A93UH1D / 92G1UH 110*C16 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High
Medium-High
Medium-Low
Low
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
0.00
2030
905
1750
805
1425
665
1225
530
0.10
1950
865
1755
770
1430
630
1215
515
0.20
1935
840
1675
735
1455
610
1230
505
0.30
1885
810
1660
685
1410
585
1200
485
0.40
1830
780
1585
645
1385
570
1190
470
0.50
1750
740
1565
630
1320
535
1165
455
0.60
1660
695
1485
585
1280
505
1105
425
0.70
1540
665
1380
555
1230
485
1060
405
0.80
1420
615
1290
520
1140
445
945
375
0.90
1290
575
1175
470
1045
410
850
350
A93UH1D / 92G1UH 110*C20 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
Bottom Return Air, Side Return Air with Optional Return Air Base,
Return Air from Both Sides or Return Air from Bottom and One Side.
Single Side Return Air -
Air volumes in
bold
require field fabricated
transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper
air velocity.
High
Medium-High
Medium-Low
Low
High
Medium-High
Medium-Low
Low
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
0.00
2395
1265
2250
1055
2020
875
1725
715
2570
1390
2300
1110
1990
905
1685
725
0.10
2410
1250
2215
1025
1980
855
1730
705
2490
1345
2220
1090
1970
890
1650
710
0.20
2370
1220
2180
995
1950
830
1670
685
2415
1325
2170
1060
1925
880
1620
700
0.30
2270
1190
2120
975
1885
810
1635
670
2335
1270
2115
1025
1865
850
1605
685
0.40
2185
1160
1995
945
1835
790
1605
660
2230
1235
2055
1005
1820
825
1565
675
0.50
2115
1120
1955
925
1760
765
1545
640
2160
1200
1995
975
1755
795
1510
650
0.60
2020
1100
1865
885
1721
745
1485
615
2065
1155
1875
925
1690
770
1455
630
0.70
1910
1065
1765
855
1630
720
1425
600
1945
1100
1800
900
1595
735
1425
620
0.80
1815
1025
1675
825
1555
695
1330
575
1850
1060
1700
865
1515
715
1315
590
0.90
1680
1000
1575
805
1440
670
1275
565
1700
1025
1590
835
1430
690
1210
565
A93UH1D / 92G1UH 135*D20 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
Bottom Return Air, Side Return Air with Optional Return Air Base,
Return Air from Both Sides or Return Air from Bottom and One Side.
Single Side Return Air -
Air volumes in
bold
require field fabricated
transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper
air velocity.
High
Medium-High
Medium-Low
Low
High
Medium-High
Medium-Low
Low
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
0.00
2455
1300
2225
1055
2000
890
1730
725
2480
1410
2240
1160
1955
900
1650
735
0.10
2410
1260
2220
1045
1970
865
1755
710
2450
1380
2240
1130
1885
890
1660
725
0.20
2350
1235
2170
1020
1945
840
1710
695
2370
1345
2160
1075
1930
865
1630
715
0.30
2260
1200
2100
985
1915
815
1675
680
2350
1310
2120
1065
1895
845
1620
700
0.40
2135
1160
2050
955
1825
795
1655
660
2225
1265
2080
1030
1800
830
1605
690
0.50
2095
1135
1950
930
1805
785
1575
640
2165
1220
1985
1000
1775
805
1580
670
0.60
1980
1085
1875
895
1720
750
1540
625
2065
1185
1905
960
1715
775
1460
625
0.70
1885
1055
1820
870
1680
725
1480
610
1985
1140
1810
930
1665
755
1460
625
0.80
1810
1030
1690
830
1580
690
1405
590
1885
1110
1695
885
1600
735
1440
610
0.90
1690
995
1620
800
1505
670
1360
565
1800
1075
1540
850
1515
705
1335
580
NOTE
: All air is measured external to unit without filter (filter not furnished - field provided)
Summary of Contents for 045-08
Page 3: ...507270 03 Page 3 of 60 Issue 1917 Parts Arrangement Figure 1 ...
Page 24: ...507270 03 Page 24 of 60 Issue 1917 Figure 25 Figure 26 ...
Page 38: ...507270 03 Page 38 of 60 Issue 1917 Figure 58 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Page 44: ...507270 03 Page 44 of 60 Issue 1917 Figure 67 Typical Wiring Diagram ...