background image

Page 2

FIGURE 1

−10

o

F

−10

o

F

5

o

F

17

o

F

27

o

F

37

o

F

37

o

F

27

o

F

17

o

F

5

o

F

−10

o

F

99% Winter Design Temperatures for the Contiguous United States

This map is a necessarily generalized guide to temperatures in the contiguous Unites States. Temperatures shown for areas such as
mountainous regions and large urban centers may not be accurate. The data used to develop this map was taken from the 1993 ASHRAE
Fundamentals Handbook (Chapter 24, Table 1: Climate Conditions for the United States.
This map has been reprinted with permission from NFPA 54: National Fuel Gas Code 

1999, National Fire Protection Association, Quincy,

MA 02269. This reprinted material is not the complete and official position of the National Fire Protection Association on the referenced subject,
which is represented only by the standard in its entirety.

Table 2 lists winter design temperatures for some of the
major U. S. cities.

TABLE 2

Minimum Winter Design Temperatures

of Major U. S. Cities

City

Minimum Winter Design

Temperature −− °F (°C)

Baltimore

+10°F (−12°C)

Boston

+6°F (−14°C)

Chicago

−8°F (−22°C)

Columbus, OH

0°F (−18°C)

Des Moines

−10°F (−23°C)

Detroit

+3°F (−16°C)

Kansas City

+2°F (−17°C)

New York

+11°F (−12°C)

Philadelphia

+10°F (−12°C)

Pittsburgh

+1°F (−17°C)

Salt Lake City

+3°F (−16°C)

St. Louis

+2°F (−17°C)

Requirements

The room temperature surrounding the furnace and vent
connectors must be at least 60°F (16°C).

The space surrounding the furnace must not be
depressurized by more than 0.2" w.c. below the outdoor
pressure (caused by exhaust fans, clothes dryers, etc.)
Furnace capacity must not exceed 1.7 times the
calculated heating load.
Sea level input ratings should be used when determining
maximum capacity for high altitude installation.
If the furnace is to be vented into an exterior chimney, the
furnace must share a common vent with at least one
drafthood−equipped appliance to prevent condensation in
the masonry chimney.
If the furnace is to be vented into an interior chimney, the
furnace may be vented as a single appliance or into a
shared vent.

Chimney and Vent Connector 
Requirements and Sizing

The masonry chimney vent adapter kit may only be used
in applications which include vent exit through the
furnace top cap. Applications which require side vent
exit are not permissible.
When two or more appliances are vented into a single
masonry chimney, the flow area of the largest section of
vertical vent shall not exceed seven times the flow area
of the vent adapter outlet or drafthood outlet , 

whichever

is smaller

, unless the vent is designed in accordance

with approved engineering methods.

Summary of Contents for 18M7901

Page 1: ...80AF1UH ML180UH EL280UH and SL280UH units installed in masonry chimney vent applications in accordance with limitations set by NFPA 54 and the International Mechanical Code The included vent tables a...

Page 2: ...10 F 12 C Pittsburgh 1 F 17 C Salt Lake City 3 F 16 C St Louis 2 F 17 C Requirements The room temperature surrounding the furnace and vent connectors must be at least 60 F 16 C The space surrounding t...

Page 3: ...nector per table 3 and figure 2 when a single appliance is being vented into an interior masonry chimney Size the chimney and vent connector per tables 4 and 5 and figure 3 when using an interior or e...

Page 4: ...le Lined Masonry Chimney Serving a Single 80AF1UH ML180UH EL280UH or SL280UH Furnace Equipped with Vent Adapter Kit and One or More Drafthood Equipped Appliances Typical Application Shown FIGURE 3 TIL...

Page 5: ...70 8 1 2 3 105 127 145 148 179 206 210 240 276 10 1 2 3 108 129 148 153 184 209 216 247 281 15 1 2 3 114 134 153 164 192 215 229 260 292 20 1 2 3 119 138 157 173 199 222 239 270 301 30 1 2 3 127 145 1...

Page 6: ...sing mortar or brick must be replaced Tile liner and top seal must be in good condition If necessary make repairs All debris mortar tile fuel oil residue etc must be removed from chimney clean out Til...

Page 7: ...g sheet metal screws to firmly secure the vent adapter assembly to the round collar of the unit flue transition Drive one self drilling screw through the front and one through each side of the vent ad...

Page 8: ...al setting 11 Test the furnace for proper draft and spillage a Inspect the venting system for proper size and horizontal pitch Determine that there is no blockage restriction leakage corrosion or othe...

Reviews: