Wiring
Power and Network connections:
1. Plug the unit into a standard outlet for 120VAC operation using the C13 to 5-15P power cord. For 208VAC
operation, plug the unit into an IEC C13 socket using the C13 to C14 power cord.
The system will be usable in approximately
10 seconds.
2. Connect a network cable to the unit’s Protocessor input. The Protocessor is the network server.
The Protocessor is pre-loaded with Lencore’s System Manager. System Manager allows
adjustment to the masking characteristics.
The unit includes a rear panel terminal block for the connection of an optional UPS. The
UPS output would connect to the terminal block: +24VDC to pin 2 and 24V COM to pin 3. When a
UPS is not used, jumpers In+ to Out+ and In- to Out- must be installed.
Use a UL 864 listed power supply for the UPS. The UPS must be 24VDC regulated until the power
supply batteries are exhausted. Lencore's PSM7A meets these requirements.
Incorporate a safety margin into the calculated amp-hour rating of 20%.
Maximum battery amp hour capacity supported by the charger to be 24 hours minimum.
Normal and alarm standby load is 100mA.
For US installations, the alarm time period is 15 minutes and for Canadian installations, the alarm time
period is 2 hours.
UPS
connection:
5