507270-03
Page 21 of 60
Issue 1917
Table 6A.
A95UH1D and 95G1UH-P Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 - 4,500 ft
Number of
90° Elbows
Used
2" Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
070
090
110
135
045
070
090
110
135
045
070
090
110
135
1
76
61
39
19
n/a
110
95
63
38
n/a
132
132
113
113
109
2
71
56
34
14
105
90
58
33
127
127
108
108
104
3
66
51
29
9
100
85
53
28
122
122
103
103
99
4
61
46
24
n/a
95
80
48
23
117
117
98
98
94
5
56
41
19
90
75
43
18
112
112
93
93
89
6
51
36
14
85
70
38
13
107
107
88
88
84
7
46
31
9
80
65
33
8
102
102
83
83
79
8
41
26
n/a
75
60
28
n/a
97
97
78
78
74
9
36
21
70
55
23
92
92
73
73
69
10
31
16
65
50
18
87
87
68
68
64
Standard Termination Elevation 4,501 - 10,000 ft
Number of
90° Elbows
Used
2" Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
070
090
110
135
045
070
090
110
135
045
070
090
110
135
1
76
61
39
n/a
n/a
110
95
63
38
n/a
132
132
113
113
109
2
71
56
34
105
90
58
33
127
127
108
108
104
3
66
51
29
100
85
53
28
122
122
103
103
99
4
61
46
24
95
80
48
23
117
117
98
98
94
5
56
41
19
90
75
43
18
112
112
93
93
89
6
51
36
14
85
70
38
13
107
107
88
88
84
7
46
31
9
80
65
33
8
102
102
83
83
79
8
41
26
n/a
75
60
28
n/a
97
97
78
78
74
9
36
21
70
55
23
92
92
73
73
69
10
31
16
65
50
18
87
87
68
68
64
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.
Summary of Contents for 045-08
Page 3: ...507270 03 Page 3 of 60 Issue 1917 Parts Arrangement Figure 1 ...
Page 24: ...507270 03 Page 24 of 60 Issue 1917 Figure 25 Figure 26 ...
Page 38: ...507270 03 Page 38 of 60 Issue 1917 Figure 58 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Page 44: ...507270 03 Page 44 of 60 Issue 1917 Figure 67 Typical Wiring Diagram ...