The maximum recommended chimney height in all
applications which include the vent adapter is 35 feet
(10.6m).

Vent connector from the vent adapter to the tile−lined
chimney must be constructed of type B, double−wall vent
pipe.

The furnace vent connector rise shall not exceed 3 feet
(.9m).

Vent connector lateral length must not exceed 18"
(457mm) for each inch of vent connector diameter. For
example, a  6" (152mm) diameter vent connector would
have a maximum lateral length of 9 feet (2.7m).

Vent connectors should not be sized more than two sizes
greater than the listed appliance categorized vent
diameter, flue collar diameter, or drafthood outlet

diameter.
The vent  sizing tables allow for two 90° turns. For each
additional turn, or equivalent, reduce the maximum
capacity listed in the venting tables by 10 percent (.90 X
maximum table capacity).
Interpolation is permitted when calculating capacities for
vent dimensions that fall between table entries; however,
extrapolation beyond the table entries is not permitted.
Size the chimney and vent connector per table 3 and
figure 2 when a single appliance is being vented into an
interior masonry chimney. Size the chimney and vent
connector per tables 4 and 5 and figure 3 when using an
interior or exterior masonry chimney as a common vent
serving multiple appliances.
Use table 6 to determine the equivalent area of masonry
chimney liners.

TABLE 3

Interior Masonry Chimney Only

Type B Double Wall Vent Connector Serving a Single 80AF1UH, ML180UH, EL280UH or SL280UH Furnace 

with Masonry Chimney Vent Adapter Kit

Vent

Height

H

(ft)

Lateral

L

(ft)

Type B Double Wall Vent Connector Diameter  − (inches)

to be used with chimney areas within the size limits at bottom

6 in.

7 in.

8 in.

Appliance  Input Rate in Thousands of Btu per Hour

NAT
Max

NAT
Max

NAT
Max

6

2
5

130

117

180
165

247
231

8

2
5
8

145
134
127

198
183
175

266
247
239

10

2
5
8

162
148
139

221
204
191

298
277
263

15

2
5

10
12

179
164
153
148

250
231
216
210

336
313
296
290

20

2
5

10
12

210
184
172
167

274
254
237
230

375
350
332
325

30

2
5

10
12

216
198
184
179

303
281
263
255

421
393
373
365

35

2
5

10
12

225
206
192
186

315
291
273
265

435
406
386
378

MASONRY CHIMNEY INTERNAL AREA

Minimum internal area of chimney (in. 

2

)

38

50

63

Maximum internal area of chimney (in. 

2

)

198

269

352

Summary of Contents for 18M7901

Page 1: ...80AF1UH ML180UH EL280UH and SL280UH units installed in masonry chimney vent applications in accordance with limitations set by NFPA 54 and the International Mechanical Code The included vent tables a...

Page 2: ...10 F 12 C Pittsburgh 1 F 17 C Salt Lake City 3 F 16 C St Louis 2 F 17 C Requirements The room temperature surrounding the furnace and vent connectors must be at least 60 F 16 C The space surrounding t...

Page 3: ...nector per table 3 and figure 2 when a single appliance is being vented into an interior masonry chimney Size the chimney and vent connector per tables 4 and 5 and figure 3 when using an interior or e...

Page 4: ...le Lined Masonry Chimney Serving a Single 80AF1UH ML180UH EL280UH or SL280UH Furnace Equipped with Vent Adapter Kit and One or More Drafthood Equipped Appliances Typical Application Shown FIGURE 3 TIL...

Page 5: ...70 8 1 2 3 105 127 145 148 179 206 210 240 276 10 1 2 3 108 129 148 153 184 209 216 247 281 15 1 2 3 114 134 153 164 192 215 229 260 292 20 1 2 3 119 138 157 173 199 222 239 270 301 30 1 2 3 127 145 1...

Page 6: ...sing mortar or brick must be replaced Tile liner and top seal must be in good condition If necessary make repairs All debris mortar tile fuel oil residue etc must be removed from chimney clean out Til...

Page 7: ...g sheet metal screws to firmly secure the vent adapter assembly to the round collar of the unit flue transition Drive one self drilling screw through the front and one through each side of the vent ad...

Page 8: ...al setting 11 Test the furnace for proper draft and spillage a Inspect the venting system for proper size and horizontal pitch Determine that there is no blockage restriction leakage corrosion or othe...

Reviews: