Temperature F _____ Liquid Line Temperature F _____ Subcooling Value F r o o d t u O p m e T F F 1 g n i l o o c b u S d i u q i L 8 1 4 2 0 3 6 3 2 4 8 4 0 6 5 6 3 1 3 1 7 4 1 5...

Page 12: ...e 7 Approach Values for TXV Systems Approach value is the liquid line temperature minus the outdoor ambient temperature 1 F NOTE For best results use the same digital thermometer to check both outdoor...

Page 13: ...1 8 8 6 2 9 7 8 6 2 4 8 5 6 2 5 8 7 7 2 1 8 F 5 1 1 4 9 2 6 8 7 0 3 5 8 9 9 2 3 8 9 0 3 1 8 8 0 3 5 8 3 0 3 6 8 8 1 3 3 8 C F R e c i f i r O d e x i F F 5 6 4 4 1 3 7 7 4 1 8 6 0 4 1 6 6 0 5 1 7 6 7...

Page 14: ...or correct voltage at unit with unit operating 6 Check amp draw outdoor fan motor Unit nameplate _________ Actual _________ NOTE If owner complains of insufficient cooling the unit should be gauged an...

Page 15: ...nician ________________________________________ Nameplate Voltage ______________ Rated Load Ampacity ________ Compressor _______________ Outdoor Fan ___________________ Maximum Fuse or Circuit Breaker...

Page 16: ...OCAL CODES OUTDOOR FAN F C H 1 2 3 R S C C 2 3 1 EQUIPMENT GROUND HR1 L2 208 230 60 1 L1 K1 1 BLACK YELLOW RED RED C12 BLACK ORANGE B4 PURPLE K1 S4 S24 A4 C Y1 TO 24 VAC POWER SOURCE 20 VA MINIMUM NEC...

Page 17: ...2 L3 EQUIPMENT GROUND HR1 S40 K1 1 BLACK BLACK B1 BLACK ORANGE BLACK B4 C1 PURPLE RED 1 FOR USE WITH COPPER CONDUCTORS ONLY REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURR...

Page 18: ...the only warranty made by the warrantor this warranty is in lieu of and excludes all other warranties express or implied The warrantor does not authorize any person to provide any other warranty or to...

Reviews: