background image

Page 8

Common Venting Using Tile−Lined Masonry Chimney

TILE−LINED

MASONRY

CHIMNEY

PERMANENTLY
SEALED FIREPLACE
OPENING

FURNACE

OTHER

APPLIANCE

FIGURE 6

B VENT

VENT

ADAPTER

ASSEMBLY

1 FOOT

MINIMUM

(2 ft.

preferred)

 8 − When an exterior masonry chimney is being used,

the furnace must be commonly vented with at least
one other drafthood−equipped gas−fired appliance.

 9 − Continue with furnace installation, start−up and

adjustments as outlined in furnace installation
instructions.

NOTE − Furnace blower heating speed should be
adjusted so that temperature rise is at the high
end of the range listed on the unit rating plate.

10 − Test the operation of the blocked vent switch.

CAUTION − Ensure good ventilation of the area
where the furnace is installed before performing
this test.

 a − Remove double−walled B−vent from top of vent

adapter assembly.

 b − Adjust  room  thermostat  to  signal  heating

demand.

 c − Allow furnace to operate for 2 minutes, then

completely cover the top of the vent adapter
assembly outlet to simulate a vent blockage.
Furnace should shut off within 2 minutes.

 d − Remove blockage and 

allow unit to cool for 5

minutes

. Press reset button on blocked vent

switch. Reinstall double−walled vent pipe. Adjust
thermostat to normal setting.

11 − Test the furnace for proper draft and spillage.

 a − Inspect  the  venting  system  for  proper  size  and

horizontal pitch. Determine that there is no

blockage, restriction, leakage, corrosion, or other
deficiencies which could cause an unsafe
condition.

 b − Close all building doors and windows and all

doors between the space in which the
appliances remaining connected to the common
venting system are located and other spaces of
the building. Turn on clothes dryers and any
appliances not connected to the common
venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate
a summer exhaust fan. Close fireplace dampers.

 c − Follow the lighting instructions. Turn on the

appliance that is being inspected. Adjust the
thermostat so that the appliance operates
continuously.

 d − After the main burner has operated for 5

minutes, test for leaks of flue gases at the draft
hood or vent adapter relief opening. Use the
flame of a match or candle, or smoke from a
cigarette, cigar, or pipe.

 

− After determining that each appliance

connected to the common venting system is
venting properly, (step 3) return all doors,
windows, exhaust fans, fireplace dampers, and
any other gas−burning appliances to their
previous mode of operation.

 f − If a venting problem is found during any of the

preceding tests, the common venting system
must be modified to correct the problem.

Summary of Contents for 18M7901

Page 1: ...80AF1UH ML180UH EL280UH and SL280UH units installed in masonry chimney vent applications in accordance with limitations set by NFPA 54 and the International Mechanical Code The included vent tables a...

Page 2: ...10 F 12 C Pittsburgh 1 F 17 C Salt Lake City 3 F 16 C St Louis 2 F 17 C Requirements The room temperature surrounding the furnace and vent connectors must be at least 60 F 16 C The space surrounding t...

Page 3: ...nector per table 3 and figure 2 when a single appliance is being vented into an interior masonry chimney Size the chimney and vent connector per tables 4 and 5 and figure 3 when using an interior or e...

Page 4: ...le Lined Masonry Chimney Serving a Single 80AF1UH ML180UH EL280UH or SL280UH Furnace Equipped with Vent Adapter Kit and One or More Drafthood Equipped Appliances Typical Application Shown FIGURE 3 TIL...

Page 5: ...70 8 1 2 3 105 127 145 148 179 206 210 240 276 10 1 2 3 108 129 148 153 184 209 216 247 281 15 1 2 3 114 134 153 164 192 215 229 260 292 20 1 2 3 119 138 157 173 199 222 239 270 301 30 1 2 3 127 145 1...

Page 6: ...sing mortar or brick must be replaced Tile liner and top seal must be in good condition If necessary make repairs All debris mortar tile fuel oil residue etc must be removed from chimney clean out Til...

Page 7: ...g sheet metal screws to firmly secure the vent adapter assembly to the round collar of the unit flue transition Drive one self drilling screw through the front and one through each side of the vent ad...

Page 8: ...al setting 11 Test the furnace for proper draft and spillage a Inspect the venting system for proper size and horizontal pitch Determine that there is no blockage restriction leakage corrosion or othe...

Reviews: