A95UH1D / 95G1UH 090*C12 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High
Medium-High
Medium-Low
Low
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
0.00
1630
715
1345
590
1090
475
885
385
0.10
1615
700
1320
580
1070
465
890
380
0.20
1580
675
1305
570
1070
455
890
370
0.30
1525
620
1295
535
1060
435
890
360
0.40
1480
615
1275
515
1055
430
885
350
0.50
1415
565
1220
485
1030
410
860
330
0.60
1350
535
1175
450
1005
390
835
310
0.70
1260
505
1115
415
955
360
785
290
0.80
1190
480
1010
380
880
325
740
285
0.90
1060
435
930
360
795
295
655
250
A95UH1D / 95G1UH 090*C16 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High
Medium-High
Medium-Low
Low
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
0.00
2140
880
1895
780
1590
645
1350
550
0.10
2110
850
1880
760
1585
635
1360
545
0.20
2060
810
1835
725
1580
620
1360
520
0.30
1990
765
1805
690
1550
585
1365
495
0.40
1925
750
1755
655
1510
545
1330
470
0.50
1830
700
1680
610
1455
525
1285
450
0.60
1720
645
1610
575
1390
480
1230
415
0.70
1600
615
1525
535
1300
465
1165
390
0.80
1455
560
1410
495
1195
430
1035
365
0.90
1300
515
1305
465
1100
390
900
320
A95UH1D / 95G1UH 110*C16 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High
Medium-High
Medium-Low
Low
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
0.00
2000
910
1675
765
1360
635
1185
525
0.10
1980
895
1650
745
1370
610
1180
505
0.20
1935
855
1600
710
1400
590
1170
485
0.30
1875
830
1560
680
1370
570
1160
490
0.40
1800
785
1490
655
1325
545
1120
455
0.50
1725
720
1400
610
1295
515
1080
435
0.60
1630
685
1335
585
1185
480
1030
410
0.70
1530
665
1290
525
1100
435
940
385
0.80
1410
610
1190
485
985
400
790
365
0.90
1245
560
1000
430
925
380
715
315
NOTE
: All air is measured external to unit without filter (filter not furnished - field provided)
Summary of Contents for 045-08
Page 3: ...507270 03 Page 3 of 60 Issue 1917 Parts Arrangement Figure 1 ...
Page 24: ...507270 03 Page 24 of 60 Issue 1917 Figure 25 Figure 26 ...
Page 38: ...507270 03 Page 38 of 60 Issue 1917 Figure 58 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Page 44: ...507270 03 Page 44 of 60 Issue 1917 Figure 67 Typical Wiring Diagram ...