background image

Page 4/15 

28October2022/Version 7 

LEM reserves the right to carry out modifications on its transducers, 

 

in order to improve them.

LEM International SA 

Route du Nant-d’Avril, 152

1217 Meyrin 

 www.lem.com

ITZ 5000-S FLEX ULTRASTAB

Electrical data

At 

T

A

= 25 °C unless otherwise noted.

Parameter

Symbol

Unit

Min

Typ

Max

Comment

Primary continuous direct current

I

P N DC

A

−5000

5000

Primary nominal RMS current 

1)

I

P N

A

5000

See graphs on 

page 5

Primary current, measuring range

I

P M

A

−7072

7072

See graphs on 

page 6

Measuring resistance

R

M

Ω

0

1.5

Secondary current

I

S

A

−2

2

Turns ratio

N

P

/

N

S

1:2500

Resistance of secondary winding

R

S

Ω

4.3

Primary withstand peak current (max) 

1)

Î

P max

kA

25

Mains supply RMS voltage

V

100

240

Rated power supply frequency

f

Hz

50/60

Power consumption 

I

P

= 0 A 

@ Mains supply = 230 V RMS

P

C

VA

38 

82

Average 

Peak

Power consumption 

I

I

P N DC 

 (5000 A) 

@ Mains supply = 230 V RMS

P

C

VA

76 

116

Average 

Peak

RMS noise current 0 … 10 Hz 

2)

I

no

ppm

0.02

RMS noise current 0 … 10 kHz 

2)

2.5

RMS noise current 0 … 100 kHz 

2)

20

Re-injected RMS noise on primary bus bar 

0 ... 100 kHz

µV

10

Electrical offset current 

3)

I

O E

ppm

−2

2

Temperature coefficient of 

I

O E 

3)

TCI

O E

ppm/K

−0.1

0.1

10 °C .. 40 °C

Offset stability 

3)

ppm/month

−1

1

Linearity error 

3)

ε

L

ppm

−3

3

Delay time @ 90 % of the final output 

value 

I

P N DC

 step

t

D 90

µs

1

With a  

d

i

/d

t

 ≥ 20 A/µs

Frequency bandwidth (± 3 dB)

BW

kHz

0

80

Small-signal 

bandwidth, 

1 % of 

I

P N

 

DC

d

i

/d

accurately followed

d

i

/d

t

A/µs

20

Notes: 

1)

  With cable length < 12 meters (see graphs page 4)  

 

2)

  Single pulse of 100 ms only, not AC. The transducer may require a few seconds to return to 

 

  normal operation when autoreset system is running 

 

3)

  All ppm figures refer to full-scale which corresponds to a secondary current (

I

S

) output of 2 A.

Summary of Contents for ITZ 5000-S FLEX ULTRASTAB

Page 1: ...9 pin D sub male output connector Secondary current monitoring on BNC connector 4 mm banana sockets for secondary current output Full featured indicator panel Advantages Very high accuracy Excellent...

Page 2: ...required cleaning by dry compressed air is authorized This transducer is a build in device whose hazardous live parts must be inaccessible after installation This transducer must be mounted in a suit...

Page 3: ...ons over voltage cat III pollution degree 2 Rated insulation RMS voltage reinforced insulation UNm V 2000 IEC 61010 1 conditions over voltage cat III pollution degree 2 RMS voltage for AC insulation t...

Page 4: ...ion IP 0 A Mains supply 230 V RMS PC W VA 38 82 Average Peak Power consumption IP IP N DC 5000 A Mains supply 230 V RMS PC W VA 76 116 Average Peak RMS noise current 0 10 Hz 2 Ino ppm 0 02 RMS noise c...

Page 5: ...40 45 50 RM 0 5 RM 1 RM 1 5 Cable length m provided by LEM Primary nominal RMS current versus Cable length TA 0 to 55 C Primary nominal RMS current A Primary nominal RMS current versus cable length Pr...

Page 6: ...000 4000 3000 2000 1000 0 1000 2000 3000 4000 5000 6000 7000 8000 0 5 10 15 20 25 30 35 40 45 50 RM 0 5 RM 1 RM 1 5 Cable length m provided by LEM Primary current measuring range versus Cable length T...

Page 7: ...them LEM International SA Route du Nant d Avril 152 1217 Meyrin www lem com ITZ 5000 S FLEX ULTRASTAB Typical power consumption 0 10 20 30 40 50 60 70 80 90 6000 5000 4000 3000 2000 1000 0 1000 2000...

Page 8: ...d LED This LED is lit when the transducer head saturates due to excessive primary current 600 A 24000 A yellow LED These LEDs are lit when a transducer head with the corresponding full scale range is...

Page 9: ...tatus Interlock signal outputs 9 pin D Sub male UNC 4 40 screw lock 8 Option A B These positions are for future expansion or customization not used 2 8 3 1 7 6 5 4 LEM International SA Route du Nant d...

Page 10: ...is wired it can be Active Low or Active High as shown below In the Diagram A Active Low Output the output signal Uout switches to GND when the corresponding LED is ON In the Diagram B Active High Outp...

Page 11: ...ducer head is not saturated High IP UC The primary current is higher than 105 of nominal full scale output 0 2 V The primary current is lower than 105 of nominal full scale output ACTIVE UC The primar...

Page 12: ...off When the rack electronics temperature cools to approximately 60 C the measuring circuit is automatically re enabled and the status LED is again lit Over current protection Electrical specification...

Page 13: ...AC peak becomes lower than the trip level indicated in the table above Transducer head description Connect the transducer head to the electronics rack using the supplied transducer head cable The sid...

Page 14: ...ransducer head European Schuko CEE 7 7 and US Japanese mains cables 2 m each with three pole IEC C13 female connector Short plug for 4 mm banana terminals and 15 pin D Sub short plug for analog output...

Page 15: ...modifications on its transducers in order to improve them LEM International SA Route du Nant d Avril 152 1217 Meyrin www lem com ITZ 5000 S FLEX ULTRASTAB Dimensions Rack electronics in mm general tol...